Running a PanelView HMI at -20°C Without Ghosting the LCD
Short answer
Yes, with one condition: hold the enclosure air at +5 °C or warmer so the powered terminal never leaves its 0…55 °C operating rating, and expose the screen to -20 °C only for minutes at a time — an arrangement Rockwell Automation knowledge answer 707514 accepts. If the glass must sit bare at that temperature all shift, no PanelView is rated for it; run FactoryTalk View Machine Edition on a wide-temperature touchscreen computer instead.
On this page
A PanelView Plus 7 terminal is rated 0…55 °C while it is operating and -25…+70 °C only while it is off. That split decides your -20 °C site: keep the terminal inside a heated enclosure whose air never drops below +5 °C, expose the screen to the cold only for minutes at a time, and the installation is inside the rating — an arrangement Rockwell Automation's knowledge answer 707514 accepts. If the glass itself must sit bare in that air for a whole shift, no PanelView carries that rating, and the right move is a wide-temperature touchscreen computer running the same FactoryTalk View Machine Edition runtime.
The rating: 0 °C operating, -25 °C only while off #
The PanelView Plus 7 Standard technical data lists operating at 0…55 °C and nonoperating at -25…+70 °C, with relative humidity 5…95% without condensation. The Performance terminals (publication 2711P-TD009) list 0…55 °C for the 6.5-in through 15-in sizes and 0…50 °C for the 19-in Series A. Across the current family — Standard, Performance, ArmorView — every datasheet carries the same cold floor: 0 °C powered, -25 °C unpowered. PanelView Plus 6 terminals share it. Some entries in the operator-interface literature list a 0…45 °C upper end for particular variants, so the hot end moves with the catalog number; the cold floor does not.
| Terminal | Operating | Nonoperating |
|---|---|---|
| PanelView Plus 7 Standard | 0…55 °C | -25…+70 °C |
| PanelView Plus 7 Performance, 6.5–15 in | 0…55 °C | -25 °C floor |
| PanelView Plus 7 Performance, 19 in Series A | 0…50 °C | -25 °C floor |
| PanelView Plus 6 | 0 °C floor | -25 °C floor |
Nonoperating covers an unpowered terminal — storage, transport, a spare on a shelf. The moment it draws power, the floor applies, and that includes boot-up. On the hot end of the same rating, mounting orientation and clearance do the moving; the derating rules are covered in portrait HMI panel mounting and temperature derating.
What -20 °C air does to the LCD during an opening #
Liquid-crystal viscosity climbs steeply as the fluid cools, so pixel transitions slow from tens of milliseconds at room temperature to beyond 500 ms at -20 °C. Moving numerals leave visible trails, a static screen smears, and the backlight dims and warms up slowly. This ghosting is the symptom of a cold front glass; it reverses completely once the glass is back above the floor. Damage is a separate mechanism — hours of powered operation far below that limit — and it announces itself as image retention that survives rewarming. A minutes-long opening buys you a hard-to-read screen for those minutes, not a dead panel.
One safety line belongs here: never take a smeared, half-frozen display as the source for a critical decision; confirm the process state at the controller or on a warm indication.
The decision for a cold site #
| Your requirement | Decision | Basis |
|---|---|---|
| Read the screen through a heated window; open the front for minutes at a time | Keep the PanelView, hold enclosure air at the setpoint | The floor governs the powered terminal; brief surface exposure is accepted while the enclosure stays above its minimum |
| Glass directly exposed and touched all shift in the cold | No PanelView carries that rating; move the runtime to a wide-temperature touchscreen computer | 0 °C floor on every current model; -25 °C is nonoperating only |
| Terminal unpowered in the cold — spare, storage, shipment | Acceptable down to -25 °C | Nonoperating rating; restore heat before applying power |
Knowledge answer 707514 (visible with a free account) says, in substance, that the arrangement is acceptable while the enclosure remains above the minimum allowed temperature, and that the screen surface may be exposed to lower temperatures during brief openings. That is the vendor position your concept leans on; put the answer number in the design file. Keep the terminal powered through every opening — its dissipation and the warm air behind it are what hold the electronics inside the rating while the front chills.
