Fix WinCC Flexible 2005 Closing Right After the Splash Screen

HMI and touchscreens Published 6 min read

Short answer

WinCC flexible 2005 with a valid license that closes at the splash screen is failing on damaged per-user profile data: rename the two folders named Simatic WinCC flexible 2005 — one under Application Data, one under Local Settings — and it starts again. Rename one at a time so you know which folder held the fault, and keep a rollback.

On this page
  1. What the failure pattern tells you
  2. Rule the license out first
  3. Rename the two profile folders one at a time
  4. The reported case: WinCC flexible 2005 SP1 HF7 on Windows XP
  5. Prove the fix and keep a rollback
  6. If both renames change nothing
  7. Questions asked

WinCC flexible 2005 that shows its splash picture and then closes, leaving nothing in Task Manager, is failing on its own per-user profile data — not on your project and not on the shortcut. In the reported case, WinCC flexible 2005 SP1 HF7 on Windows XP exited at the splash screen from every launch path until the two folders named Simatic WinCC flexible 2005 were cleared from the affected user's profile: one under Application Data, one under Local Settings. Startup worked immediately afterwards. Rename those two folders instead of deleting them, one at a time, and you keep both the answer to which folder held the fault and a rollback. Rule the license out first in the installed license manager; in the reported case it read valid, which sent the diagnosis straight to the profile.

What the failure pattern tells you #

Check the pattern before you change anything, because it decides which fault class you are in:

  • Both launch paths fail identically — Quickstart and the normal desktop or Start-menu icon show the splash picture, then close.
  • No WinCC flexible process is left in Task Manager after the exit.
  • Nothing on the PC changed beforehand: no Windows update, no virus-scanner update, no configuration change.
  • The installation is WinCC flexible 2005 SP1 HF7 on Windows XP.

Every entry point failing at the same step, with nothing surviving the exit, means the application is aborting during its own startup, before any project is opened. That puts the fault in startup state or licensing, not in a project file. Copy your active project files aside anyway, so a startup repair is never confused with project recovery.

If the operator terminal itself is the thing hanging on its splash picture — the panel, not the engineering PC — read fixing startup splash screen errors on legacy panel PCs; that is the hardware-side fault, and it takes a different path.

Rule the license out first #

Siemens documents, in support entry 36660078, why WinCC flexible closes again automatically after the program start: an expired trial license, a missing or incorrect WinCC flexible license, or an upgrade license that was not activated correctly. Open the Siemens license manager installed with the system and read the WinCC flexible license status. In the reported case the license read valid, which is exactly what points the diagnosis at the profile data.

  • License missing, expired or unusable: repair it through the documented license route and retest. Do not reinstall WinCC flexible for a license fault.
  • License valid and the same splash-screen exit: go straight to the profile folders.

Rename the two profile folders one at a time #

WinCC flexible keeps per-user settings and startup state inside the Windows profile. When that state is damaged, the executable gets far enough to show the splash picture and then exits before the main window exists. The same user-profile dependence bites other WinCC generations — WinCC 7.5 runtime failing under a new Windows user is the same class of fault — and machine-local state is what leaves WinCC flexible runtime showing ### on a copied target PC.

The repair is to move the two suspect folders aside and let the application rebuild them:

  1. Log in with the Windows account that normally launches WinCC flexible; the folders belong to that user.
  2. Close WinCC flexible and confirm nothing is running in Task Manager.
  3. Locate the two folders, named exactly Simatic WinCC flexible 2005:
    • C:\Documents and Settings\%USERNAME%\Application Data\Simatic WinCC flexible 2005
    • C:\Documents and Settings\%USERNAME%\Local Settings\Simatic WinCC flexible 2005
  4. Rename the Application Data copy by appending the suffix .old.
  5. Launch WinCC flexible from the shortcut that failed, and record whether the main window appears.
  6. If it still closes, rename the Local Settings copy the same way and launch again.

Rename, never delete. The reported cure deleted both folders and worked, but a rename preserves the data and tells you which folder held the fault. The application builds fresh profile data when it starts again, and user-specific settings return to defaults. Touch nothing outside this profile — no other accounts, no project directories, no similarly named folders elsewhere on the drive.

