Troubleshooting
Why TIA Portal V14 shows only Basic panels under WinCC Basic
Short answer
TIA Portal V14 lists no Comfort Panels when the installed engineering scope is WinCC Basic, which supports the Basic Panel family only. Comfort Panels need at least WinCC Comfort, so install that edition first; an HSP then covers a single missing model and never the family-wide gap.
On this page
- Why does TIA Portal V14 show only Basic panels in the device catalog?
- Which WinCC edition engineers which panel family?
- How do you confirm which WinCC edition your PC actually has?
- Why can't you fix it by reopening or migrating the project?
- When does one missing Comfort model mean an HSP instead?
- How do you fix a Basic-only installation on V14?
- What should you see after the fix?
- Does the same edition rule apply to newer TIA Portal releases?
- Questions asked
A fresh TIA Portal V14 station that lists Basic Panels and nothing else under HMI devices is not broken, and your panel is not discontinued: the installed engineering scope is WinCC Basic. That scope carries device support for the Basic Panel family and nothing above it, while every Comfort Panel needs at least WinCC Comfort. One rule splits the fault into two branches with different fixes — an absent Comfort family points at the edition, and one missing model inside a visible Comfort family points at a Hardware Support Package (HSP) or an image-version mismatch. This article shows how to read the catalog symptom, confirm the installed scope, apply the matching fix, and verify your exact panel becomes selectable.
Why does TIA Portal V14 show only Basic panels in the device catalog? #
Because the installed engineering scope is WinCC Basic, and that edition carries device support for the Basic Panel family only, so the entire Comfort Panel family is absent from the catalog until the Comfort edition is installed on the same V14 station.
The catalog mirrors the engineering tier that was installed, not the panel market or the installation media. Leaving the scope at Basic during setup means the installer adds no Comfort Panel device support, and no amount of searching, filtering or restarting makes the family appear. The symptom pattern is consistent enough that the first check takes one look:
| Catalog symptom | What it means | Next action |
|---|---|---|
| No Comfort Panel entries anywhere in the HMI catalog | Installed scope is Basic | Install the Comfort edition |
| Comfort family present, one model missing | Edition covers the family; that model needs an HSP or a matching image version | Check the panel's technical data |
| Family and exact model present | Device support is complete | Create the device and configure it |
A still earlier failure looks similar from the start screen: when TIA Portal offers no HMI entry at all, the WinCC engineering component is missing entirely rather than reduced to Basic, which is the case the article on installing WinCC Engineering when TIA Portal shows no HMI option covers.
Which WinCC edition engineers which panel family? #
WinCC Comfort is the minimum edition for Comfort Panels: WinCC Basic engineers Basic Panels only, Comfort adds the Comfort and mobile panel families, Advanced adds the PC runtime Advanced, and Professional adds RT Professional for SCADA-sized stations.
The four editions build on each other, and each rung unlocks device entries in the catalog:
| Edition | Engineering scope |
|---|---|
| WinCC Basic | Basic Panels |
| WinCC Comfort | Basic Panels plus Comfort Panels and mobile panels |
| WinCC Advanced | the Comfort scope plus WinCC Runtime Advanced on a PC |
| WinCC Professional | the Advanced scope plus WinCC RT Professional for PC-based SCADA stations |
Two consequences follow. First, the edition decides the device catalog, so a runtime license on the target panel or PC never adds engineering capability on the engineering station — keep the engineering edition and the runtime license as separate checks, the way the article on whether a WinCC Professional entry means SCADA runtime is installed treats them. Second, the ladder is additive: a higher edition engineers everything below it, so Comfort Panels remain configurable under Advanced and Professional.
How do you confirm which WinCC edition your PC actually has? #
Read the installed-software list before changing anything: the WinCC component installed alongside TIA Portal names the scope, and the license manager shows whether a matching Comfort or higher key is present on the same PC.
Three places on the station should agree, and checking them takes minutes:
- The Windows installed-programs list, where the WinCC component entry names its scope next to the TIA Portal release.
- The product information that TIA Portal itself reports for the installed automation software.
- The license manager installed alongside TIA Portal, which lists the keys the station holds; the key must match the scope you intend to use.
If all three say Basic, you have the cause and can go straight to the fix below. If the component says Comfort but the family is still missing, check which instance your shortcut launches — several TIA Portal releases can sit side by side on one PC, and an icon pointing at the wrong install reproduces the symptom exactly. When the component, the license and the launched instance all say Comfort, move to the single-model branch further down instead of reinstalling anything.
Why can't you fix it by reopening or migrating the project? #
Project content cannot extend engineering scope: reopening, migrating or recreating a project never adds the Comfort Panel device class that a WinCC Basic installation lacks, so correcting the installed edition always comes before any project-level work.
The missing family is a property of the installed software, not of the project file. A project written on a Comfort-capable station references device support your station does not carry, so expect the Comfort device to be reported as unsupported rather than configurable. Resaving cannot create a catalog class the installed edition does not contain, and migrating the project to another TIA Portal release moves it forward in version but not up the edition ladder. Correct the installation first, then reopen the project and configure the device normally.
