Troubleshooting
TIA Portal shows no HMI option: install WinCC Engineering
Short answer
WinCC Runtime Advanced only executes HMI projects; it cannot create them. TIA Portal shows no HMI device option until the matching WinCC engineering package (Basic, Comfort/Advanced or Professional) for your TIA Portal version is installed and licensed. Reinstalling the runtime does nothing.
On this page
- Why does TIA Portal show no HMI option when Runtime Advanced is already installed?
- What is the difference between WinCC runtime and WinCC engineering?
- Which WinCC engineering package do I need for WinCC Runtime Advanced?
- How do I check what is actually installed on the PC?
- What about the engineering license and the 21-day trial?
- How do I install the engineering package and verify the fix?
- What if the HMI option appears but the Runtime Advanced target does not?
- Questions asked
If TIA Portal V11 shows no HMI device option while WinCC Runtime Advanced V11 SP2 is installed, the cause is a missing engineering component, not a broken runtime. The runtime executable only runs a compiled project; creating, editing and compiling an HMI project requires the separately installed WinCC engineering software for the same TIA Portal version, with its own license. Reinstalling the runtime cannot fix this. Work through the checks below in order.
Why does TIA Portal show no HMI option when Runtime Advanced is already installed? #
Because installing a runtime adds an executable, not an editor. TIA Portal builds its device catalog from the engineering packages installed on the computer, and WinCC Runtime Advanced V11 SP2 contributes no engineering functionality, so the HMI entries never appear no matter how many times the runtime is installed or repaired.
When you started the runtime installer and it reported the product was already present, that message identified only the component being installed. It confirms runtime files exist on disk and nothing more. The missing piece is the engineering package, which installs the HMI device types, editors and compile capability that TIA Portal displays. Engineering software is the configuration environment used to create screens, tags and alarms; runtime software executes the compiled result. One cannot substitute for the other.
What is the difference between WinCC runtime and WinCC engineering? #
Engineering creates and compiles the project; runtime runs it. Both ship under the WinCC name, both come in versions, and both need licenses, but they are separate installations with separate purposes.
| Component | Purpose | What it tells you when present |
|---|---|---|
| TIA Portal V11 environment | Hosts the installed engineering functionality | Presence alone proves no HMI engineering is installed |
| WinCC engineering package | Creates and configures HMI applications | Required on the development computer |
| WinCC Runtime Advanced V11 SP2 | Executes a compiled runtime application | An "already installed" message proves nothing about engineering |
| Engineering license | Authorizes the selected engineering package | Must match the package used for development |
The decision: if the installed-software inventory lists runtime but no WinCC engineering component, that is the fault, and the fix is one engineering installation.
Which WinCC engineering package do I need for WinCC Runtime Advanced? #
The package follows the target, not the product name. Siemens splits WinCC engineering into Basic, Comfort/Advanced and Professional tiers, differing in supported targets and features: Basic covers entry-level panels, Comfort/Advanced adds mobile and keypad panels plus the PC runtime, and Professional covers PC SCADA. For a WinCC Runtime Advanced target you need the Comfort/Advanced engineering package or higher; Basic will not offer the target.
Match versions too. Engineering and runtime must sit on the same release, here V11 SP2, before a compiled project downloads and runs cleanly. If you later migrate to a newer release, plan the runtime upgrade at the same time as the engineering upgrade; the same discipline applies to projects such as running a TIA Portal V14 HMI on WinCC Runtime Advanced (article:run-a-tia-portal-v14-hmi-on-wincc-runtime-advanced).
How do I check what is actually installed on the PC? #
Open the operating system's installed-software inventory and write down every Siemens product name and version before changing anything. You are looking for one specific fact: does any entry identify WinCC engineering, or does the list contain only WinCC Runtime Advanced?
- Record the complete product names and version numbers, including service packs.
- Distinguish any entry containing "engineering" from entries containing "runtime".
- Note the TIA Portal version installed, since the engineering package must match it.