Sizing the heater: the arithmetic #
Take an 800 × 600 × 250 mm painted-steel enclosure outdoors at -20 °C ambient, interior held at +5 °C.
- Surface area A = 2(0.8 × 0.6) + 2(0.8 × 0.25) + 2(0.6 × 0.25) = 0.96 + 0.40 + 0.30 = 1.66 m²
- Heat-loss coefficient of painted sheet steel ≈ 5.5 W/(m²·K), a standard enclosure-heater table value; confirm against your heater vendor's table, which also derates for wind exposure
- Temperature difference ΔT = 5 °C - (-20 °C) = 25 K
- Steady-state loss Q = 5.5 W/(m²·K) × 1.66 m² × 25 K = 228 W
- Door-open allowance of +25% for the warm air each opening dumps: 228 W × 1.25 ≈ 285 W
Fit a 300 W PTC heater with an integral thermostat. Set the thermostat to that +5 °C setpoint with its roughly 3 K hysteresis and the air swings between about 3.5 and 6.5 °C — the low point still 3.5 K above the floor. Add an independent thermostat contact that alarms below +2 °C, so a failed heater is caught before the rating is crossed rather than after. Credit the terminal's own dissipation as zero in this calculation: the enclosure then holds setpoint even with the HMI powered down for replacement.
The open-front protocol #
- Keep the terminal powered while the front is open; the warm enclosure air and the panel's own mass are what stay inside the rating.
- Keep each opening to the several minutes the task needs, then close and let the thermostat recover before the next one.
- Never apply power below the floor. If a heater failure or an outage lets the enclosure cold-soak, restore heat first, confirm the interior is back at setpoint, then restart the terminal.
- A terminal carried from the cold into a warm room will collect condensation — the humidity rating is 5…95% without condensation — so let any visible moisture dry before it goes live.
- After any unusually long exposure, look at the display once it is fully warm again: a faint outline that survives rewarming is image retention, which is damage, not cold ghosting.
When the screen itself must live in the cold #
If operators have to touch the glass all shift in air that never warms, the fixed floor rules out every PanelView, and no enclosure trick changes the terminal's datasheet. The path that keeps the Allen-Bradley software stack is FactoryTalk View Machine Edition running on a touchscreen computer chosen for the site: same project source, same EtherNet/IP path to the controller, with the runtime licensed for that PC. The class to specify is industrial panel PCs, and the acceptance line on the datasheet is a documented operating range reaching -20 °C for both display and touch. The migration steps are the ones in planning an HMI terminal replacement from an older operator panel.
Questions asked
How long can the front stay open at -20 °C before it counts as out of spec?
The vendor answer ties acceptability to the enclosure staying above its minimum, not to a printed minute count. The front glass tracks ambient within a couple of minutes, so treat the length of the task — a few minutes — as the ceiling, then close and let the thermostat recover. The line you must not cross is leaving the front open unattended through a shift; that is continuous exposure, which no part of the rating covers.
Can I boot the terminal at -20 °C, since storage goes to -25 °C?
No. Applying power is operating, and the operating floor is 0 °C. The -25 °C figure covers an unpowered terminal only. Warm the enclosure back to its setpoint before switching on — including after a power outage or heater failure that let the cabinet cold-soak overnight, which is the most common way a cold boot happens by accident.
Will the touch input still work while the glass is cold?
Expect it to degrade before it fails. Below the floor the whole terminal, touch layer included, is outside its rating, so taps can lag or drop while the display smears. Make critical entries before opening the front or right after closing it, and never route an emergency stop through a cold, ghosting screen.
What does real cold damage look like, as opposed to ghosting?
Cold ghosting clears within minutes of the glass returning above the floor. Damage is image retention: a faint outline of a fixed screen element still visible after hours at normal temperature, sometimes with a dimmer patch where the backlight has been stressed. If the outline survives a full rewarm, the panel has been run too cold for too long, and it will not clean up.
Is a bigger viewing window better for round-the-clock legibility?
It trades both ways. A larger window lets operators read the screen without opening the front, and every minute the front stays closed saves the heat an opening dumps. But the window is a loss path too, so more glazing means more heater load. Size the window for legibility at working distance, then let the heater arithmetic follow.