KTP700 Basic Runtime Startup Wait and the Start Center

HMI and touchscreens Published 5 min read

Short answer

The Start Center wait on a KTP700 Basic is set on the panel, not in the project. Open Settings, select System Control/Info in the System section, set Autostart to ON where the panel shows it, and set the Wait selector to OFF. Runtime then starts at power-up and the defined project start screen appears without anyone pressing Start.

On this page
  1. Two settings decide what appears at power-up
  2. Setting the Wait selector to OFF on the panel
  3. Worked example: a KTP700 Basic PN already delivered to the customer
  4. If the panel menus do not match
  5. Verifying the result at power-up
  6. Questions asked

The wait that holds a KTP700 Basic at the Start Center after power-up is a panel-side setting, not a project setting. Defining a screen as the start screen in your engineering project only selects the first screen shown once Runtime is already running; it cannot remove the manual press of Start. To make your project start screen appear on its own, change the setting at the panel: in the Start Center, open Settings, select System Control/Info in the System section, set the Autostart switch to ON where the panel shows one, and set the Wait selector to OFF. After that change the panel launches Runtime by itself at every power-up. The fix is made entirely on the device, so it also works when the machine is already at the customer and no engineering laptop is connected.

Two settings decide what appears at power-up #

The project and the panel each hold one startup setting, and they answer different questions:

  • Project start screen — defined in the engineering project; it selects the first project screen displayed after Runtime launches.
  • Runtime startup wait — held on the HMI device; it decides whether the Start Center starts Runtime automatically and, if so, after what delay.

The screen with the three buttons — Parameters, Start and Settings — is the device's own Start Center, not a project screen. Its Start button starts the project on the HMI device and its Settings button opens the Start Center's settings pages, as Siemens documents for these panels. While the panel sits there, the project is not running, so no start-screen definition can take effect. Deciding when an individual screen object becomes usable is a separate job, handled by the visibility settings covered in Enable object access on a KTP700 Basic Panel with Visibility.

Setting the Wait selector to OFF on the panel #

  1. Power the panel and let it stop at the Start Center with the three buttons.
  2. Touch Settings.
  3. In the System section, touch System Control/Info.
  4. If the page shows an Autostart switch, set it to ON. Siemens documents this switch together with the Wait selector in the Basic Panels 2nd Generation operating instructions.
  5. Set the Wait selector to OFF. With OFF selected, the device does not wait and starts Runtime immediately at power-up. If a delay was deliberately configured on this machine, set the time instead with the selection wheel under Wait; Runtime then starts after that delay.
  6. Close the settings pages and power-cycle the panel to confirm.

Worked example: a KTP700 Basic PN already delivered to the customer #

Inputs, and where each comes from: a KTP700 Basic PN that stops at a Start Center showing Parameters, Start and Settings (the reported case); a project in which a screen is already defined as the start screen (the reporter's own project); a panel side on which Runtime never starts by itself, so someone presses Start after every power-up (the reported symptom); and a machine already installed at the customer, so the change has to be made at the panel (the reported site condition).

Rule, in words: the Start Center launches the project by itself only when the device's autostart is on, and the Wait selector decides whether that launch is immediate (OFF) or happens after the set delay. The Start button is needed only when autostart is off.

The chain, written out:

  • Autostart ON and Wait OFF → Runtime launches at power-up → the first project screen shown is the defined start screen.
  • Autostart ON and Wait set to a time → Runtime launches after that delay, then the start screen appears.
  • Autostart OFF → the Start Center stays on screen until Start is pressed → the reported symptom.

Result: the two touches at the panel — Settings, then System Control/Info — plus the Autostart and Wait changes put the defined start screen on the panel at every power-up. No project edit, no download and no engineering workstation are involved.

Decision: set Autostart to ON and Wait to OFF whenever the machine should be operable the moment it is powered; keep the Wait at a set time only where that delay was put there on purpose, and leave autostart off only when the Start Center itself must be the first thing operators see. Have site personnel make the change and agree the power-cycle with whoever owns the machine, because Runtime that starts by itself puts the start screen — and every control on it — within reach the moment the panel is powered.

If the panel menus do not match #

Basic Panels of different generations, Comfort Panels, Multi Panels and PC-based Runtime each arrange these menus differently. If the Settings area has no System Control/Info entry or no Wait selector, stop and identify the panel family and generation from its Settings layout first; Comfort Panels, for example, keep the runtime startup time on a different settings page entirely, so the Basic Panel path does not transfer. Match the instruction to the page the panel actually shows rather than searching for a substitute menu.

Verifying the result at power-up #

Power the panel down and up again. Runtime should launch without anyone pressing Start, and the defined project start screen should be the first screen shown. If the Start Center still appears, recheck the Autostart switch and the Wait selection. If Runtime starts but the wrong project screen appears, the startup setting is fine — correct the start-screen definition in your project instead and download it again.

Note the limits of this test: a power cycle here only restarts the panel as configured. If a panel comes back without its project after every power cycle, that is a different fault with its own causes — see Why an HMI Loses Its Program After Every Power Cycle.

Questions asked

Is the automatic start setting named the same on other HMI panel families?

Different panel families name and place it differently. Unified Basic Panels have an Automatic runtime start entry that defines whether the project starts automatically and after what delay. Basic Panels 2nd Generation use the Autostart switch together with the Wait selector. Match the instruction to what your panel's Settings page actually shows before changing anything.

How is the runtime startup time changed on a Comfort Panel?

A Comfort Panel keeps this outside System Control/Info: the runtime startup time is edited in Transfer Settings, on the Directories tab. Because Basic, Comfort, Multi and PC-based Runtime panels arrange their menus differently, confirm which family the HMI belongs to before reusing the Basic Panel path.

Does the Wait selector affect the PLC or the machine controls?

No. The Wait selector only decides when the panel's Runtime software launches. It does not change PLC program behavior, communication settings or tag addresses; the panel simply connects to the controller once Runtime is running.

Keep reading

  • Troubleshooting

    Why the PDATA.FWX configuration file could not be loaded

    The message means the panel could not read the runtime configuration file its project generated, so it shut the application down. Save a backup, delete the generated PDATA file from the project, compile again, and prove the project starts clean on the PC runtime before redownloading. If the panel still fails, delete its stale copy from the flash storage folder the message names and download again.

    HMI and touchscreens

  • Troubleshooting

    Scaling encoder counts to inches on an HMI display

    A value like 9E-46 on a scaled encoder readout is a data-type symptom: the HMI tag reads integer counter memory as a 32-bit float. Set the tag to the integer type the counter writes, apply two-point scaling from 0 counts/0 inches to 2,540 counts/1 inch, set four decimal places on the object, and let one layer, HMI or PLC, own the conversion so the count is never scaled twice.

    HMI and touchscreens

  • How-to

    When popup calendar buttons are too small for touch panels

    The popup calendar's date-navigation buttons don't grow with the component, because a Swing panel and the buttons' maximum sizes hold them at their old rendered size; a propertyChange script that resizes the five buttons and their containing JPanel fixes it. Judge the fix in millimetres: rendered pixels × active display area ÷ resolution. On a 1280 × 800 panel with a 216 mm active area, 100-pixel buttons render at 16.9 mm and clear a 10 mm plant-floor target.

    HMI and touchscreens