Fixing an HMI Project Upload That Reports Communication Failed

HMI and touchscreens Published 8 min read

Short answer

Treat a failed HMI project upload as three separate branches: the installer's parallel-port dongle driver message is a licensing fault, a "communication failed" report before any progress is a transfer-path mismatch, and a "file system error" after the panel answers is a storage or destination fault. Identify the layer from the message and the moment it appears, fix that layer only, and retest. A dongle fault never blocks the cable, and a successful ping never proves the transfer service is up.

On this page
  1. Record the message and the moment it appears
  2. The parallel-port message is a licensing fault, not a cable fault
  3. Match the selected transfer interface to the cable on the panel
  4. The file system error: fix the side the timing points to
  5. Timing a 2 MB upload on a serial transfer path at 115200 baud
  6. Retest one layer at a time and keep what works
  7. Questions asked

An HMI project upload that reports communication failed is not one fault, and the panel is rarely the guilty part. Start with the timing test that splits the branches: on a serial line at 115200 baud, a 2 MB project takes roughly six minutes to move, so an error inside the first seconds — with no progress shown — means no data moved and the fault is in the licensing or transfer-path layer; an error after a minute or more of progress means the path works and the file-system layer applies. The third branch is the parallel-port dongle driver message, which appears during software installation and is a licensing fault on the PC, not a cable fault. Read the exact message, note the moment it appears, fix that one layer, and retest. Change one thing per attempt — a repair you cannot attribute will not survive the next machine.

Record the message and the moment it appears #

Before touching a cable or a setting, capture what the screen actually said. The three reports in this failure sit in different subsystems, and the stage at which each one appears tells you which subsystem to open.

Exact message Where it appears What it points to
"There are no parallel port in this computer or parallel port is disabled.can not install parallel port dog driver." Software installation Licensing-device driver on the PC; no relation to the cable to the panel
"communication failed" Upload attempt, before any progress shows Transfer path: selected interface versus physical connection
"file system error" Once the transfer has started or the panel has answered PC destination folder or panel-side project storage

Write down, before you change anything:

  1. The complete message text and any code shown with it.
  2. The operation that produced it: installer run, upload attempt, or mid-transfer failure.
  3. The software's product name, edition and version from its identification screen — the short label in the installer title is not enough to match licensing documentation or pick a replacement installer.
  4. The panel model from the nameplate.
  5. The interface selected in the transfer dialog and the cable physically plugged into the panel.

Keep this separate from runtime faults: an upload uses the engineering connection, not the tag traffic between panel and PLC, so a screen that reads live values correctly can still refuse an upload. A failed live value involves the PLC driver and the controller, and that different timeout is covered in Fixing HMI PLC Communication Timeout Over Serial.

The parallel-port message is a licensing fault, not a cable fault #

That installer message names a driver for a hardware license key — the "dog" in the text is a dongle. The installer looked for an enabled parallel port, found none (current PCs ship without one, and on older machines the port is often disabled in the firmware setup), and skipped the key driver. Nothing in that sequence touches the cable to the panel.

Work it in this order:

  • Read the licensing requirements supplied with your exact software release and decide whether the operation you need requires the parallel-port key at all; many releases license project transfer by other means.
  • If the key is required, use the vendor's documented key and driver arrangement. A passive parallel-to-USB adapter does not make a parallel-port key work, because the driver expects direct access to the port hardware, not a printer adapter. Get the package and the license components through the vendor or its authorized distributor; do not disable the license check and do not install an unofficial driver.
  • If setup misbehaves beyond the dongle message — aborting, files vanishing, repeated failed reinstalls — start again from a fresh, complete installer package; broken installer behavior has its own causes, covered in why an engineering-software installer deletes itself during updates.

The decision: open the software and try to reach the upload dialog. If it opens and permits the transfer operation, the dongle message is not what is stopping the upload — move to the transfer path below. If licensing blocks the operation, resolve it with the vendor first. A dongle problem does not block the cable path, and fixing it would not prove the panel is reachable.

Match the selected transfer interface to the cable on the panel #

Read the transfer configuration in the engineering software, then look at the panel: the selected target model must match the nameplate, the selected interface must match the physical port used, and that port must be one the panel maker documents for project transfer. The connector that talks to the PLC is not automatically the programming connection.

Then check the physical path by interface:

  • USB: several HMI makers require a PC-side USB driver before the programming software can see the panel. Before another upload attempt, open the operating system's device list and plug the cable in. No new device appearing, or a device with a driver error, puts the fault in the cable, the port or the driver — not in the software settings.
  • Serial: select the COM port the operating system actually assigned to your adapter; adapters moved to a different USB socket frequently take a new number. The cable must follow the panel maker's pinout, and crossed send and receive lines are the norm on programming cables — the wiring traps are covered in How to Upload an HMI Program Without the Right Cable Pinout.
  • Ethernet: check the link LEDs, put the PC and the panel in the same subnet or behind a valid route, and ping the panel. A reply proves the network layer only. Reachability does not prove the panel's transfer service is up; if ping passes and the upload still reports communication failed, check the panel-side transfer state and whether your software release supports that panel model — a mismatched package fails even on a healthy network.

Repair the first layer that fails, in this order: no USB device entry points to driver, cable or port; a failed ping points to addressing and link; a passed ping with a refused transfer points to the panel's transfer state or the software-panel pairing.

