Why WinCC Logging for Runtime Advanced asks for a license

HMI and touchscreens Published 6 min read

Short answer

The message means the runtime computer holds no valid option key for historical logging; the base WinCC Runtime Advanced license never covers it. Order WinCC Logging for Runtime Advanced (6AV2107-0GA00-0BB0), one per operator station, and install or transfer the key with Automation License Manager; keys from generators or copied folders do not clear it.

On this page
  1. What the message is really saying
  2. Confirm the diagnosis on the runtime computer
  3. The license this message asks for
  4. Install and transfer the key the documented way
  5. Before reinstalling or replacing the runtime PC
  6. Example: one Advanced logging station against the Professional included tags
  7. Questions asked

Your data log is blocked because historical logging is a separately licensed option in WinCC Runtime Advanced. The base runtime license covers displaying and operating the visualization and nothing more; the moment a project with a configured data log is compiled, the licensing check looks for the option key on the runtime computer and reports it missing. No setting in TIA Portal removes that check. The message clears only when a valid key for WinCC Logging for Runtime Advanced (ordering reference 6AV2107-0GA00-0BB0) sits in a license storage location the runtime reads, placed there with Automation License Manager. Keys from generators or copied from another installation are not valid entitlements and change nothing, so the path below is the documented one: confirm the diagnosis, order the option, transfer the key, verify the build.

What the message is really saying #

WinCC licensing has two layers. The runtime license authorizes the visualization to execute at all; an option license authorizes one added function, and historical logging — archiving selected process values for trends and later retrieval — is such a function. An engineering installation working normally proves nothing about the second layer, because the check does not run against the engineering software. It compares the functions configured in the project against the keys installed on the computer that will run the project.

That explains the pattern you see: everything else runs, and only the data log fails. It also explains why installing more keys changes nothing. The check accepts only keys issued for that exact product; a key for a different product, a damaged key, or one the vendor never issued leaves the same message on screen no matter how often it is installed.

Confirm the diagnosis on the runtime computer #

Work through these three checks before any purchase, because the conditions in the table below look identical on screen and need different remedies.

  1. Write down the exact license name in the message; the Advanced option is named WinCC Logging for Runtime Advanced, and that full name is what you order against.
  2. Read the runtime edition configured in the project and the runtime installed on the target computer; both must be Runtime Advanced, because the same data log on a Professional runtime is a different licensing case.
  3. Open Automation License Manager on the computer that executes the runtime — not only on the engineering laptop — and read the inventory: product names, counts and status of every key.
What Automation License Manager shows What it means The remedy
No logging key on the machine The option was never licensed for this station Order the option named in the message
A key named WinCC Logging RT Professional It belongs to the Professional runtime edition and does not satisfy an Advanced runtime Leave it in place; order the Advanced option, or move the project to a Professional runtime
The Advanced logging key with an error status Present but damaged or incomplete Stop and use the vendor's repair and recovery route, with the purchase documents at hand

The license this message asks for #

The product to order is WinCC Logging for Runtime Advanced, an option for WinCC (TIA Portal) with ordering reference 6AV2107-0GA00-0BB0. The product information sets the rule for Runtime Advanced: one license is required per operator station, counted by the job each station does — every runtime computer that runs the logging needs its own key, and a computer that only displays needs none. Give the supplier the runtime edition, the installed WinCC version and the complete text of the diagnostic, and the reference itself does not change. The project needs no modification: the compile that failed passes as soon as a valid key is in place.

Install and transfer the key the documented way #

Automation License Manager is the tool that administers Siemens license keys and the storage locations they live on. A key is a managed object with a product name and a status, not a loose file: copying folders or restoring a disk image is not a license transfer, and whether a key may move at all depends on its license type.

  1. Connect the license medium and start Automation License Manager on the runtime computer.
  2. Select the keys to move and open the Transfer License Key dialog from the License Key menu, targeting a storage location the runtime reads, normally the local hard disk; the full sequence is in the guide to transfer a WinCC license from USB key to hard disk.
  3. Confirm in the inventory that the key's product name matches the message and its status shows no error.
  4. Recompile the project and start the runtime; the data log builds without the message. Restart the runtime during a planned stop, because the operator loses the screen while it comes back up.

