IMDTouchKnowledge BaseShop main store

Troubleshooting

Why WinCC Runtime Advanced Has No Screens Folder

HMI and touchscreens Published 7 min read

Short answer

The Screens folder is missing because the installed engineering edition cannot configure a WinCC Runtime Advanced PC station: WinCC Basic covers panels only. Install WinCC Advanced or Professional, license it, add the PC station in a new clean project, and the tool generates the folder. The proxy-device message is a later check, and reinstalling TIA Portal does not fix it.

On this page
  1. What the missing Screens folder means
  2. Why WinCC Basic stops at the panel
  3. Steps that restore the Screens folder
  4. Working the V13 case: WinCC Basic at work, Professional at home
  5. The proxy-device message is a later check
  6. If the folder is still missing after the edition fix
  7. Questions asked

The Screens folder does not get deleted — it never gets created. When you add a PC station configured for WinCC Runtime Advanced in TIA Portal and the HMI RT branch shows no Screens folder, the workstation's installed engineering edition almost always cannot configure a PC runtime station at all. WinCC Basic, the edition that ships with STEP 7 Basic, engineers panel-type HMI devices and stops there, which is why every panel you add works while the PC station comes up hollow. The fix is to install an edition that engineers PC runtime — WinCC Advanced or WinCC Professional — license it, and build the station in a new clean project. The proxy-device message on the configuration page is a correlated symptom, not the cause, and reinstalling TIA Portal is a last check, not the fix.

What the missing Screens folder means #

The Screens folder is an output of the engineering tool. TIA Portal generates it when a station is added and the installed edition supports that station type; there is no menu command that creates it by hand. An absent folder means the engineering step never ran for that station, not that the project is damaged.

WinCC Runtime Advanced is PC-based visualization for single-station systems, so its engineering has to come from an edition that supports PC runtime targets. The runtime side is licensed separately from the engineering side: a runtime key belongs on the PC that runs the project, and the workstation needs its own engineering license. WinCC RT vs RC Licenses and Moving a Runtime Key covers how those keys differ and how a runtime key moves between PCs.

Why WinCC Basic stops at the panel #

The WinCC editions in TIA Portal split by target, not by quality. WinCC Basic comes with STEP 7 Basic and engineers panel-type HMI devices; WinCC Advanced adds the PC station running WinCC Runtime Advanced; WinCC Professional extends to larger data volumes and higher-end architectures. That split decides which settings and station types exist on your machine, and it bites in more places than this one — why a WinCC Professional DateTime format is missing compared with the Advanced edition is the same mechanism showing up as a missing setting instead of a missing folder.

The trap in this fault is that WinCC Basic keeps working for panels. You can add panel HMI devices, configure screens on them and download them, and none of that proves the PC runtime scope is present. In the reported case the work PC created other HMI panels without problems and failed only at the PC station — that pattern is the signature of an edition limit, not a project defect. For the full ladder of WinCC editions and tools, WinCC Explorer vs Advanced, Professional, Flexible and Unified lays them out side by side.

Steps that restore the Screens folder #

  1. Check the installed edition on the workstation before anything else — the TIA Portal setup shows what is installed. If it reads WinCC Basic, the PC station cannot be configured, whatever else works on that machine.
  2. Do not count panel creation as proof. Under Basic, panels are created normally and the PC station is not; the passing panels tell you nothing about PC runtime support.
  3. Install WinCC Advanced or WinCC Professional for your TIA Portal version and license the engineering with its license key. Siemens' licensing documentation requires a license key for the installed editions, and a valid Basic license does not unlock Advanced engineering.
  4. Create a new clean project rather than upgrading or copying the old one, add the PC station with WinCC Runtime Advanced, and check the HMI RT branch for the Screens folder.
  5. Add a screen under the folder and open the screen editor to confirm the whole visualization chain works.
  6. Only if the folder is still missing with a supporting edition and a valid license, move on to the proxy-device message and the installation state as a separate fault.

If your symptom sits one step earlier — TIA Portal shows no HMI entry at all — the fix is the same kind of edition check: TIA Portal shows no HMI option: install WinCC Engineering walks through that case.

Working the V13 case: WinCC Basic at work, Professional at home #

Inputs, each from the reported case: TIA Portal V13 with all reported updates installed; a new, clean project rather than an upgraded one; a PC station configured for WinCC Runtime Advanced whose HMI RT branch shows no Screens folder, with a message about a proxy device at the bottom of the configuration page; the work workstation running WinCC Basic; the home workstation running WinCC Professional, where the same creation works without problems. The documented rule behind them: WinCC Basic engineers panel devices, and a PC station running WinCC Runtime Advanced needs WinCC Advanced or Professional engineering.

The rule in words: the Screens folder is generated only when the installed edition supports the station type, so the setup that fails is the one whose edition lacks PC runtime engineering.