The file system error: fix the side the timing points to #

A file system error reported from a TPC 7022KX-class panel — or any model — is decided by timing. An immediate error, while you select or create the destination, points to the PC side. An error after the panel answers or after progress appears points to panel-side project storage or the panel's transfer service.

PC side:

  • Pick a local destination folder the current user can write to, and prove it: create a test file there with the operating system and delete it again.
  • Check free space on that drive.
  • Retry into a new local folder rather than a network share, which removes the network file system from the test.

Panel side:

One warning, and the only place to be conservative in this job: never format the panel storage, initialize the panel, or download a blank project to clear the error — that can destroy the only working application on the machine. If upload protection is set, use the authorized project credentials or the vendor's documented recovery, nothing else.

Timing a 2 MB upload on a serial transfer path at 115200 baud #

Inputs: a project file of 2 MB, that is 2,000,000 bytes in decimal megabytes — an illustrative size for a mid-size embedded HMI project, not a measured file; a serial line at 115200 bits per second, a standard rate and a common default for HMI transfer paths, with 8 data bits, no parity and 1 stop bit, which is 10 bits per byte; and an overhead allowance of 2 for protocol framing, acknowledgements and the panel writing to flash — an illustrative engineering allowance.

Rule in words: transfer time equals bytes multiplied by bits per byte, divided by the line rate, then multiplied by the overhead allowance.

Arithmetic:

  • 2,000,000 bytes × 10 bits per byte = 20,000,000 bits.
  • 20,000,000 bits ÷ 115,200 bits per second = 173.6 seconds.
  • 173.6 seconds × 2 = 347 seconds, about 5 minutes 47 seconds.

Result: a healthy serial upload of this project runs for minutes, roughly six.

Decision, with its threshold: if the software reports communication failed with no progress shown — inside the first seconds, far under the six-minute mark — no project data moved, and the fault sits in the licensing or transfer-path branches. If progress runs for a minute or more before the error, the path works and the file-system branch applies. Progress before failure means storage; silence before failure means the path.

Retest one layer at a time and keep what works #

Apply the correction at the first failed layer and retest without changing anything else. One variable per attempt, and write the message down after each: the table at the top tells you which branch you have moved into, and a message that changes from communication failed to file system error is progress, not a new fault.

After a successful upload, open the retrieved file immediately in the same software release that pulled it, and keep that release identified next to the file. If the file system error traces to panel-side storage that the documented tools cannot repair, or the panel model is discontinued with no supported recovery, the repair is not worth pursuing — replacing the terminal with one of today's industrial panel PCs keeps the machine on a supported platform.

Questions asked

Does the parallel-port warning mean the HMI panel is faulty?

No. The warning is produced by the engineering software's installer on the PC while it tries to set up a driver for a parallel-port hardware license key. It says nothing about the panel. Judge the panel by its own behavior: if it boots and runs its project on the machine, the panel side is healthy and the upload fault is on the PC or in the connection between them.

Can a USB-to-parallel adapter make the dongle driver install?

Usually not. A USB-to-parallel adapter presents a printer port to Windows; a parallel-port license key driver expects to talk to the port hardware directly, and a generic adapter does not pass that through. Check the software vendor's licensing documentation for the license methods supported on a current PC before buying any adapter, and get the key and driver through the vendor or an authorized distributor.

My panel answers ping but the upload still reports communication failed. What now?

Ping proves only that the network path and IP settings are right. The transfer is a separate service on the panel, and some panels accept one transfer client at a time. Close other engineering stations that may hold a session with the panel, power-cycle the panel so its transfer service restarts, and confirm your software release supports that panel model before retrying the upload.

Which COM port should I select for a serial upload?

The one the operating system has actually assigned to your cable right now, not the one that worked last week. Open the device manager, unplug and replug the USB-serial adapter, and watch which entry appears and disappears; USB adapters frequently take a new number when moved to a different USB socket. Select that number in the transfer dialog and leave the other settings at the panel's documented values.

Is the file I finally upload back the editable source project?

Not always. Depending on the panel and software release, an upload returns an editable project, a runtime package, or another backup format, and the three are not interchangeable. After a successful retrieval, open the file immediately in the same software release that produced it, note that version next to the file, and keep both together, because a newer release may refuse an older package.

Keep reading

  • Troubleshooting

    Fixing a PCS 7 OS download that fails with SQL errors

    The transfer fails because the target-side WinCC SQL databases, the CC_* copies, stay attached to SQL Server or sit in RECOVERY_PENDING, so WinCCOM cannot replace them. Close Runtime and all editors, reboot the target, remove the obsolete CC_* databases through the SQL administration layer rather than by deleting .mdf files, delete the stale CC_OM DSN, then run one clean download.

    HMI and touchscreens

  • Troubleshooting

    Fixing an HMI Project That Fails After a Git Clone

    The clone is broken because a referenced bitmap .PLK was never committed, not because of an ignore rule. Read the HMI Output tab for the exact filename, prove the file is untracked with git check-ignore followed by git ls-files, then restore and commit it and re-test from a clean clone. Track the .tgt and .def files for the HMI BIOS version as well.

    HMI and touchscreens

  • Troubleshooting

    E200 HMI recovery when the supplied file is a GOT project

    The E200 is an E-series terminal programmed with E-Designer, and it accepts only a native E-Designer project file with the .MPA extension. GT Designer3 opens GOT projects and can convert E-Designer projects toward the GOT, never the reverse, so recovery means obtaining the original .MPA from the machine builder or a backup, then downloading it over the documented serial cable.

    HMI and touchscreens