IMDTouchKnowledge BaseShop main store

Explainer

Sharing HMI monitors between WinCC, video and MES without a KVM

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

A shared pulpit monitor can switch between WinCC, camera video, MES and measuring-device PCs without a KVM. Decode video locally on the pulpit PC, show other Windows software as an embedded remote session, keep WinCC pictures native, and let an S7-written request tag trigger the switch script. There is no conversion from WinCC to WinCC OA, so staying on WinCC and embedding the sources is the low-cost route.

On this page
  1. The source class decides the method
  2. Why video never goes through a remote session
  3. Embedding each source in WinCC
  4. Driving the switch from the S7
  5. What a move to WinCC OA actually costs
  6. Verification on the bench
  7. The decision
  8. Questions asked

Yes. One pulpit monitor can serve WinCC, camera video, MES clients and measuring-device PCs without a KVM switch, and the S7-400 can drive the selection automatically. The answer is classification, not a platform change: decode video locally on the pulpit PC, show other Windows software as an embedded remote session, keep WinCC pictures native, and let a PLC-written request tag trigger a change script. A move to WinCC OA does not shorten the work, because no conversion exists between the two engineering systems. The sections below classify each source, show what each embedding method breaks, and give the switching mechanism with its verification steps.

The source class decides the method #

Classify every source before choosing a technique. The classes have different requirements, and the requirement, not the platform, picks the method:

Source What the operator needs Method on the shared monitor
WinCC process screens Native graphics, alarms, faceplates Normal WinCC pictures, no extra layer
Camera video High refresh rate, low latency Video object or player decoding locally on the pulpit PC
Level 3/MES, measuring devices, other Windows software Interactive window, moderate update rate Embedded RDP or VNC session, or a foreground switch to a locally running application

Remote desktop and VNC both transmit compressed pictures of screen changes. That suits an operator window onto an MES client or a measuring-device application. It does not suit live video, for a reason the numbers make plain.

Why video never goes through a remote session #

Worked example with illustrative rates you must confirm on your own link. A process camera streams at 25 fps, so the frame period is 1 s ÷ 25 = 40 ms. Assume the remote session pushes compressed screen updates at 10 updates/s, a value worth measuring before you commit. The update period is 1 s ÷ 10 = 100 ms. Over a 2 s camera pan: frames produced = 25 × 2 = 50, updates displayed = 10 × 2 = 20, so 50 − 20 = 30 frames never reach the screen, and network latency stacks on top. The decision follows directly: camera video decodes on the pulpit PC, inside the plant network, and never rides a remote session.

Decoding plus the WinCC runtime load the same machine, so check its processor and graphics headroom. If the existing pulpit PC has none, that is the point to specify new hardware — the runtime belongs on one of the industrial panel PCs sized for the combined load.

Embedding each source in WinCC #

Each method has a distinct failure mode, so verify the one that applies before building the rest:

  • Native WinCC pictures. Nothing to add. The runtime keeps its alarms, faceplates and structure concept untouched.
  • Embedded video. Insert the video object or player into the picture the way any object is inserted, and confirm the camera stream or decoder is reachable from the pulpit PC. Smooth motion at the camera's native rate is the expected result; stutter only while WinCC is busy means the PC lacks headroom, not that the method is wrong.
  • Embedded RDP session. Register the control in the Graphics Designer first: in WinCC Explorer, right-click Graphics Designer and use the Select ActiveX function, which brings the control's OCX file into the object library. On the target side, confirm the PC permits remote sessions and the pulpit account has rights. A session that drops back to a login prompt points to wrong credentials or a session limit on the target, not to the HMI.
  • Foreground-window switch. For Windows software running on the pulpit PC itself, a script brings the application window forward on request. Windows can refuse a foreground change coming from a background process, so test the switch while another application holds focus. If it fails there, the method is unreliable for automatic changes and that source needs a session instead.

An embedded control only occupies space inside a WinCC picture. Where more than one monitor carries WinCC windows, the placement rules in how one HMI runtime places windows on two monitors apply, and the navigation structure should keep WinCC dual-monitor navigation inside picture windows so a switched source cannot tear the operator out of the plant display.

Driving the switch from the S7 #

The mechanism is the same on any platform: a state variable in the PLC, a trigger on change in the HMI, and a mapping from value to display action.

  1. Define one integer request tag per monitor in an S7 data block and in the WinCC tag list. Reserve one value for no request, leave the display as it is.
  2. Fix the mapping table in one place — for example 0 no request, 1 WinCC picture, 2 camera video, 3 MES session, 4 measuring-device session — so the mechanical sequence and the HMI script can never disagree.
  3. Attach a change-triggered action to each request tag that performs the switch for that monitor.
  4. Keep a manual override on the operator side, and show on screen which source the PLC last requested. The operator must always win against the sequence.
  5. Keep alarm display on a monitor in a fixed, never-switched picture.

Do not route any safety-relevant or alarm-acknowledgement function through a switched source; the sequence may rearrange video and auxiliary applications, but the alarm picture stays put.

