How-to
Fixing please select a correct HMI model on upload
Short answer
The error means EasyBuilder Pro has no model selected that matches the connected terminal. Read the complete model designation off the grey or silver label on the back, or off the HMI itself (Arrow icon, I icon, Version tab on non-cMT units; orange settings button, Information tab on cMT units), select that exact model, then retry the upload over Ethernet, USB or SD card.

On this page
- What does please select a correct HMI model mean?
- Where do you read the model number on the HMI itself?
- How do you find the model from the HMI's own system information screen?
- Can the serial number tell you the HMI model?
- How do you select the model in EasyBuilder Pro and retry the upload?
- Will the uploaded project let you change the language?
- What do you do when no listed model matches the unit?
- Questions asked
An upload that stops with error : please select a correct HMI model has not touched the project yet: EasyBuilder Pro checks that a model is selected before any transfer starts, and it refuses to guess. The fix takes minutes once the terminal identifies itself. Read the complete model designation off the grey or silver label on the back of the unit, or off the HMI's own system information screen (the Arrow icon, I icon and Version tab on non-cMT units; the orange settings button and Information tab on cMT units), select that exact designation in the software, and run the upload again over Ethernet, USB or SD card. The usual setting for this error is a second-hand machine: in one reported case nobody could upload from a French-language terminal under EasyBuilder Pro 6.08.02 because the model was unknown and the seller had no project copy.
What does please select a correct HMI model mean? #
It is the model check EasyBuilder Pro runs at the start of a transfer: the software compares the model chosen in its transfer window with the terminal on the connection, and it stops when the choice is empty or cannot match the connected unit.
The message comes from the computer before a byte of project data moves, so failed attempts leave the panel untouched and are safe to repeat. It carries no information about the right model, only that the current selection is wrong or missing, and retrying with the same selection reproduces it every time. The only changes that matter are the selected model and, secondarily, the connection, which is why the whole fix is identification first, transfer second.
Where do you read the model number on the HMI itself? #
The complete model designation is printed on a grey or silver label on the back of the HMI, and that label is the primary source because it stays readable even while the project runs or the screen displays another language.
Record the designation character for character, series prefix, size digits and every suffix letter, because EasyBuilder Pro's model list separates units by those suffixes and a near-miss reproduces the same error. Photograph the whole label instead of copying from memory. The serial number sits on the same label on its own line; the model line is the one the software needs. If reading it means pulling the panel out of its mounting, do that with the machine locked out and its supply off.
How do you find the model from the HMI's own system information screen? #
When the rear label is out of reach, the running HMI reports its model in system information: on non-cMT units through the Arrow icon, the I icon and the Version tab, on cMT units through the orange settings button and the Information tab.
Non-cMT series units take three taps:
- Select the
Arrowicon in the bottom-right corner of the display. - Select the
Iicon in the menu that follows. - Open the
Versiontab in the system information menu, where the model designation appears.
cMT series units take two:
- Select the orange settings button in the top-left corner of the screen.
- Open the
Informationtab.
Icon positions and tab layout do not move with the display language, so a French menu costs nothing but translated labels. Where both routes are available, the designation on the screen should match the rear label; when they differ, trust the label.
Can the serial number tell you the HMI model? #
No: a serial number identifies the individual unit for the manufacturer's build records and does not encode the designation EasyBuilder Pro asks for, so a serial such as MP0250 from a second-hand machine cannot be decoded into a model to select.
Only the manufacturer's build records pair a serial with a model, and that pairing is nothing the transfer window accepts or a user can look up. Practically, the rear label carries the model on its own line beside the serial, and the system information screen exists to show the model directly, so neither documented route runs through the serial. When a seller can quote only a serial, treat the model as unidentified and go to the unit itself.
How do you select the model in EasyBuilder Pro and retry the upload? #
Open EasyBuilder Pro, pick the exact designation you recorded from the model list before any transfer opens, then run the upload again over Ethernet, USB or SD card.
- Write the complete designation down from the rear label or the
VersionorInformationtab, suffixes included. - In EasyBuilder Pro's transfer window, select that designation in the model list; the list is long and grouped by series, so match the whole string, not only the family name.
- Choose the connection: Ethernet needs the panel's IP address on a network the computer can reach, USB connects the panel directly with the cable the software names, and the SD card path carries the request to the panel and the recovered project file back on the card.
- Start the upload and let the progress run to completion.
- Open the recovered file in EasyBuilder Pro and confirm it before editing anything.
Two failure patterns can remain after the model is accepted. When the panel answers on the network but the project transfer still fails, when VNC works but HMI project upload fails over Ethernet separates the two layers. When the direct cable is the suspect, how to upload an HMI program without the right cable pinout covers the wiring side.
Will the uploaded project let you change the language? #
The upload clears the way, but only an editable project carries the text you can translate, and a recovered copy is not automatically one, so check what the transfer produced before planning the language change.
Open the recovered file and decide on what you see. If it opens as source with editable screens and text objects, translate the text, leave the device addresses untouched, and download the project back to the panel. If it opens only as a runtime copy, the panel keeps its French screens until the editable source arrives from the machine builder; why an uploaded HMI copy is not an editable project explains which kind of file you are holding.
What do you do when no listed model matches the unit? #
Stop retrying and escalate: a designation that never appears in the model list is either newer than the EasyBuilder Pro release on the computer or a custom model built for the machine manufacturer, and the machine builder holds both the project and the software identity.
- Update first. Install a current EasyBuilder Pro release and reopen the model list, because a model absent from an old release such as
6.08.02can be present in a new one. - If the designation is still absent, treat the terminal as a custom unit: machine builders do commission HMIs under custom designations, and the programming software and project source sit with them, not with the equipment seller.
- Ask the machine builder for the editable source project and for confirmation of the terminal's exact designation, and keep the reply on record.
- For a vendor support case, collect the diagnostics first: run
Utility Manager, select the model type, open theMaintenancetab, start theHMI Information Collectorand search for the target HMI; the sequence is shown in the guide to collecting and reporting HMI errors with the Diagnostic Tool.
The order never changes: identify from the rear label or the system information screen, select that exact model, transfer over Ethernet, USB or SD card, and escalate to the machine builder only when the designation is missing from the list. With the model known and selected, the message error : please select a correct HMI model disappears on the next attempt.
Questions asked
Can a newer EasyBuilder Pro release list a model missing from 6.08.02?
Yes. Each EasyBuilder Pro release carries the model list current to its release date, so a terminal built after that date appears only in a newer release. Take the current release from the manufacturer's own download page, install it, and reopen the model list before deciding the unit is a custom model.
What if the upload asks for a password after the model is accepted?
The project was downloaded with upload protection, and the transfer will not read it out without the project password. That password belongs to whoever built the machine, so the request goes to the machine builder together with the request for the source project; no tool recovers a protected project without it.
What should you send the machine builder when you request the project?
Send the complete model designation from the rear label, the serial number printed beside it, the EasyBuilder Pro version on the computer, and the exact error text from the transfer window. Ask for the editable source project rather than a compiled copy, because only the source carries translatable screens and text.
Why is recovering a project called an upload?
The HMI is the reference point for every transfer in EasyBuilder Pro: a download moves data onto the HMI and an upload moves data off it. The user manual defines the pair that way for its FTP object, where download takes a file from the server to the local HMI and upload sends one back. Recovering a project therefore always runs as an upload.