TP900 Comfort to MicroLogix 1100 EtherNet/IP connection

HMI and touchscreens Published 5 min read

Short answer

Yes, the link works. A TP900 Comfort 6AV2124-0JC01-0AX0 communicates with a MicroLogix 1100 1763-L16BBB over EtherNet/IP using WinCC Comfort's Allen-Bradley channel. The connection only carries tag data after you confirm the panel's process-coupling entry, the driver settings and a verified read and write.

On this page
  1. Can a TP900 Comfort really talk to a MicroLogix 1100 over Ethernet?
  2. What do you need before you configure anything?
  3. How do you build the connection in WinCC Comfort?
  4. How do you check the process-coupling entry for 6AV2124-0JC01-0AX0?
  5. Why does the panel reach the controller but show no values?
  6. How do you improve cycle times with a MicroLogix controller?
  7. What is the final decision for this pairing?
  8. Questions asked

Yes, the combination works. A Siemens TP900 Comfort, order number 6AV2124-0JC01-0AX0, communicates with an Allen-Bradley MicroLogix 1100, catalog number 1763-L16BBB, over EtherNet/IP using the Allen-Bradley channel in WinCC Comfort. Siemens documents EtherNet/IP support for the Comfort panel family and publishes an optimization FAQ for exactly this controller class, so the link is a supported path, not a workaround. What stops most installs is not the cable: it is skipping the process-coupling check and the driver configuration, then blaming the hardware when the screen stays at quality-bad.

Can a TP900 Comfort really talk to a MicroLogix 1100 over Ethernet? #

Yes, over EtherNet/IP, and both vendors' documentation supports it. The TP900 Comfort data sheet for 6AV2124-0JC01-0AX0 lists EtherNet/IP among the panel's communication options, and Siemens maintains a dedicated FAQ on connecting SLC 5/05 and MicroLogix controllers to Comfort Panels. The 1763-L16BBB has a built-in 10/100 Ethernet channel, so neither side needs added hardware.

The panel's rear carries a dual-port Ethernet switch, which matters in a small system: you can wire the panel to the controller and hang a programming laptop on the second port without adding a switch. The panel also has PROFINET and an MPI/PROFIBUS DP interface, but for this pairing you ignore those and configure the EtherNet/IP channel only.

What do you need before you configure anything? #

You need the panel, the controller, WinCC Comfort and a reachable network, verified in that order. Confirm the panel's order number on the rating plate is 6AV2124-0JC01-0AX0 and the controller is a 1763-L16BBB before you start, because process-coupling data is published per order number and a sibling Comfort model can differ.

  • SIMATIC HMI TP900 Comfort, 6AV2124-0JC01-0AX0, powered and booted
  • MicroLogix 1100, 1763-L16BBB, with its Ethernet channel assigned a valid IP address
  • WinCC Comfort installed on the engineering PC, with the online help available for the installed version
  • A laptop ping or web-browser check that both devices answer on the same subnet

How do you build the connection in WinCC Comfort? #

You add an Allen-Bradley MicroLogix connection to the project, enter the controller's network settings, and then verify tags against real controller data. Follow the numbered sequence and do not skip the test step at the end.

  1. Open the project in WinCC Comfort and confirm the selected device is the TP900 Comfort.
  2. Add a new connection, choose the Allen-Bradley MicroLogix connection type from the channel list, and enter the controller's IP address and node settings in the connection properties.
  3. Create a small set of HMI tags mapped to controller data addresses whose values you know, following the address format shown in the online help of your installed WinCC version rather than a syntax copied from another project.
  4. Build one test screen showing those tags, then download the project to the panel.
  5. Compare each displayed value against the controller's data table and perform one controlled HMI write to a spare register before you scale up to the full tag database.

How do you check the process-coupling entry for 6AV2124-0JC01-0AX0? #

You open the Siemens support entry for that exact order number and read the process-coupling section before writing tags. Process coupling is Siemens' published list of which communication relationships a specific Comfort order number supports; it is where a mismatch between what you assume and what the panel actually permits first shows up.

The check is short: on the Siemens Industry support pages, look up 6AV2124-0JC01-0AX0, open the technical data, and confirm EtherNet/IP appears in the supported communication list with the controller class you intend to use. If your panel was ordered with a different option set, the coupling entry for your actual number is the one that counts, not the one for a catalog sibling.