Before reinstalling or replacing the runtime PC #

A new disk or a replacement computer changes the licensing picture, so treat project data and licenses as two separate jobs:

  1. Back up the project, runtime settings and archive data, and verify that HMI project data is inside your platform backup; a backup restores engineering data, never keys.
  2. Record the license inventory in Automation License Manager — product names, counts, statuses — and file the purchase documents with it, so every entitlement can be named without the old Windows installation.
  3. Transfer the keys with the documented procedure to a permitted destination before the old disk is formatted.
  4. If a key refuses to transfer or reports damage, stop there and request license recovery from the vendor, quoting the purchase documents, instead of reinstalling over it.

Example: one Advanced logging station against the Professional included tags #

The case at hand: one runtime computer running WinCC Runtime Advanced, compiling its first data log, with the message on screen.

Inputs

  • Logging operator stations on Runtime Advanced: 1 (the computer in this case).
  • Documented rule (product information): WinCC Runtime Advanced requires one WinCC Logging for Runtime Advanced license per operator station.
  • Documented comparison (product information): WinCC Runtime Professional already includes 500 logging tags; take a Professional project configured at exactly that count as the comparison input.

Rule in words: multiply Advanced logging stations by the per-station requirement; on Professional, subtract the included tags from the configured tags.

Arithmetic

  • Advanced path: 1 operator station × 1 license per operator station = 1 license, ordered as 6AV2107-0GA00-0BB0.
  • Professional comparison: 500 configured logging tags − 500 included logging tags = 0 tags needing an additional logging option.

Result: the Advanced station needs the option purchased; the Professional comparison needs no additional logging purchase, with zero tags of headroom at its configured count.

Decision: order exactly one WinCC Logging for Runtime Advanced license for this station, and one for every further Advanced station that logs, from the first logged tag onward. Count tags instead of stations only if the project moves to Runtime Professional: at or below the included tag count the runtime license covers logging; above it, the Professional logging option joins the order.

Questions asked

Does the message mean the logging function was never installed?

No. The logging function ships inside WinCC Runtime Advanced, and the purchase is a license key only; the data sheet describes it as a single license without software and without documentation. Nothing is downloaded into TIA Portal beyond placing a valid key in a storage location the runtime computer reads.

The key is installed but the message still appears. What should I check?

Three things. The key must sit in a license storage location on the runtime computer itself, not only on the engineering laptop. Its product name must match the message, because a Professional logging key does not satisfy an Advanced runtime. And the project must be recompiled and the runtime started after the transfer, since the licensing check runs at that point.

When does this licensing check actually run?

When a project with a configured data log is compiled, against the keys installed on the computer that will run the project. A project that only displays live values never triggers it, which is why an installation can run for months and then ask for the license the first time someone adds historical logging.

Can the license move when the panel PC is replaced later?

Transfer rights depend on the license type purchased, so keep the license medium and the purchase documents for the life of the station. The documented route is a transfer with Automation License Manager to the new computer before the old disk is wiped; a disk image restore is not a license transfer.

Keep reading

  • Troubleshooting

    Why WinCC Flexible Logging Fails to Create Oracle Tables

    Oracle is not among the databases tested and released for WinCC flexible, so the table-definition and insert statements the runtime generates were never validated there. The startup message covers only initialization. Archive to a released database and transfer committed records to Oracle with a separate, restart-safe service.

    HMI and touchscreens

  • How-to

    Transfer a WinCC license from USB key to hard disk

    Open Automation License Manager, confirm the USB key and the local disk both appear as drives, right-click each WinCC license on the key and run the License Key > Transfer command to the local disk. A transfer is a managed move, not a file copy: the license must leave the key and appear on the disk with valid status, after which the station no longer needs the key.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Deactivates When the Alarm Report Fails

    Runtime deactivates because the copied project's Alarm Logging message sequence report job has no valid printer or file output on the new PC, and the stored computer name no longer matches. A missing MPI cable does not shut Runtime down. Fix the print job, set a default printer, correct the computer entry, and run Project Migrator on a copy when moving from 6.0 to 7.0.