When does one missing Comfort model mean an HSP instead? #
Only when the rest of the Comfort family is visible in the catalog: an HSP adds one specific hardware entry to an edition that already engineers that family, so a family-wide gap is never an HSP case.
An HSP is the manufacturer's support package for hardware entries that your installed TIA Portal catalog does not yet contain; it operates inside an edition that already covers the family and never upgrades the edition itself. A reported worked case of the split: the SIMATIC HMI TP1500 COMFORT OUTDOOR became projectable from WinCC Comfort V13 SP1 once its HSP was installed — the Comfort scope supplied the family support, and the package supplied that one outdoor variant. Decide the branch with three checks:
- Confirm that other Comfort models appear in the catalog; if the whole family is absent, go back to the edition fix.
- Read the exact model designation from the panel nameplate or order data, because a similar-looking variant in the catalog is not interchangeable.
- Check that panel's technical data against your installed release; the data states the required engineering version and whether an HSP is specified.
For the model-specific search itself, the article on an HMI model missing from the programming software list walks the lookup step by step. The same visible-family-but-no-usable-device pattern appears on newer releases too — the article on why TIA Portal V20 finds 0 compatible Unified Comfort panels covers that variant, and a panel whose image version is newer than your engineering version can fail at download rather than in the catalog.
How do you fix a Basic-only installation on V14? #
Install the WinCC Comfort engineering component that matches your V14 release from the manufacturer or an authorized distributor, complete its licensing, restart the engineering station and reopen the device catalog — the Comfort Panel family then appears.
Work in this order so the licensing and catalog checks land on a stable installation:
- Record the exact installed release, V14 or V14 SP1, because the component you add must match it.
- Back up the project with your normal project backup before touching the installation.
- Run the installation for that release and add the Comfort engineering component; installing an HSP at this point is not a substitute for the edition change.
- Complete the licensing step for the new component through the license manager installed with TIA Portal, so the installed scope and the key agree.
- Restart the engineering station, reopen the project and check the HMI device catalog again.
One operational note: the running panel keeps executing its loaded project no matter what your engineering PC has installed, but do not verify the fix by downloading to a panel on a live line — prove the new project on a bench panel or during planned downtime.
Decision: if the family now appears, create the device and continue. If the family appears but your exact model is still absent, the edition problem is solved and the remaining gap is the model-specific branch above. If the family is still absent, the component did not land in the instance you launch — repeat the confirmation checks before installing anything else.
What should you see after the fix? #
The Comfort Panels family appears under HMI devices, your exact model designation becomes a selectable entry, and TIA Portal accepts the device as a Comfort Panel instead of offering only Basic alternatives.
Close the fault with four verifications:
- The installed-programs list and the license manager both name the Comfort edition or a higher one.
- The HMI device catalog shows the Comfort Panel family.
- Your exact model designation matches a selectable catalog entry.
- Creating the device exposes Comfort-level screens, tags and functions rather than a Basic-limited substitute.
If one check fails, map it back: a failed first check means the licensing step is incomplete; a failed second means the wrong instance or an incomplete installation; a failed third sends you to the HSP and image-version branch; a failed fourth means the device was created under the old scope and should be deleted and re-created in the corrected project.
Does the same edition rule apply to newer TIA Portal releases? #
Yes — Basic engineers Basic Panels only in every TIA Portal release, so the installed edition, not the version number, decides which families appear; what changes between releases is the model list, image versions and HSP set.
The diagnosis in this article therefore transfers unchanged: a family-wide absence always means scope, and a single missing model inside a visible family means a model-specific gap. Newer releases add families such as Unified Comfort panels, which come with their own image-version and compatibility requirements, so a model absent there may need an image update or an HSP rather than an edition change. Check the family first, then the model; the order never reverses.
Questions asked
Does an HSP ever add Comfort Panel support to WinCC Basic?
No. A Hardware Support Package attaches one specific hardware entry to an edition that already engineers that device family. On a Basic-only station the whole family is absent, so the package has nothing valid to attach to. Correct the edition first, then add an HSP only if one model is still missing afterward.
Can a WinCC Basic station open a project that contains a Comfort Panel?
Treat it as inspection only: the station lacks the device support the project was written against, so the Comfort device cannot be configured, compiled or downloaded from there. If you need to look at screens or tags, open a copy and leave the original untouched, because resaving under a reduced scope cannot restore the missing device support later.
Where do the engineering component and the HSP come from?
Both come from the manufacturer's official support channels or an authorized distributor, and keeping unofficial download sources away from an engineering station is part of keeping the catalog trustworthy. Match each package to your exact release, V14 or V14 SP1, because a component built for a neighboring release either refuses to install or drags the project into a version migration you did not plan.
Do you need the Advanced edition when a PC visualization is added later?
Only when the same station must also run the PC runtime, because that runtime capability is what the Advanced rung adds; the panel engineering itself stays within the Comfort scope. Since each higher edition covers everything below it, a later upgrade is additive and the existing panel project keeps working.