WinCC flexible stuck on the ES startup splash with a gray screen

HMI and touchscreens Published 6 min read

Short answer

When even a standalone launch of WinCC flexible 2008 SP3 opens a gray window, the editor's own startup state is the fault: restart Windows, right-click the SIMATIC WinCC flexible Start Center and choose Reset SIMATIC WinCC flexible. Test a standalone launch first; if the editor opens normally there, the problem is the STEP 7 integration, not the editor state, and the reset is not the fix.

On this page
  1. Separate the editor from the project
  2. Rule out a hidden dialog before you reset
  3. Check the host baseline before you reset
  4. Reset SIMATIC WinCC flexible from the Start Center
  5. If the standalone editor opens normally
  6. Verify the repair
  7. Questions asked

A WinCC flexible 2008 SP3 editor that stops on the SIMATIC WinCC flexible ES wird gestartet splash and then shows nothing but a gray window is failing in the editor's own startup state, before any project is read. The fix is the vendor-documented reset: restart Windows, right-click the SIMATIC WinCC flexible Start Center in the taskbar and select Reset SIMATIC WinCC flexible. Run one decision test first. Launch WinCC flexible on its own, without SIMATIC Manager. If that standalone launch is gray too, reset the editor. If the standalone editor opens with a full workspace, the editor is healthy, the fault sits in the STEP 7 integration, and the reset is not the fix.

Separate the editor from the project #

On the reported station, an integrated open from STEP 7 V5.5 SIMATIC Manager used to show the ES wird gestartet splash together with a no default file found dialog; acknowledging that dialog let the project open. ES is the engineering station, and the splash words simply mean it is starting. That dialog acted as the last gate of startup. Its disappearance changes the diagnosis: startup now fails before the editor reaches the point where it asks for a default file, so waiting for it cannot clear the fault.

Use the standalone launch to decide which branch you are on:

What you see What it tells you Next step
Integrated open stops on the ES wird gestartet splash The editor starts but does not finish initializing Launch WinCC flexible standalone
Standalone launch also shows a gray window The shared editor startup state is failing, not the project Reset from the Start Center
Standalone editor opens with a full workspace The editor is healthy; the fault is in the STEP 7 integration or the HMI station Check the integration, do not reset
Splash clears, then the editor closes A crash after startup, a different failure mode Windows event log, not the reset

The last row is not this fault. An editor that exits right after the splash has its own failure mode and its own fix, written up as WinCC flexible 2005 closing right after the splash screen.

Rule out a hidden dialog before you reset #

Two conditions mimic a dead editor and cost nothing to check.

  • A stacked window. A startup dialog hidden behind another window looks identical to a hang. Check the taskbar previews and cycle every open window before declaring the process stuck; this is the same window-stacking trap that buries a MotoSIM EG-VRC keyboard behind the taskbar.
  • A process that has already exited. If the gray window is gone and Task Manager shows no running WinCC flexible process, startup crashed rather than hung. Trace that in the Windows event log. The reset below addresses a hung, incomplete startup, not an exiting one.

If a hidden dialog does turn up, acknowledge it and watch whether loading continues. If the splash clears and the project opens, the editor was never the fault.

Check the host baseline before you reset #

This installation had run for years on Windows 7 SP1 with 8 GB of RAM and an Intel Core i7 at 2.7 GHz, which puts a gross hardware mismatch far behind the startup-state fault. The storage floor still deserves a current measurement, because the documented page-file rule scales with RAM.

Item Documented minimum Reported station Decision
Operating system Windows 7 Professional, Ultimate or Enterprise with SP1 (32- or 64-bit); Windows 10 Professional, Enterprise or LTSB Enterprise (64-bit) Windows 7 SP1 Matches
Processor Pentium 4 class at 1.6 GHz or faster Intel Core i7 at 2.7 GHz Exceeds
RAM 1 GB or more; 512 MB for WinCC flexible Micro 8 GB Exceeds
Display resolution 1024 x 768 or higher read it in Windows display settings Correct a resolution below the floor before judging the editor layout
Free disk space 2 GB or more; 1.2 GB for WinCC flexible Micro measure the system and project volumes Free storage first if either volume is below its floor
Page file three times installed RAM 3 x 8 GB = 24 GB Resize if configured below the rule

The page-file rule is the one number worth computing. Three times the reported 8 GB gives 3 x 8 GB = 24 GB. The configured page file and the software's 2 GB free-space minimum draw on the same volume, so read the page-file setting and the free capacity of the system partition, and make the partition cover both, not the 2 GB alone. A page file left at a small fixed value after a memory upgrade is the usual way this floor gets missed.

Reset SIMATIC WinCC flexible from the Start Center #

The reset returns WinCC flexible to the original status of its last installation, as the vendor's support documentation describes it: it restores the editor's own startup settings, not the project data on disk. One caution first. Keep a separate copy of the STEP 7 and HMI project before you change application state, so a known-good copy exists no matter what the reset touches.

