How-to
Connecting a PanelView 550 2711-B5A2 to an SLC 5/03 over DH-485
Short answer
Connect the PanelView 550 2711-B5A2 to the SLC 5/03 over DH-485 — drop cable or 1747-AIC trunk, one node address per device, 150 Ω termination at both trunk ends — then download a two-screen PanelBuilder32 trial application over the RS-232 port with a null-modem cable and prove the link by forcing a value into N7:0, writing into N7:1 from the terminal and pulsing B3:0/0.
On this page
The 2711-B5A2 PanelView 550 joins the SLC 5/03 over DH-485 at 19.2 kbps: link the terminal's DH-485 RJ45 to channel 1 of the controller with a drop cable or a 1747-AIC trunk, give the SLC node address 1 and the terminal node address 2, then download a two-screen trial application from PanelBuilder32 over the RS-232 port with a null-modem cable. Prove the link before building real screens: force a value into a spare word, write one back from the terminal, and pulse a spare bit. That takes an unused terminal from bare cables to a verified application in one shift, and because every address in the trial is a spare you choose, nothing in the running program changes.
What the terminal does on the process #
The 2711-B5A2 is a monochrome keypad operator station for a DH-485 network. Its screens read data-table addresses out of the SLC and write operator entries back into them: a numeric display shows a process value, a numeric entry sets a setpoint, a pushbutton starts or stops a drive or gate, and an alarm screen lists what has faulted. On a plant where the process runs mostly unattended, that is the whole justification for the unit: a few screens replace door-mounted pushbuttons, selector switches and pilot lights, and they report stage and fault information to an operator who walks the line instead of watching it from a control room. If the terminal powers up and its DH-485 port answers, commissioning it is worth an afternoon; the trial application below proves every path before you invest in real screens.
What you need #
- The terminal: a PanelView 550, catalog 2711-B5A2, the DH-485 version with the RS-232 port for transfers; the label inside the unit shows its firmware, 2.01 on the terminal this procedure was written against.
- The controller: an SLC 5/03 with channel 1, its DH-485 port, free for this terminal.
- RSLogix 500 online with the controller, to watch the data table during the tests.
- PanelBuilder32, catalog 2711-ND3, on a PC with a working serial COM port, real or on a USB adapter.
- A null-modem RS-232 transfer cable, catalog 2711-NC13 or an equivalent you build yourself.
- A DH-485 RJ45 drop cable to connect terminal to controller: catalog 1747-C11 or 1747-C20.
- For a trunk longer than one drop cable, or for more devices: a 1747-AIC link coupler with Belden 3106A or 9842 trunk cable, per installation sheet 1747-IN062.
- The user manual, publication 2711-UM014, for the transfer-mode key sequence and the terminal's ratings.
Disconnect power to the terminal and the SLC rack before wiring anything on the network.
Wire the DH-485 link #
For one terminal and one controller, connect channel 1's RJ45 to the terminal's DH-485 RJ45 with a drop cable — the 1747-C11 is 3 m long and the 1747-C20 is 5 m — and keep the terminal within reach of the panel. When the run is longer, or when more devices will join later, build a trunk: run Belden 3106A or 9842 cable to a 1747-AIC at each drop, terminate the trunk at both ends with 150 Ω resistors across the data pair, switch in the coupler's built-in terminators where a coupler sits at an end, and ground the shield at one point only. DH-485 carries up to 32 devices over 1,219 m (4,000 ft) at 19.2 kbps, and that is the only rate this terminal's port speaks.
Then set the addresses. In RSLogix 500's channel configuration for channel 1, select DH-485, node address 1, 19.2 kbps, and a maximum node address that covers every node you plan to add. In PanelBuilder32's Terminal Setup communication settings, give the terminal node address 2. Both settings travel with their projects, so fix them now and leave them alone.
Build the two-screen trial application in PanelBuilder32 #
The trial application needs exactly four objects on two screens; its job is to exercise every path once, not to look finished.
- Create a new PanelBuilder32 project and select the terminal type for a PanelView 550 keypad unit, catalog 2711-B5A2.
- In Terminal Setup's communication settings, enter the node address you fixed above and a maximum node address that covers the nodes you plan to add.
