HMI and touchscreens Published 7 min read

Short answer

A .fwx extracted from a panel backup runs under WinCC flexible Runtime on a PC but cannot be copied onto an MP277 or opened in the engineering tool. Compilation and transfer are one-way services, so the fix is to match image version, clear storage, and do a clean transfer from the Engineering System with upload enabled.

On this page
  1. What each file actually is
  2. Check 1: Locate the failure
  3. Check 2: Image version and target match
  4. Check 3: Storage and the manual-copy trap
  5. Which recovery path returns an editable project
  6. Worked example: this MP277 8-inch panel
  7. Transfer procedure and verification
  8. Questions asked

Your .fwx runs under WinCC flexible Runtime on a PC and drives the PLC, but the same file dropped onto the MP277 by hand gives Starting WinCC flexible RT failed every time. That combination points at the transfer mechanism, not at the project: compilation and download are one-way services of the Engineering System (ES), and a manual copy performs none of the steps a transfer performs. The fix is a clean ES transfer after checking image version, target match and storage.

What each file actually is #

Three artifacts matter, and they are not interchangeable:

Artifact Produced by Contents Editable in ES
.hmi WinCC flexible ES Screens, tags, connections, scripts — the source Yes
.fwx ES compiler Compiled, device-specific runtime binary No
Panel backup ProSave or the panel's backup function Complete device content: image, project, recipes, settings No, restore only

The ES cannot open, import or convert a .fwx; there is no decompiler in the product family, so the plan of turning the runtime file back into a WinCC flexible project ends here. The second constraint is equally hard: PC runtime is an execution engine with no transfer function, so it cannot download anything to the panel either. A panel backup restores a whole device; it is not a project you can edit or send selectively.

Check 1: Locate the failure #

Run the compiled project on a PC with WinCC flexible Runtime against the same PLC.

  • Runtime starts and tags follow the PLC — the binary is intact and the connection configuration is correct. The fault is local to the panel: image version, storage or a broken project directory. Go to Check 2.
  • Runtime refuses the file or reports a version error — the file is truncated or was compiled for a different target. Go to Check 2 for the target check, then recompile from source if you have it.

The panel runs the same runtime kernel, but loads it from the Windows CE image in flash instead of a PC installation. Once the project executes elsewhere against the same controller, every remaining variable lives inside the panel.

Check 2: Image version and target match #

The panel runtime rejects a project compiled by an ES newer than the installed image. The rule is one-directional: the image on the device must be at least as new as the ES that generated the .fwx.

Read the image version on the panel via the Loader's control panel, on the device information page, and compare it against the version the OS update function in ProSave reports for the connected device. If the device image is older, run the OS update and re-transfer. If versions match or the device is newer, version is excluded and you move to storage.

An OS update that completes cleanly and leaves the error unchanged is still a diagnostic result: the update overwrites the runtime image but leaves the flash file system and the stored project untouched, so it cannot repair a corrupt project directory. That outcome moves the fault onto the project files.

Also confirm the target. The device node in the ES project tree must name your exact MP277 variant; a project compiled for a different MP277 size or another panel family aborts at start on this hardware.

Check 3: Storage and the manual-copy trap #

Check free storage memory on the panel's control panel. You need room for the .fwx plus headroom for recipes and logs; if it is low, delete old recipes, logs and the previous project through ProSave before transferring.

Transfer is a transaction, not a file copy. The panel's transfer service writes the .fwx, installs the option and driver components the project references, updates the startup pointer the Loader's Start button reads, and clears the previous project's files. Dragging the Simatic folder across from a USB stick performs none of those four actions, so the Loader still points at a project that is absent, stale or incomplete — which is exactly the failure you are seeing. Remove all hand-copied content first; the leftovers keep the failure alive through subsequent transfers.

If a clean transfer still fails, treat the flash file system as suspect and run the OS update with the reset-to-factory-settings option, which reformats before writing the image. That erases everything on the device, so back up first if the panel still answers on the transfer channel.

Which recovery path returns an editable project #

Situation Action Result
Archived .hmi exists Open in ES, compile for your MP277 variant, transfer Full edit and full recovery
No .hmi, upload was enabled at last download Upload from the panel over the transfer channel ES rebuilds the .hmi from the stored compressed source
No .hmi, upload was disabled Re-transfer the identical .fwx from the station that built it, or restore a matching backup Panel runs, no editing possible
Backup from a healthy panel ProSave restore Image, project, recipes and settings in one operation

Upload runs over the transfer channel with the device sitting in the Loader, so it does not require the runtime to start. A panel stuck at Starting WinCC flexible RT failed can still surrender its source. If the ES reports no project on the device, the transfer that installed this project had upload cleared, and nothing on the panel brings the source back. Leaving upload cleared is bad practice on any machine that will outlive its engineering PC.

