How to Find the ProTool Version From the TDOP Project Folder

HMI and touchscreens Published 5 min read

Short answer

The project folder identifies the original engineering release: the .pdb file inside the TDOP subfolder carries version strings, and the runtime on the target Panel PC bounds the candidate versions. Work only on a copied project, because opening it with a newer ProTool triggers a one-way conversion that drops old-panel features.

On this page
  1. Why the version matters
  2. Safety note
  3. Steps to read the version from the project folder
  4. Interpreting the string
  5. Building an environment for the identified version
  6. Decision
  7. Questions asked

The original ProTool release that built a legacy project is written into the project files themselves: open the .pdb file inside the project's TDOP subfolder and read the version strings stored there. The runtime installed on the target Panel PC bounds the candidate versions, so you can confirm the string against the machine. Work on a copied project directory, because opening an older project with a newer engineering tool converts it forward and that conversion cannot be undone.

Why the version matters #

ProTool stores a project as a proprietary database plus a device-specific subtree. Each release extends that schema and the object model of the supported panels. When a newer tool imports an older database it maps the old objects onto the new schema, and anything valid only in the older device drivers is remapped or silently dropped: device-specific screen objects from phased-out panels, function-list entries bound to renamed functions, text and graphic list attributes, recipe and data record structures, and ProTool/Pro runtime options that need version parity with the installed runtime.

In the case behind this article, a project for a Windows NT 4.0-based visualization PC was opened with ProTool V6.0 SP3 on the engineering station, the conversion fired, and features were lost. The project could not be written back in its original format. The required engineering version turned out to be V5.2, which needs Windows NT or, from Service Pack 2 onward, Windows 2000. If the panel is beyond editing and a rewrite is the real answer, the process differs; the guide to replacing an old HMI when no project files exist covers that path.

Safety note #

Take a byte-level copy of the entire project directory, including the TDOP subfolder, before any engineering tool touches it. Work only on the copy; the original stays untouched on its storage.

Steps to read the version from the project folder #

  1. Copy the whole project directory to your engineering station and close every tool that could open it.

  2. Open the TDOP subfolder inside the project directory. ProTool creates it to hold device-specific and generation data, and it stores version information in the files there.

  3. Find the .pdb file in TDOP. Open it in a hex editor or a text viewer and search the readable ASCII or Unicode strings for a version pattern such as 5.2, 6.0, V5 or a service-pack token. Read only: do not save any change.

  4. Right-click each project file and check the Version tab of its file properties. ProTool components frequently carry a file-version resource, which gives a second reading.

  5. Correlate the earliest file creation date in the project with the ProTool release timeline you can confirm from your own license and media archive. This narrows the candidate set when the embedded string is ambiguous.

  6. Cross-check against the target machine. Log on to the Panel PC, open Control Panel, Add/Remove Programs, and record every SIMATIC entry with its version and service pack. Right-click the runtime executable and read the file version on its Properties Version tab, then check the Startup folder or autostart configuration to confirm which runtime the machine launches at boot. The runtime bounds the engineering version: the project was generated by a tool compatible with that runtime.

Interpreting the string #

An embedded version string may identify the database schema level rather than the exact installed service pack. If it resolves only to a major and minor release, for example V5.2, assume the highest service pack you can obtain and verify by opening the backup copy: no conversion dialog means the match is correct, and any conversion prompt means the installed tool is newer than the project, so roll back and step down the service pack. If your TDOP folder is missing files entirely, the companion article on restoring missing PDB files in S7 TDOP projects covers how to rebuild it.

In the documented case the project opened natively only under ProTool V5.2, and opening it with V6.0 SP3 was exactly what triggered the lossy conversion.

Building an environment for the identified version #

ProTool V5.2 predates Windows XP, and the vendor's own compatibility documents confirm the base release was cleared for Windows 95, 98, 98 SE and NT 4.0, with Windows 2000 added in the later service pack levels of V5.x. Installing it on a modern desktop OS is not a supported path and the installer commonly fails outright.

Provision a period-correct OS in a virtual machine: Windows NT 4.0 or Windows 2000 Professional, matching the requirement of your identified version. A VM beats physical hardware because it snapshots cleanly. Take a snapshot after the clean OS install, after each SIMATIC component install, and before the first project open, then roll back rather than repair when something breaks.

Install the engineering software at the identified version and service pack, base release first and service pack second. If the target runs ProTool/Pro RT of the same generation, generate the runtime file from the restored project and download it without upgrading the panel runtime. Upgrading the runtime on a production machine carries its own validation burden, so avoid it unless the change list demands it.

The vendor has phased ProTool out, so the old media and licenses come from your own archive or the vendor's service organization; a forum post will not produce an installer.

Decision #

If the .pdb strings and the target runtime both point to one release, install that exact version and service pack on a supported period OS and edit the copy with no conversion. If the string is ambiguous, use the highest obtainable service pack for the major and minor version and let the absent conversion prompt confirm it. If no version can be recovered from the folder, fall back to the target runtime version as the upper bound, and if the panel itself is the problem, replace the unit and rebuild the project rather than chase a legacy installer.

Questions asked

Why did opening the project in ProTool V6.0 SP3 remove features from it?

Each ProTool release extends the project database schema and the object set of the supported panels. When a newer tool imports an older database, objects or attributes valid only in the older device drivers are remapped to a nearest equivalent or dropped. The conversion is one-way: the project cannot be saved back in the original format, so always open a copied project first.

Which operating system does ProTool V5.2 need?

ProTool V5.2 predates Windows XP. The approved platforms for the base release were Windows 95, 98 and 98 SE plus Windows NT 4.0, with Service Pack 2 for V5.2 adding Windows 2000 support. Run it in a virtual machine with a snapshot taken after the clean OS install and before the first project open.

The version string only shows a major and minor release. Which service pack do I install?

Assume the highest service pack you can obtain for that version, then verify by opening the backup copy. If the tool opens the project without a conversion prompt, the match is correct. A conversion dialog means the installed engineering version is newer than the project, so roll back and install an earlier service pack.

How do I confirm which HMI runtime the Panel PC actually runs?

Right-click the runtime executable, open its Properties Version tab and record the file version, then check the Startup folder or autostart configuration to see which runtime the machine launches at boot.

Keep reading

  • How-to

    How to Migrate a ProTool HMI Project to a New Touch Panel

    A discontinued ProTool-era panel is replaceable without a rewrite only when the editable project file exists: migrate it under WinCC flexible 2008 with Service Pack 2, Advanced edition for ProTool Pro projects, then review every conversion message and adapt tags and screens for the chosen target. Without the .ptp file, budget the job as a rebuild.

    HMI and touchscreens

  • How-to

    Where to Set HMI Project Version and Author in Vijeo Designer

    Vijeo Designer has no equivalent of Machine Expert's Project Information option, and opening both projects together transfers nothing: the HMI shows PLC metadata only if the PLC writes it into variables. Put the HMI release designation and author on a dedicated information screen as fixed text, archive the source under the same number, and read the screen back on the panel after every download.

    HMI and touchscreens

  • Troubleshooting

    Fix a Vijeo Designer project version mismatch by updating the build

    The project version mismatch error means the project was saved by a newer Vijeo Designer build than the 6.3.0.103 you have installed, so copying the file locally cannot fix it. Update through Schneider Electric Software Update to a later 6.3-series build such as the reported 6.3.1.32, confirm the version inside the running application, then retest.

    HMI and touchscreens