  1. Close SIMATIC Manager and every visible WinCC flexible window.
  2. Copy the project directory to a separate location.
  3. Restart the computer and let Windows startup complete.
  4. Locate the SIMATIC WinCC flexible Start Center entry in the taskbar, or start the Start Center and right-click inside its window.
  5. Select Reset SIMATIC WinCC flexible in the menu that opens.
  6. Let the reset run to completion.
  7. Launch WinCC flexible on its own and expect a full workspace with menus and project controls.
  8. Open the HMI station from SIMATIC Manager and expect the ES wird gestartet splash to clear into the project editor.

If no default file found appears again on the integrated open, acknowledge it. Loading continuing after that dialog was this station's normal behavior before the fault, not a problem to chase.

If the standalone editor opens normally #

Do not run the reset. A healthy standalone launch clears the shared editor state of suspicion, and the reset would only restore defaults you did not need. The fault then sits in the integration between STEP 7 and WinCC flexible: check that the HMI station object inside the STEP 7 project is intact and correctly associated with the editor, and try opening the project's screens from the project view rather than the station shortcut. Comparing against a second installation of the same versions is worthwhile here, because an integration component mismatch shows up exactly in this branch.

Verify the repair #

  • A standalone launch opens a complete, responsive editor with menus, not a gray client area.
  • The integrated open from SIMATIC Manager clears the ES wird gestartet splash into the project editor.
  • Representative screens open with their objects and text intact.
  • Once the editor is back, prove the project still behaves by running it against a simulated PLC behind WinCC flexible 2008 SP3 before you touch the real controller.

Questions asked

Does Reset SIMATIC WinCC flexible delete my project?

No. The vendor documents the reset as returning WinCC flexible to the original status of the last installation, which is the editor's configuration rather than the project files on disk. Screens, tags and connections stay as they were saved. Copy the project first anyway, because a known-good copy costs one folder and settles any later question about what changed on the station.

Why did the no default file found dialog stop appearing?

The no default file found dialog was not an error that blocked the project; acknowledging it was the step that let loading proceed. It stopped appearing because startup now fails earlier, before the editor reaches its default-file check, so no amount of waiting brings it back. The reset targets that earlier stage instead, which is why it is the effective action here.

What are the minimum system requirements for WinCC flexible 2008 SP3?

The documented minimums are Windows 7 Professional, Ultimate or Enterprise with SP1 in 32- or 64-bit, or Windows 10 Professional, Enterprise or LTSB Enterprise in 64-bit; a Pentium 4 class processor at 1.6 GHz or faster; 1 GB of RAM; 2 GB of free disk space; and a display resolution of 1024 x 768 or higher. WinCC flexible Micro runs with 512 MB of RAM and 1.2 GB of free disk space.

How large should the page file be on the engineering station?

Use three times the installed RAM. On a station with 8 GB of RAM that is 3 x 8 GB = 24 GB, and the system partition must hold that page file plus the software's 2 GB free-space minimum. Resize the page file whenever the installed memory changes, because the rule scales with RAM.

Can the reset run while SIMATIC Manager is still open?

Close it first. The reset restores editor state shared by the standalone editor and the STEP 7 integrated editor, and the procedure assumes the applications are closed. Restarting Windows as part of the sequence also guarantees that no WinCC flexible process is holding the old startup state when the reset runs.

Keep reading

  • Troubleshooting

    Fix WinCC Flexible 2005 Closing Right After the Splash Screen

    WinCC flexible 2005 with a valid license that closes at the splash screen is failing on damaged per-user profile data: rename the two folders named Simatic WinCC flexible 2005 — one under Application Data, one under Local Settings — and it starts again. Rename one at a time so you know which folder held the fault, and keep a rollback.

    HMI and touchscreens

  • How-to

    Controlling 100 Motors From One Reusable WinCC Flexible Screen

    Build one motor screen with Start, Stop and Alarm buttons bound to PLC-connected tags, then reuse it across the 100 motors through an indirect-addressing method your flexible runtime target actually supports. The classic WinCC PictureWindow TagPrefix recipe does not exist in WinCC flexible, so prove one motor screen first and read the installed help for the target's screen-reuse features before choosing shared or fixed bindings.

    HMI and touchscreens

  • Troubleshooting

    Why SIMATIC HMI Station Is Missing in STEP 7 Insert Station

    The SIMATIC HMI Station entry under Insert > Station appears only when WinCC flexible is installed with its Integration in STEP 7 component while STEP 7 is already on the PC. Reinstall WinCC flexible with that option ticked and restart; STEP 7 V5.4 with WinCC flexible 2008 SP2 is a working pair, while STEP 7 V5.7 is not supported.

    HMI and touchscreens