Worked example: this MP277 8-inch panel #

Inputs, from the case as reported:

  • The .fwx runs correctly under PC runtime against the same PLC, so the binary and connection data are good.
  • The Simatic folder was copied to the panel by hand from a USB stick, and the OS update was already run without changing the error.
  • No .hmi archive is mentioned; the backup was taken through the panel itself.

The rule: when PC runtime runs the project and an OS update changes nothing, the remaining causes are the hand-copied project directory and the startup pointer. The fix sequence is: delete the copied Simatic content from the panel flash, put the panel in transfer mode from the Loader, configure the ES transfer settings for the same channel and address with upload enabled, then compile and transfer from the ES and press Start in the Loader.

Two outcomes follow. If the original engineering station or a .hmi archive still exists, that transfer restores full editing and the problem is closed. If the only artifact is the .fwx extracted from the backup and upload was never enabled, the ES cannot accept a download of a compiled file and no editable project can be recovered from this panel — the panel runs only after the identical .fwx is transferred cleanly from the station that built it, or a matching backup is restored. If neither station nor backup exists and the panel is beyond repair, a replacement unit such as an industrial panel PC running the same visualization becomes the fallback, with the project rebuilt from the running system's tags and screens.

Transfer procedure and verification #

  1. Back up first if the panel answers: complete backup via ProSave, saved off-device.
  2. Clear the wreckage: remove hand-copied folders, or run the OS update with reset to factory settings when the project directory contents are unknown.
  3. Put the panel in transfer mode from the Loader, with the channel enabled.
  4. Use one channel: MPI/PROFIBUS with the panel's station address, or Ethernet/USB on the second channel.
  5. Match the ES transfer settings to the same mode and address, and enable upload.
  6. Compile, then transfer. Watch the ES output through to the completion message; a transfer that stops early leaves you in exactly the failure state you started with.
  7. Let the panel return to the Loader and press Start.

Verify in this order: the ES reports transfer complete; the Loader's Start launches the project without the error; tags track the PLC live. If any step fails, the outcome table in the previous section tells you which path remains.

Safety note: before pulling the panel out of service or wiping it with a factory reset, confirm the machine cannot start unexpectedly — the operator station losing its runtime is a stop condition you should plan, not discover.

Questions asked

Can I open a .fwx file in WinCC flexible to edit and re-download it?

No. A .fwx is the compiled runtime binary the engineering tool generates; the toolchain has no decompiler, so WinCC flexible ES cannot open, import or convert it. To get an editable project you need the original .hmi source archive, or the panel must have had upload enabled when the project was downloaded, which lets the ES rebuild the .hmi over the transfer channel.

Why did the OS update not clear the Starting WinCC flexible RT failed message?

An OS update overwrites the Windows CE runtime image but leaves the flash file system and any stored project files untouched. If the project directory is corrupt or half-written from a manual file copy, a clean image cannot repair it. Run the OS update with the reset-to-factory-settings option, which reformats the flash before writing, then transfer the project again from the engineering station.

Does the panel backup file restore the project if the runtime will not start?

Yes. The backup taken by ProSave or the panel is a restore archive of the whole device: image, project, recipes and settings. Restoring it with ProSave puts the panel back to the state it was in, runtime included. It does not give you an editable project, and it only helps if the backup came from a panel that was working.

Where do I enable upload so the source can be recovered later?

In the engineering tool, before the transfer, in the transfer settings dialog, check the upload option. The stored compressed source is the only field-recoverable copy of the project. Leaving it cleared saves a little flash but means that if the engineering PC or its project archive is lost, the panel cannot give the source back.

Keep reading

  • Troubleshooting

    How WinCC Flexible License Authorization Transfer to a Panel Works

    Transferring authorization to an HMI device moves a license for a panel option package such as SmartService onto the panel, and it is independent of the WinCC flexible installation. The 14-day license transfers only once and is spent. When the unlimited license does not appear at the destination, check whether it is still at the source before transferring again.

    HMI and touchscreens

  • Troubleshooting

    Use the Transfer Dialog Not a NetPro Connection for HMI Download

    Put the panel's IP address in the WinCC flexible transfer dialog and start the Ethernet transfer from there. A connection in NetPro or the communications palette configures runtime data exchange with the controller, not the download path. If the panel does not switch to transfer mode automatically, select transfer mode manually from its startup menu after power-up; the failing MPI discovery is a separate interface with its own addressing.

    HMI and touchscreens

  • How-to

    Redownloading an HMI Project After a User Lockout

    Yes — WinCC flexible 2008 SP3 opens and converts an SP2 project, and the converted project downloads to the panel. The lockout itself only clears if you remove the failed-login limit in the project and transfer with the option that replaces user administration on the panel; a plain application download leaves the locked account in place.

    HMI and touchscreens