The reported case: WinCC flexible 2005 SP1 HF7 on Windows XP #

Inputs, each with its source:

Input Value Where it comes from
WinCC flexible version 2005 SP1 HF7 the reported installation
Operating system Windows XP the reported PC
Launch paths that fail 3 — Quickstart, desktop icon, Start-menu icon the report
Processes left in Task Manager after the exit 0 the report
License status valid the license manager, as reported
Folders named Simatic WinCC flexible 2005 in the profile 2 the reported profile

Rule in words: when every launch path dies at the same splash-screen exit, no process survives, and the license reads valid, the fault is per-user startup state — isolate it with one rename per launch test.

Arithmetic: 3 failing launch paths out of 3 tested means every entry point fails identically, so no project, no shortcut and no project file is implicated. Two suspect folders at one rename per test is 2 tests and 2 launch attempts to a verdict. The reported repair cleared both folders before the successful restart, so the split between the two folders went unmeasured — which is precisely the information the one-at-a-time rename keeps.

Decision: a start that survives within 2 renames convicts the profile data; keep the .old folders aside until validation passes. Two renames with no change — 0 for 2 — clears the profile data: restore both folders and stop modifying the profile.

Prove the fix and keep a rollback #

  • Launch from the normal shortcut and wait for the main window, not just the splash.
  • Confirm in Task Manager that the process is still present after the splash screen closes.
  • Open a known-good project and confirm it loads.
  • Close and relaunch once to confirm the fix survives a fresh start.
  • Keep the .old folders until all four checks pass; restore them only if the fresh profile introduced a regression.

Treat any rename as unproven until the application runs: a rename elsewhere can leave stale references behind, as when a gateway rename left the local connection stale, so verification is part of the method, not an afterthought.

If both renames change nothing #

  • Restore both .old folders to their original names.
  • Re-read the license in the installed Siemens license manager against the documented causes above, and repair it through the documented license route if it is not valid.
  • Only with a valid license and identical behavior is an uninstall-and-reinstall of WinCC flexible the next step — the reported case considered that route and never needed it after the folders were cleared.

Questions asked

Why does WinCC flexible exit right after the splash screen with no error?

Because it is aborting while loading its own per-user startup state, before the main window exists. The splash picture appears, initialization fails, and the process exits too quickly to leave anything in Task Manager. Damaged data in the two Simatic WinCC flexible 2005 profile folders produced exactly this on the reported 2005 SP1 HF7 installation, and clearing them restored startup.

Does clearing these folders touch my projects?

No. Those two folders hold per-user application settings, not project files; your projects stay wherever you saved them. Even so, copy active project files aside before the test so a startup repair is never mistaken for project recovery.

Why rename the folders instead of deleting them?

Because a rename is reversible. The reported fix deleted both folders at once and worked, but it could not tell you which folder held the fault; renaming one at a time gives you that answer plus a rollback if the fresh profile misbehaves. Keep the renamed copies until the application opens, loads a project and restarts cleanly.

What if WinCC flexible still closes after both renames?

Restore both folders to their original names and stop changing profile data: two renames with no change clears the profile as the cause. Re-read the license in the installed Siemens license manager, and only with a valid license and unchanged behavior is an uninstall and reinstall the next step.

Keep reading

  • How-to

    Redownloading an HMI Project After a User Lockout

    Yes — WinCC flexible 2008 SP3 opens and converts an SP2 project, and the converted project downloads to the panel. The lockout itself only clears if you remove the failed-login limit in the project and transfer with the option that replaces user administration on the panel; a plain application download leaves the locked account in place.

    HMI and touchscreens

  • How-to

    How to Change WinCC Flexible Screens From the PLC

    Enable Screen number and Job mailbox in the connection's Area pointer tab, reserve a data block for each, and write the screen-selection job from the PLC as a one-shot: parameters first, job number last, and never again until the panel clears the job word to zero. The screen-number area pointer then reports the current screen back to the PLC.

    HMI and touchscreens

  • Troubleshooting

    Use the Transfer Dialog Not a NetPro Connection for HMI Download

    Put the panel's IP address in the WinCC flexible transfer dialog and start the Ethernet transfer from there. A connection in NetPro or the communications palette configures runtime data exchange with the controller, not the download path. If the panel does not switch to transfer mode automatically, select transfer mode manually from its startup menu after power-up; the failing MPI discovery is a separate interface with its own addressing.

    HMI and touchscreens

WinCC flexible stuck on the ES startup splash with a gray screen