IMDTouchKnowledge BaseShop main store

Troubleshooting

How WinCC Flexible License Authorization Transfer to a Panel Works

HMI and touchscreens Published 5 min read

Short answer

Transferring authorization to an HMI device moves a license for a panel option package such as SmartService onto the panel, and it is independent of the WinCC flexible installation. The 14-day license transfers only once and is spent. When the unlimited license does not appear at the destination, check whether it is still at the source before transferring again.

On this page
  1. What does transfer authorization to an HMI device do?
  2. Why does the unlimited license not appear in the destination drive?
  3. How many times can the 14-day license be transferred?
  4. Can you transfer authorization after installing WinCC flexible?
  5. How do you verify where every license ended up?
  6. What does the "wrong step 7 product number" error mean?
  7. Questions asked

WinCC flexible keeps two kinds of licensing apart: the licenses that run the engineering software on the PC, and the authorizations that option packages need on the panel itself. File > Transfer > Authorization moves the second kind — a license for a panel option package such as SmartService — from the authorization disk onto the HMI device. The transfer is independent of the WinCC flexible installation, so it works before or after setup. Two limits decide most of what goes wrong here: the 14-day license can be transferred once and is then spent, and a running transfer dialog is not proof that the license arrived. The same setup session can also end on the "wrong step 7 product number" error during installation, so that fix closes this article.

What does transfer authorization to an HMI device do? #

It moves a license from the authorization disk onto the panel so an installed option package that requires its own authorization can run; SmartService is one such package, and the project download is not part of this function.

In WinCC flexible the function sits at File > Transfer > Authorization. Option packages on the panels can require an authorization of their own, and SmartService is the confirmed example; whether a different package needs one is a property of that package, so its own documentation is the list to trust. The transfer writes a license to the HMI device only — carrying the configured project to the panel is a separate runtime download, and why an HMI edit needs a new runtime download covers that side of it. The licenses that run the engineering software stay on the PC under different rules; WinCC RT and RC licenses and moving a runtime key covers that PC-side mechanism.

Why does the unlimited license not appear in the destination drive? #

The visible transfer process does not prove the license was written, so the first check is the source: if the unlimited license still sits on the authorization disk, the transfer never committed, and only that state justifies a retry.

The symptom — the transfer runs, the destination drive shows no license — fits several causes: an incompatible or damaged license, an already consumed one, or a destination that is not the panel you think it is. The symptom does not separate them, and the next action does not depend on which one it is:

  • List the licenses on the source drive and on the panel, and count them at each end.
  • Unlimited license still at the source: the panel never received the write. Confirm the destination is the intended panel, retry once, and recount.
  • License at neither end: stop retrying — a repeated transfer cannot recover a license that is nowhere.

How many times can the 14-day license be transferred? #

Once — the 14-day license accepts a single transfer and is then spent, so it must never be used to test the transfer path, because the test itself consumes the only move it will ever make.

The two types on the authorization disk behave differently: the 14-day license moves exactly once and is finished, while the unlimited license is the one meant for a panel that stays in service. If a 14-day license refuses a second transfer, that is the single-use limit doing its job, not a fault to troubleshoot. Decide before you touch it whether the short-term need is real, because after the transfer there is no undo and no second move.

Can you transfer authorization after installing WinCC flexible? #

Yes — the authorization transfer is completely independent of the software installation, so it works after setup, and reinstalling WinCC flexible is not a remedy for a failed or missing transfer.

Install first and transfer later, or transfer before the software exists: both orders are valid, which is why a transfer problem is never solved by reinstalling. When a transfer misbehaves, the fault lives in the license media, the license state, or the destination, and none of those is touched by setup.

How do you verify where every license ended up? #

Count licenses at both ends before and after each transfer: the source count plus the destination count must equal what the authorization disk held, and any license missing from both ends is lost, not hidden.