Expected reading: a list showing runtime present and engineering absent, which explains the missing HMI option completely.
What about the engineering license and the 21-day trial? #
The V11 SP2 trial can be evaluated for 21 days; that is the documented evaluation period for the trial download. Use it to prove the fix on the bench, but do not build a production workstation on an expired evaluation. For ongoing work, order the engineering license that matches the package you installed, Basic, Comfort/Advanced or Professional.
A license authorizes use; it is separate from the installed program files. Two different checks answer two different questions: the installed-software inventory answers whether the engineering files exist, and the license check answers whether you may use them. Check license status with the Siemens licensing tools supplied with the software.
How do I install the engineering package and verify the fix? #
Close TIA Portal, run the engineering installation for the matching version, accept any restart it requests, then verify in this order:
- Reopen the installed-software inventory and confirm the engineering component now appears with its version.
- Check the license status for that package.
- Open TIA Portal, create a new test project, and open the add-device workflow.
- Confirm HMI entries are now offered and select the WinCC Runtime Advanced target.
- Add the target, place one static text object on a screen, compile, and download to the runtime.
The test project matters: it separates workstation configuration from anything specific to your existing project. The static screen proves the engineering-to-runtime path without making PLC addressing or network setup part of the first test. Once that path works, controller communication is a separate topic; for that stage, see the fix for a WinCC runtime that connects to the PLC only via TIA Portal (article:fix-wincc-runtime-that-connects-to-the-plc-only-via-tia-portal). A runtime that then fails to start a downloaded project has its own diagnosis in why WinCC runtime reports project is locked (article:why-wincc-runtime-reports-project-is-locked-and-how-to-recover).
What if the HMI option appears but the Runtime Advanced target does not? #
Then the engineering package installed is a lower tier than the target needs, most often Basic where Comfort/Advanced was required. The tiers are not interchangeable labels for one editor: each package installs only the device types it supports, so Basic engineering shows panel targets but no PC runtime target.
Distinguish the three symptoms before changing more software: no HMI choices at all means the engineering component is missing entirely; HMI choices without the Advanced target means the wrong package tier; a target that opens but reports a licensing message means the files are right and the license is not. Each symptom has exactly one corrective action, in that order: install engineering, install the correct tier, then resolve the license.
If the target list is empty even inside the PLC station view instead of the add-device workflow, that is a different insertion symptom covered by the SIMATIC HMI Station missing in STEP 7 article (article:why-simatic-hmi-station-is-missing-in-step-7-insert-station).
The decision, case by case: runtime-only installation means install the matching Comfort/Advanced engineering package and its license; wrong tier means upgrade the package; wrong version means align engineering and runtime to the same release; expired evaluation means purchase the engineering license for a permanent workstation.
Questions asked
Do I need a license for WinCC Runtime Advanced as well as the engineering package?
Yes, they are two separate licenses with two separate jobs. The engineering license authorizes creating and compiling the project in TIA Portal; the runtime license authorizes the PC that executes the finished application. A workstation licensed for engineering still needs a runtime license (or an evaluation within its permitted period) on the machine that runs the project.
Can a project created with WinCC engineering run on Runtime Advanced of a different version?
Match the major version and service pack between the engineering tool and the runtime. A project edited in a newer TIA Portal version generally cannot be opened or run by an older runtime, and the compile step must complete without errors before download. Keep both components on the same release, for example engineering and runtime both at V11 SP2.
Does WinCC Basic engineering work for a Runtime Advanced target?
No. Basic engineering covers entry-level panels only. The package distinction follows the target: Basic for first-line panels, Comfort/Advanced adding mobile and keypad panels plus the PC runtime, Professional for PC SCADA. So the Basic tier will not offer the PC runtime target; you need Comfort/Advanced or higher.
Why does the installer say WinCC Runtime Advanced is already installed?
That message identifies only the component the installer was asked to install. It checks the runtime files on disk and reports them present, which is correct, but it says nothing about the engineering package. Treat it as confirmation that the runtime is there, not as evidence that HMI engineering exists.