The comparison, variable by variable: TIA version — V13 on both machines, no difference. Project type — a new clean project on the failing machine, the same creation workflow on the working one, no difference. Failure pattern on the work machine — panels pass, PC station fails, so the failure is confined to exactly the station type the Basic scope excludes: 1 failing station type out of the 2 attempted, 1 edition difference between the two machines (Basic versus Professional), and 1 exact match between the failing station type and the documented Basic limit. All three counts point at the edition.

Result: the Screens folder is absent because the work workstation's WinCC Basic cannot configure a WinCC Runtime Advanced PC station; the proxy message rides along with it.

Decision: with WinCC Basic installed, the PC station will never show the folder, and no amount of rebuilding in Basic changes that. Install WinCC Advanced or Professional with its license, rebuild in a new clean project, and the folder is created. The order matters: the edition check comes before any reinstall or proxy-device work, because reinstalling on Basic burns the effort — another user with the same symptom reinstalled and still had no runtime screens.

The proxy-device message is a later check #

The message is real, and it is not established as the cause. In the reported case the project never used a proxy device, all reported updates were installed, and a new clean project showed the same behavior — three facts that argue against the message being the driver. The proxy device is a legitimate hardware-catalog object: V13 SP1 lists it in the hardware catalog under Controllers, and installing its GSD description is normally relevant to direct buttons on a panel, which this project did not use.

Reinstalling TIA Portal sits last for the same reason: it replaces program files but not the edition's engineering scope, and it did not restore the runtime screens for the user who tried it. Verify the edition and the license first; chase the proxy message only when a supporting, licensed edition still fails.

If the folder is still missing after the edition fix #

Two checks remain. First, connection leftovers: a stale proxy connection from earlier work that was never fully deleted can keep the message alive, so clear any remains of old proxy connections in the project. Second, the installation state itself — with the edition and license confirmed correct, damaged installation components become the plausible cause.

Once the folder exists, mind the load side as well: if the version of WinCC Runtime Advanced installed on the target device does not match the configured device version, the project cannot be loaded, so keep the runtime on the target PC at the version the project was configured for. From there, generating and loading the runtime file is the usual next step; Run a TIA Portal V14 HMI on WinCC Runtime Advanced follows that flow.

Questions asked

Why did TIA Portal V11 handle WinCC RT Advanced but V13 does not?

An installation that engineered a Runtime Advanced station under V11 must have carried an edition whose scope covered it. TIA Portal versions can be installed in parallel, so the working copy may still sit beside V13 on that machine. Check which edition each installed version actually carries before blaming the version change; WinCC Basic's scope has not grown to include PC stations.

Does reinstalling TIA Portal bring the Screens folder back?

Not on its own. A reinstall replaces program files but does not change the edition's engineering scope, and a user with this exact symptom reinstalled and still had no runtime screens. While WinCC Basic is the installed edition, the PC station comes up without a Screens folder every time; only WinCC Advanced or Professional changes the outcome.

Which license keys does a WinCC Runtime Advanced project need?

One key per side. The engineering workstation needs a WinCC Advanced or Professional key, and Siemens' licensing documentation requires a key for each installed edition. The runtime PC needs a WinCC Runtime Advanced runtime key, sold in power-tag counts such as 128, 512 and 2k. A valid WinCC Basic license does not unlock Advanced engineering.

Can the Screens folder be created by hand?

No. The engineering tool generates the folder when a station is added under an edition that supports PC runtime, and no menu command creates it manually. A folder made by hand carries none of the station's generated configuration, so the supported path is to install WinCC Advanced or Professional and let the tool build the structure.

Keep reading

  • Troubleshooting

    TIA Portal shows no HMI option: install WinCC Engineering

    WinCC Runtime Advanced only executes HMI projects; it cannot create them. TIA Portal shows no HMI device option until the matching WinCC engineering package (Basic, Comfort/Advanced or Professional) for your TIA Portal version is installed and licensed. Reinstalling the runtime does nothing.

    HMI and touchscreens

  • How-to

    Run a TIA Portal V14 HMI on WinCC Runtime Advanced

    Compile the HMI for its configured WinCC RT Advanced target, transfer the compiled application, and select it in RT Loader. Match the configured device version to the runtime installed on the workstation. Verify Windows support and use a valid runtime license sized for the application.

    HMI and touchscreens

  • How-to

    Selecting a WinCC Unified PC Target in TIA Portal

    An IPC can host WinCC Unified as a PC-based HMI. If the SIMATIC HMI application list shows only WinCC RT Advanced, your TIA Portal installation is missing the Unified PC engineering option: add a PC station, add the SIMATIC WinCC Unified PC application, then match the runtime version and license on the target computer. The hardware is not the deciding check.

    HMI and touchscreens