Worked example with illustrative counts — an authorization disk holding 2 licenses, one 14-day and one unlimited, and a panel holding none:

  • Start: source = 2, panel = 0, total = 2.
  • Transfer the 14-day license once: source = 2 − 1 = 1, panel = 0 + 1 = 1, total = 2. Transfers left on that license: 1 − 1 = 0, spent.
  • Transfer the unlimited license: the process runs, then source = 1, panel = 1, total = 2. Nothing is lost — the write to the panel simply did not commit.

The numbers give the decision. The unlimited license is still at the source, so one retry after confirming the destination is correct. If that retry ends with source = 0 and panel = 0, the license is lost at both ends and only a replacement authorization restores it.

What does the "wrong step 7 product number" error mean? #

It means the integration option checked the installed STEP 7 product during WinCC flexible setup and rejected the pairing — reported with SIMATIC Manager version 5.3 — and the workaround is to install standalone first and add integration afterwards.

The message appears during setup when you select "integration to step7". What the product-number check compares is not spelled out in the message, and the fix does not need it:

  1. Install WinCC flexible with the STEP 7 integration option cleared.
  2. After the standalone installation completes, select the STEP 7 integration separately.
  3. Verify that WinCC flexible opens and that the integration can be selected without the same "wrong step 7 product number" message.

The error is an installation-time integration pairing problem. It does not affect authorization transfer, which behaves the same with or without integration installed.

Questions asked

Is the 14-day license good enough for a production panel?

Only for a short-term need. The license runs for its 14 days and can never be transferred again, so a production panel left with it loses the option package authorization when that period ends. Move the unlimited license for any panel that stays in service, and keep the 14-day one as a one-shot spare you may choose never to spend. If the unlimited transfer keeps failing, fix that path first.

The unlimited license is gone from both the disk and the panel. What now?

That is a lost license, not a hidden one, and repeating the transfer cannot bring it back. Request a replacement authorization through the vendor's licensing support or your distributor, with proof of purchase for the original. Do not accept recovered keys or key generators from outside the vendor's channel; a replacement obtained that way is exactly what the license terms exclude.

Do I have to transfer the authorization before downloading the project?

The authorization licenses the option package; it does not gate the project download itself, so the panel will take the project with or without it. What waits is the package: it requires its own authorization to run, so move the unlimited license before you rely on the package's functions in production.

Keep reading

  • Comparison

    WinCC V7.4, WinCC Flexible 2008 and TIA Portal Compared

    WinCC V7.x is PC-based SCADA software, WinCC Flexible 2008 engineers operator panels and single PC stations and is discontinued as a standalone tool, and WinCC inside TIA Portal is the successor engineering platform alongside STEP 7. Decide by the target device and the exact project files on your engineering workstation, not by the shared WinCC name. STEP 7 is the PLC tool, not a WinCC product.

    HMI and touchscreens

  • How-to

    How to migrate a WinCC flexible project to TIA Portal

    One TIA Portal installation replaces both STEP 7 Classic and WinCC flexible, but the two project types move differently: the STEP 7 V5.x project is imported, and the WinCC flexible 2008 project is migrated through an intermediate release because the newest TIA Portal versions no longer offer that migration. Verify the exact S7-300 CPU and panel against the device lists and license STEP 7 and WinCC Comfort separately.

    HMI and touchscreens

  • Comparison

    TIA Portal vs STEP 7 plus WinCC hardware configuration

    Configuring the same PLC and HMI in TIA Portal instead of STEP 7 plus WinCC needs no extra PLC, panel, module or network hardware — the cabinet stays exactly as it is. The difference is where devices, networks and tags are configured: one integrated project instead of two. The one hard limit: S7-1200 and S7-1500 CPUs engineer only in TIA Portal, and CPU firmware sets the minimum release, so a V2.9 CPU needs TIA Portal V17 or higher.

    HMI and touchscreens

Starting WinCC Flexible RT Failed on an MP277 Panel