Why does the panel reach the controller but show no values? #

Because network reachability and driver configuration are two separate failures, and a ping passing proves only the first. When ping succeeds but every tag stays at quality-bad, the driver layer is where you look: the connection type selected in WinCC Comfort, the IP address and node settings entered in that connection, and the tag address syntax against the controller's data table.

Work it in that order. Reopen the connection properties and confirm the controller's actual IP address is entered there, not on the engineering PC's adapter. Then test one known readable value on its own before adding the remaining tags, because a single malformed address can stall the whole connection's update cycle.

How do you improve cycle times with a MicroLogix controller? #

You start from Siemens' optimization FAQ for SLC 5/05 and MicroLogix connections to Comfort Panels, document 109475773, not from guesswork. That FAQ explains how to arrange the driver settings for this controller class and ships an RSLogix demo project you can compare against your own application when setting up the driver.

The practical habit it encourages: group the tags the screen actually needs into the smallest set of reads that refresh it, rather than scanning the controller's whole data table. Comfort panels and MicroLogix-class controllers do not have the native integration Siemens S7 controllers enjoy, so the driver does more work per tag, and the tag layout decides how fast the screen updates. If communication works but feels slow, rebuild the tag list around what the operator sees before you consider any hardware change.

What is the final decision for this pairing? #

Build it. The TP900 Comfort 6AV2124-0JC01-0AX0 and the MicroLogix 1100 1763-L16BBB connect over EtherNet/IP as a supported path, the panel's dual-port Ethernet switch even leaves a port free for your laptop. Commission it with the process-coupling check, the Allen-Bradley MicroLogix connection in WinCC Comfort, and a proven read and write on a spare register before any live tags go on screen. Once the link runs, the same panel can be given a second role later, and if you ever migrate the visualization toward a PC-based runtime, the same EtherNet/IP connection logic carries over to a project on industrial panel PCs without redoing the controller side.

Questions asked

Can a TP900 Comfort panel drive an Allen-Bradley MicroLogix controller?

Yes. The TP900 Comfort, order number 6AV2124-0JC01-0AX0, supports EtherNet/IP, and Siemens publishes connection guidance specifically for SLC 5/05 and MicroLogix controllers. The 1763-L16BBB connects through its built-in Ethernet channel using the Allen-Bradley MicroLogix connection type selected in WinCC Comfort.

Which WinCC Comfort connection type do I pick for a MicroLogix 1100?

Pick the Allen-Bradley MicroLogix connection type from the channel list in WinCC Comfort and enter the controller's IP address and node settings in that connection's properties. If the installed WinCC version names the driver differently, the online help for your exact version lists the supported connection types; do not substitute a generic driver and hope the tag addressing matches.

How do I test the link without risking the process?

Create one tag pointed at a spare integer register in the controller, read it on a test screen, then perform a controlled write to that same register and confirm the value lands in the controller's data table. Only after that read and write both succeed should you build out the rest of the tag database, because a wrong address on a live output register writes to a real point.

Keep reading

  • How-to

    Connecting One NS-Series HMI to a Redundant CS1D and a CP1H

    Yes. One NS-series panel hosts both controllers: a duplex CS1D pair whose Ethernet units keep a single system IP address through CPU changeover, so the panel never selects a CPU, plus a CP1H reached through its CIF41 as a second host. Both links run FINS over Ethernet simultaneously.

    HMI and touchscreens

  • Troubleshooting

    Fixing a PanelView Plus selector that does not respond

    When the PLC sees the selector signal but the PanelView Plus screen does nothing, compare the communication shortcut's PLC address with the controller's real IP first. In the case behind this article, repointing the shortcut from 192.168.1.150 to 192.168.1.105 was the entire fix. Only if other tags still update should you open the object and compare its Value and Indicator connections.

    HMI and touchscreens

  • How-to

    Connecting a Fuji HMI to a ControlLogix PLC

    Yes, the pairing works. You need Rockwell's Logix package matched to the controller firmware on the PLC side and Fuji V-SFT for the panel; FactoryTalk View programs only Rockwell panels, and RSLinx is not part of the Fuji data path. The gate is the driver list for your exact panel model — V8, V9 and TechnoShot have the Allen-Bradley connection documented.

    HMI and touchscreens