What a move to WinCC OA actually costs #

WinCC and WinCC OA are separate product lines with separate engineering systems, and there is no conversion tool between them. A migration is a rebuild: pictures, libraries, faceplates and structure types are re-created by hand, which is the same discipline as rebuilding a lost HMI project from PLC tags and logic. For a source-switching requirement on a project with years of established concept work, that is the most expensive way to get it. If the customer strategically wants one platform that also covers the navigation role, scope WinCC OA as a new project and run it in parallel — never as a conversion of the existing one.

Verification on the bench #

Before handover, prove the whole chain with the real sources:

  • Drive every request value from the PLC, or from a forced test value, and confirm the correct source appears on the correct monitor within the switch time agreed with the customer.
  • Repeat the full sequence 50 times without restarting runtime. Expect no growing memory use, no orphaned remote sessions and no focus failures.
  • Disconnect the network to one remote-session target. Expect a defined failure state for that source and no effect on the other monitors.
  • Play camera video while WinCC cycles pictures at full tag load. Expect no visible frame drops and runtime response in its normal range.
  • Restart the pulpit PC. Expect every monitor to return to its defined start-up source without operator action, with the fixed alarm picture visible first.

The decision #

  • If reducing the monitor count is the whole goal and a KVM is acceptable, use one. It switches signals, every source keeps its native frame rate, and no HMI software is involved. This project excludes it, so the branch is closed unless the requirement is renegotiated.
  • With the KVM excluded and the WinCC library, faceplates and structures to keep: stay on WinCC and embed per class — video locally, MES and other Windows software as sessions or foreground windows, WinCC natively.
  • If a source must appear on a monitor that runs no WinCC runtime, give that monitor its own client or panel PC and apply the same session or foreground method there.
  • If the goal is a strategic single platform for navigation as well, scope WinCC OA as a new parallel project. There is no conversion, so budgeting it as a migration is budgeting fiction.

Questions asked

Can a monitor without a WinCC runtime take part in the switching?

No. An embedded control only occupies space inside a WinCC picture, so a monitor with no runtime on it cannot show one. Give that monitor its own client or panel PC running the runtime, then apply the same methods there: a remote desktop or VNC session for the Windows application, or a foreground switch for locally running software, driven by its own request tag.

Why does camera video stutter inside a remote desktop session?

A remote session transmits compressed pictures of screen changes, not a continuous video stream. With the example camera at 25 fps, a session delivering 10 screen updates a second shows roughly every second or third frame and adds network latency on top. Decoding the stream directly on the pulpit PC keeps the camera's native frame rate, provided that PC has processor and graphics headroom for decoding plus the WinCC runtime.

What values should the PLC write to select a source?

Use one integer request tag per monitor and keep the meaning fixed in one mapping table that both the PLC program and the HMI script read. A workable example set is 0 for no request and leave the display as it is, 1 for the WinCC picture, 2 for camera video, 3 for the MES session and 4 for the measuring-device session. A value outside the table should be ignored, not treated as a fault.

Is it acceptable to switch the alarm display with the sequence?

No. Alarm display and acknowledgement stay on a monitor showing a fixed picture that the switching sequence never changes, and no safety-relevant function is routed through a switched source. The switched monitors can carry video, MES and auxiliary applications, but an operator must always be able to see and acknowledge plant alarms without depending on a session, a network path or a script.

Can an existing WinCC project be converted to WinCC OA?

No conversion exists between the two engineering systems, so a move means rebuilding the project: pictures, libraries, faceplates and structure types are re-created by hand. For a source-switching requirement that cost is far higher than embedding the extra sources in the existing WinCC project. Choose WinCC OA only as a strategic platform decision, scoped as a new project running in parallel.

Keep reading

  • Explainer

    What HMI user memory initialization clears and what it protects

    Initialize User Memory is the panel's own documented way to erase a loaded application before reuse. Its password authorizes the erase only; it never removes a project's write protection. Capture recipe and log data first, prove the wipe by the restart, and replace the terminal when the erase or the tooling cannot be done.

    HMI and touchscreens

  • Explainer

    Why no HSP adds the Panel PC 477B to WinCC flexible 2005

    There is no HSP for the Panel PC 477B under WinCC flexible 2005, and none was published. The x77 panel PC family (477B, 677B, 877B, 670) appears only in the WinCC flexible 2007 and 2008 hardware catalogs. Configure in WinCC flexible 2008 and migrate any 2005 or 2007 project there before transferring it to the panel's preinstalled 2008 runtime.

    HMI and touchscreens

  • Selection guide

    Splitting recipe control and setpoints across oven HMI stations

    Give each oven a simple station for recipe select, load and a bounded setpoint trim; store recipe tables in the controller so a swapped or rebooted station loses nothing; move recipe authoring, long-term logging and alarm email to one office PC runtime. Count stations against the controller's documented connection limit.

    HMI and touchscreens

Running a PanelView HMI at -20°C Without Ghosting the LCD