Short answer
You save the running application at the terminal, not in the software. Power up while holding the bottom-right touchscreen corner until the white dot appears, then choose Save to Disk from the Memory Card menu; Restore from Card loads it back. PanelBuilder32 can write the card through a PCMCIA reader instead, and a CompactFlash card in a Type II PCMCIA adapter is the working medium.
On this page
You do this at the terminal itself, not in the software. Cycle power while holding the bottom-right corner of the touchscreen; a small white dot shows where the terminal wants the touch, and the configuration menu opens. Pick Memory Card, then Save to Disk, and the running application lands on the card in the slot. Restore from Card loads it back. The medium is a plain CompactFlash card in a Type II PCMCIA adapter — no proprietary card involved. Below: the save, the restore, the PanelBuilder32 alternative, and how to make one card carry the PLC program too.
What the card slot takes #
The terminal takes one PCMCIA Type II card, and the practical medium is ordinary:
- A standard CompactFlash card in a Type II PCMCIA adapter works in the slot; no proprietary memory card is needed.
- 8 to 128 MB covers what these terminals store. Larger cards are wasted space.
- Insert the card connector-first until it is fully seated, then apply power — put cards into terminals that are off, not into running ones.
The power cycle is the one safety consideration: do it at a planned stop, because this screen is the operator's window into a running machine, and never pull the card or cut power while a save or restore is writing.
Enter configuration mode #
Two ways in, and the application decides which is faster.
- Look for the configuration-mode button the application builder may have drawn into the screens. In the case behind this procedure there was one, and from runtime it takes you straight to the menu; the general procedure is covered in entering configuration mode on a touch HMI.
- No button? Cycle power and press and hold the bottom-right corner of the touchscreen during power-up. A small white dot appears where the terminal is reading touch — keep your finger on the dot and hold until the configuration menu opens.
- If no dot appears at that corner, stop cycling power and use the PanelBuilder32 route below; it needs no touch input at all.
The corner-and-dot entry belongs to this standard PanelView generation. Later PanelView Plus 6 terminals dropped it, and how PanelView Plus 6 terminals enter configuration mode without the corner dot describes what replaces it.
Save the running program to the card #
- Insert the card fully seated and power the terminal up.
- Enter configuration mode.
- Select Memory Card, then Save to Disk.
- Confirm the prompt and wait for the completion message. That message is the only signal the write is finished; card and power stay put until it appears.
- Verify the save: Memory Card Listing shows the stored application with its date and size.
Make this save part of every program change. A current card turns a dead panel into a card swap, and it is your exit from the situation in recovering an HMI program when the source file is lost — once the source is gone, the card is the program.
Restore a program from the card #
- Insert the card, power up, enter configuration mode.
- Open Memory Card Listing first. One card can hold several programs; confirm the one you expect is present before touching anything else.
- Select Restore from Card and confirm.
- Wait for the completion message; the terminal comes up in the restored application.
Restore overwrites whatever application is running, and the terminal keeps no second copy. In a spares cabinet holding several cards, match the machine tag on the card to the machine in front of you before you confirm.
The PanelBuilder32 route to the same card #
PanelBuilder32 writes the card too. Put it in a PCMCIA reader on the engineering workstation and send the application transfer to that card from the software's transfer options. The result restores at the terminal exactly like a card written on the floor, and it is the path to use when the touchscreen is damaged, the corner entry will not take, or you are building a labeled spare before a failure instead of after one.
If the struggle is the serial upload itself rather than the card, uploading a PanelView 600 program when DF1 AutoConfigure fails covers the connection setup that path needs.
This procedure is for the standard PanelView terminals programmed with PanelBuilder32. The later PanelView Plus generation is programmed in FactoryTalk View Studio (Machine Edition) and takes its backups on USB or SD storage instead, with a startup file such as autorun.bat on the drive root restoring the backup automatically.
Carry the PLC program on the same card #
The card does not have to hold only the terminal's file. Copy the current controller program onto it with the PLC programming software, next to the PanelView application, and drop in a small text file with the machine tag and the save date. One card then carries the whole machine: a dead panel and a dead controller become a card restore and a program load.
Two limits keep that honest. Save to Disk writes only the PanelView's own application — the controller file is a passenger the terminal ignores. And loading that file back is done from the controller side with the controller's own tools; no PanelView menu touches it.
The working practice is to leave a card in every terminal, so the next failure is a restore instead of a reprogramming session.
Checking one machine's spare against an 8 MB card #
The inputs:
- Card: CompactFlash in a Type II PCMCIA adapter, 8 MB — the bottom of the 8 to 128 MB working range.
- PanelView application: 420 KB — an example of the size Memory Card Listing reports; read your own from the same menu.
- Controller program: 64 KB — a typical ladder file for this generation.
- Machine note: 1 KB of text.
The rule: everything the machine spare needs — application, controller program, note — must fit inside the card's capacity, and the listing hands you the file sizes to add up.
The arithmetic, with 1 MB = 1024 KB:
- Content: 420 KB + 64 KB + 1 KB = 485 KB.
- Card: 8 MB = 8 × 1024 KB = 8192 KB.
- Free space: 8192 KB − 485 KB = 7707 KB.
- Oversize factor: 8192 KB ÷ 485 KB ≈ 16.9.
The result: the complete machine spare occupies 485 KB of an 8192 KB card, about 6 percent, with roughly 17 times headroom.
The decision: with total content under 1 MB — where a PanelView application plus a ladder program of this generation lands — even the smallest card in the range is heavily oversize, so standardize on one card per terminal and spend your attention on labeling and on repeating the save after every change. Step up inside the range only if your listing shows the files going past 1 MB.
Questions asked
Can one card serve several identical terminals?
As the PanelView application source, yes — Restore from Card loads the same application into any matching terminal. What differs between supposedly identical machines is usually the controller program, so if you co-store it, keep one card per machine or relabel carefully. Restoring machine A's tuning and offsets into machine B is the classic cloning mistake.
Why does nothing happen when I hold the corner at power-up?
The touch has to land during power-up, not after the application loads, and the small white dot marks the exact spot the terminal reads — keep a finger on the dot until the menu appears. If the corner stays dead, the application may carry a configured configuration button; otherwise use the PanelBuilder32 card route, which needs no touch input at all.
Can I leave the card in the terminal permanently?
Yes, and you should. The terminal touches the card only when you run Save to Disk or Restore from Card, so an idle card just rides in the slot. Label it with the machine tag and the last save date, and repeat Save to Disk after every application change so the card keeps matching what actually runs.
Will Restore from Card wipe the program on the terminal?
It replaces it. The running application is overwritten and the terminal keeps no second copy, so what protects you is the card you made earlier plus the source on the engineering PC. That is the whole argument for saving before you need it: after a failed panel, the card is the only copy left in the building.
Do I need a bigger card for a bigger application?
Almost never. A PanelView application of this generation plus its controller program lands well under 1 MB, against a working range of 8 to 128 MB, so the smallest card is already many times oversize. Match capacity to that range rather than to ambition, and put the effort into labeling and into keeping the save current instead.