- On screen 1, add a numeric display bound to N7:0, a numeric entry bound to N7:1, and a momentary pushbutton bound to B3:0/0. These three are spares in the example; pick integer words and a bit that your running program never writes.
- Create screen 2, and put a screen selector on each screen that jumps to the other screen, triggered from function key F1.
- Save the application.
- Connect the PC's COM port to the terminal's RS-232 DB-9 port with the null-modem transfer cable — not to DH-485; the first transfer goes over serial.
- Put the terminal into its transfer mode, using the key sequence for keypad terminals listed in publication 2711-UM014, and start the download from PanelBuilder32, selecting the COM port the cable is on.
- When the transfer finishes, the terminal restarts into run mode and starts scanning the controller on DH-485.
Example: proving the link with N7:0 = 1234 and N7:1 = 500 #
Inputs: RSLogix 500 online with the SLC 5/03, the trial screens running on the terminal, and two test values — 1234 forced into N7:0 from the laptop, and 500 entered at the terminal into N7:1. Both addresses are raw integers, so the numbers are unitless counts; B3:0/0 is a bit, so its only states are 0 and 1.
Rule in words: with no scaling configured, the screen must show exactly the number in the table — the display copies N7:0 onto the terminal, and the entry writes the terminal's number into N7:1 — so any difference means the object is bound to the wrong address or the link is stale.
Arithmetic: force 1234 into N7:0 in RSLogix 500 and read the display: 1234 − 1234 = 0, so the read path is proven. Enter 500 at the terminal and read N7:1 back in RSLogix 500: 500 − 500 = 0, so the write path is proven. Hold the pushbutton: B3:0/0 reads 1 while held and falls back to 0 on release.
Result: differences of zero on both words and a 1-then-0 pulse on the bit.
Decision: zero on both words plus a live pulse means the link, the driver settings and the addressing are all good — build the real screens against the same settings. Any nonzero difference, or a display frozen at its last value, means work in this order: the object's address in PanelBuilder32, then the node addresses, then the port rate, then termination on the trunk.
If it still will not talk #
Work the failures from the layer outward. A dark screen with no keypad response is power or supply wiring before it is communications. A download that never starts is the serial side: the cable, the COM port selection, or the terminal not sitting in transfer mode. A download that completes but objects that read zero or freeze are the network side: node addresses, the channel 1 rate, or missing termination on a trunk longer than a drop cable.
If you later move the PC onto the trunk and the terminal will not show up for a network transfer, the page on why a PanelView 550 will not show up for a DH-485 download covers that path; for driver-side trouble with the computer connected through a 1747-UIC, use the page on fixing RSLinx not seeing a PanelView 550 on the 1747-UIC. And if the unit proves dead and no spare exists, stop spending on it: replacing the failed terminal with a PC-based station — one of the industrial panel PCs running your HMI software against the same SLC — is the fallback before hunting scarce legacy parts.
Questions asked
Can the terminal run the DH-485 network faster than 19.2 kbps?
No. DH-485 also defines a faster 115.2 kbps mode for short trunks, but the PanelView 550's DH-485 port communicates at 19.2 kbps only, so the SLC 5/03 channel and every other device on the trunk must sit at 19.2 kbps for the terminal to join.
How do I put the programming PC on the same DH-485 trunk?
Give the computer its own interface to the network — a 1747-PIC with its 24 V DC supply, or a USB DH-485 interface such as the 1747-UIC — and assign it the next free node address, for example 3. Then raise the maximum node address on the SLC channel and on the PanelView so it covers the new address: a device will not acknowledge packets whose source address is above its UMAX value.
PanelBuilder32 cannot find the terminal for the download — what do I check first?
Check the serial side first: the cable must be a null-modem type with pins 2 and 3 crossed, not a straight serial cable; the COM port selected in PanelBuilder32 must be the one the cable is plugged into; and the terminal must already be in its transfer/configuration mode before the download starts.
Is it worth commissioning an unused PanelView 550 at all?
Yes, if it powers up and its DH-485 port answers. The two-screen trial application proves the read, write and pushbutton paths in an afternoon, and the terminal then serves as the operator station for setpoints, alarms and start/stop on that SLC. If it turns out dead, stop spending on it and replace the operator station instead.