Why no HSP adds the Panel PC 477B to WinCC flexible 2005
Short answer
There is no HSP for the Panel PC 477B under WinCC flexible 2005, and none was published. The x77 panel PC family (477B, 677B, 877B, 670) appears only in the WinCC flexible 2007 and 2008 hardware catalogs. Configure in WinCC flexible 2008 and migrate any 2005 or 2007 project there before transferring it to the panel's preinstalled 2008 runtime.
On this page
None exists, and searching for one costs you a day for nothing. There is no hardware support package that adds the SIMATIC Panel PC 477B to WinCC flexible 2005, because the whole x77 panel PC family — 477B, 677B, 877B and 670 — was never part of the 2005 hardware catalog and never backported into it. The HSPs published around the 2005 release cover a different, older panel generation. Configure the panel in WinCC flexible 2008, and open any existing 2005 or 2007 project in the 2008 engineering tool first so it migrates before the transfer to the panel's preinstalled 2008 runtime.
What a hardware support package can and cannot do #
An HSP in WinCC flexible is a vendor-published add-on that inserts device entries into the engineering tool's hardware catalog without installing a full service pack. Each HSP is scoped to one engineering version and to one explicit list of devices, and it installs from the engineering tool's options area, where the installed device support is listed.
That scoping is the whole point: if a device appears on no HSP published for your engineering version, no download issued for that version can make the catalog list it. The catalog entry has to come either from the tool version itself or from an HSP that names the device by its own device type. An HSP cannot teach an older tool about a device family that postdates it.
The 2005-era HSP list, in numbers #
Siemens entry ID 19241467 documents the HSP of 05-30-2005: it targets WinCC flexible 2004 SP1 and adds device support for exactly five devices — OP 73micro, TP 177micro, OP 73, OP 77A and TP 177A. Those are the micro panels and the 70-series operator panels with direct keys. No panel PC appears anywhere in the 2005-era HSP scope.
Here is the worked example that settles the question. The x77 family has four members: Panel PC 477B, 677B, 877B and 670. Five devices on the 2005-era HSP list, four devices in the x77 family, intersection: zero devices. An empty intersection is a hard limit, not a missing file — no combination of HSP downloads for the 2005-era releases can produce this panel's entry in the catalog.
The decision follows directly: stop looking for an HSP and move the configuration to the tool version the family was built for.
The engineering tool the x77 panel was built for #
The whole x77 generation is configured in WinCC flexible 2007 or 2008. The Panel PC 477B ships with WinCC flexible 2008 runtime preinstalled, and the 2008 engineering tool is its matching configuration environment. That pairing — 2008 tool on your PC, 2008 runtime on the panel — is the documented support path for this device, and every transfer step below assumes it.
If you are mapping out which tool goes with which target before you start, the general rule is laid out in article:which-hmi-software-works-with-which-hmi-panel-hardware, and the version checks worth running on your engineering station are in article:checking-hmi-engineering-software-before-a-panel-replacement.
What the absence looks like in WinCC flexible 2005 #
In the 2005 tool the panel simply does not exist as a selectable device: it is missing from the device selection list, and there is no panel PC entry under the device families it could belong to. If a project created in a later tool is offered to the 2005 tool, the tool reports the device as not supported by the version and refuses the project rather than silently converting it.
Both symptoms mean the same thing, and neither is a corrupted installation: the device object is not in that tool's catalog, and no HSP issued for that generation of the tool contains it. Reinstalling WinCC flexible 2005 or hunting newer HSP files will not change the catalog.
Moving a WinCC flexible 2005 project onto the panel #
The project does not have to be rebuilt from scratch. Open the 2005 project in WinCC flexible 2008 and the engineering tool migrates it automatically as part of opening: the project data is rewritten to the 2008 structure, the device selection is refreshed, and the project then compiles and transfers like any native 2008 project. Keep a backup of the original 2005 file before you open it, read the migration messages, resolve anything flagged, then recompile and download to the panel. Running the result on a PC runtime target follows the same pattern described in article:running-a-wincc-flexible-2008-project-in-pc-runtime.
A direct transfer of the unmigrated 2005 file to the panel's runtime does not work. The 2008 runtime only accepts projects in its own engineering format, so migration in the 2008 tool is the mandatory step, not an optional tidy-up.
Why a 2007 project is not enough either #
A project developed in WinCC flexible 2007 also has to pass through the 2008 engineering tool before it runs on the panel. The preinstalled runtime is the 2008 version and rejects anything built for a different engineering version, so the sequence is always: open the 2007 project in WinCC flexible 2008, let the migration run, recompile, transfer. There is no project state and no tool setting that skips this — not once, and not on any later download.
The decision #
- There is no HSP that adds this panel to WinCC flexible 2005: the 2005-era HSP scope covers the micro and 70-series panels only, and the x77 family was never backported.
- Install WinCC flexible 2008 on the engineering station; it is the tool this panel was validated against and it matches the preinstalled 2008 runtime.
- Open 2005 projects in the 2008 tool; migration is automatic, then recompile and transfer.
- Open 2007 projects in the 2008 tool as well; a 2007 file runs on the panel only after that migration.
The engineering tool version is the limit, not a missing download. Once the project lives in WinCC flexible 2008, the panel transfers and runs like any other device in that catalog.
Questions asked
The Panel PC 477B has WinCC flexible 2008 runtime preinstalled. Can I build the project on the panel itself?
The preinstalled software is the runtime that executes a project at the machine; the engineering tool is a separate product installed on your engineering PC. You still need WinCC flexible 2008 on that PC, plus a transfer connection to the panel, to build, migrate and load the project.
Does the HSP dated 05-30-2005 install into WinCC flexible 2005?
No. It targets WinCC flexible 2004 SP1, so it predates the 2005 release itself. Its device scope is the micro panels and the 70-series operator panels only, with no panel PC of any generation, so it cannot help with this target under any WinCC flexible version.
What happens when I open a WinCC flexible 2005 project in the 2008 tool?
The engineering tool migrates the project automatically as part of opening it, rewriting the project data to the 2008 structure. Read the migration messages, resolve any flagged objects, recompile and transfer. Keep an untouched backup copy of the original 2005 file first, because the opened project is converted, not preserved.
Can I skip the migration and send the 2007 project file straight to the panel?
No. The runtime preinstalled on the panel is the WinCC flexible 2008 runtime and it only accepts projects from the matching engineering version. Open the 2007 project in WinCC flexible 2008, let the migration run, recompile and transfer. That sequence applies every time, not only the first download.