Login methods on a Unified Comfort Panel by user management

HMI and touchscreens Published 6 min read

Short answer

A Unified Comfort Panel in TIA Portal V19 selects its login methods from two conditions: local user management or a central UMC domain, and direct panel operation or a web client. A web client always signs in with username and password only. The panel adds RFID cards, Unified Air biometrics and an alias system function with local users, and RFID cards with a central domain when PM-LOGON Unified is installed.

On this page
  1. The selection matrix
  2. Username and password, the only web client method
  3. RFID card login with local user management
  4. RFID with a central UMC domain
  5. Unified Air biometric login over Bluetooth
  6. Alias and parameter logins from the application
  7. The decision for each case
  8. Questions asked

A Unified Comfort Panel configured in TIA Portal V19 offers four sign-in paths, and two conditions decide which ones apply: where the users are administered, locally at the panel or in a central User Management Component (UMC) domain, and where the operator signs in, directly at the panel or through a web client. A web client always gets username and password only. Direct operation with local users adds RFID cards, Unified Air biometrics and an alias system function; direct operation with a central domain adds RFID cards when PM-LOGON Unified is installed. Fix those two conditions before you buy readers, phones or licenses, because no add-on opens the web client rows.

The selection matrix #

Authentication establishes the operator's identity; authorization decides what that identity may then do. Every method below delivers only an identity. The permission set of the signed-in account governs the rest, so a login that shows the right name but releases the wrong operations is an authorization fault, not a reader fault.

User management Operator interface Sign-in methods What the extra methods need
Local Direct panel operation Username and password, RFID card, Unified Air biometrics, alias login USB reader; Unified Air app on a mobile device with Bluetooth through the reader; system function in the application
Local Web client Username and password A configured local account
Central UMC domain Direct panel operation Username and password, RFID card PM-LOGON Unified and a supported reader
Central UMC domain Web client Username and password A permanently available UMC domain

Two rules sit under the matrix. The vendor documents RFID login as working only with a reader directly connected to the HMI device, and nothing plugged into the panel creates a reader path for a remote browser, so the web client rows stay closed to every panel-side method.

Username and password, the only web client method #

Username and password is the one method present in all four rows, so commission it first. With local user management the account is created in the panel's user management configuration; with a central domain it is provisioned in the UMC domain and the panel is pointed at that domain. A web client is a browser session against the panel runtime and forms its own login context; the runtime side of that access is covered in what publishing HMI runtime screens to web clients requires.

Prove the baseline with an account of known permissions: sign in at the panel, confirm the displayed identity, run one allowed and one blocked operation, then repeat the same test in the browser, because a working panel session proves nothing about the browser session. One line to keep straight: no sign-in method on the panel is a safety function; it decides who may operate, never whether the machine stops.

RFID card login with local user management #

Under local user management, three readers connected over USB are supported: SIMATIC RF1040R, SIMATIC RF1060R and SIMATIC RF1070R. Setup and card-to-user assignment happen inside the panel's user management: enable authentication by RFID card, open Edit User for the account, and hold the card on the connected reader when the pop-up asks for it. The operating documentation lists the panel's Control Panel as one place where the RFID login can be used, so an administrator can card into the panel settings without typing.

A detected reader and a valid account are separate requirements. The card is only a credential lookup: the presented card resolves to the account it is assigned to, and a card bound to the wrong account produces a clean login with the wrong rights. Test it as such: sign out, present the card, confirm the active user name, then run one allowed and one blocked operation.

RFID with a central UMC domain #

Central user management presumes a permanently available UMC domain, and the domain is licensed by the number of users it manages. Count every account the domain will hold, not the number of panels: for example 18 operators, 4 maintenance accounts and 1 administrator give 18 + 4 + 1 = 23 managed users, so the domain is licensed for 23 users. If the domain is unreachable the panel has nothing to authenticate against, so treat domain availability like any other control-network service.

At the panel, RFID card login then additionally requires PM-LOGON Unified. The readers are the same three USB models, or the TCP/IP-capable RFID readers that PM-LOGON supports on Ethernet. This is where the Unified panels differ from the earlier Comfort Panels, whose equivalent package is PM-LOGON Basic; the card setup for those units is covered in RFID card login on a Comfort Panel with PM-LOGON Basic. PM-LOGON Unified changes nothing for the web client: that row stays username and password.

Unified Air biometric login over Bluetooth #

Unified Air runs biometric authentication in the SIMATIC Unified Air app on a mobile device that connects to the panel over Bluetooth, using Bluetooth Low Energy. The panel has no Bluetooth interface of its own: the RF1040R or the RF1070R provides it, which is why the RF1060R, an RFID-only reader, cannot serve this method. For Unified Air 3.0 the vendor documentation also has you connect a supported USB Bluetooth dongle to the panel as its Bluetooth interface.

Commission the whole chain, because success on the phone proves nothing until the panel shows the intended user: configure biometric authentication on the mobile device, connect the app to the panel through the reader or dongle, sign in, and confirm the active local account and its permissions. Taking biometric identity beyond the panel into plant access is a separate design, covered in integrating biometric readers with HMIs for security gate control.

Alias and parameter logins from the application #

The system function SetzeLokalenBenutzer signs in a local user by an alias, a name assigned to that user in addition to the account name. The alias reaches the function through a variable or a screen object, and the control program can write that variable, so a keyswitch or ID keyswitch wired to the PLC becomes the login trigger. The full path, including the PLC side, is worked through in PLC triggered user login by alias on a unified panel.

From TIA Portal V20 a second system function, WechseleBenutzer, signs in with username and password passed as function parameters. The username may be a constant string, an HMI variable or a screen input field; the password only an HMI variable or a screen input field, so a constant password is not a documented path. After execution the function deletes the password from the variable or field automatically, so the credential does not stay in the runtime. Feed that password from a variable nothing else logs.

The decision for each case #

  • Local users, operators at the panel: password login as the baseline, RFID when shift changes must be fast, Unified Air only where phones are permitted in the cell, alias login where a keyswitch should select the user.
  • Local users, browser access: username and password only. Do not buy a reader for remote users; it cannot reach their session.
  • Central domain, operators at the panel: username and password; add PM-LOGON Unified and a reader only when card login is a written requirement. Size the domain license by managed accounts, 23 in the example above.
  • Central domain, browser access: username and password only; PM-LOGON Unified adds nothing to this row.
  • One reader for two methods: card login alone works with any of the three USB readers; card login plus Unified Air needs the RF1040R or the RF1070R, since only those carry the Bluetooth interface.
  • Commissioning order: password login and its permissions first, on the panel and separately in the browser; then the reader, then Bluetooth, then application-triggered login.

Questions asked

Can Unified Air grant access that expires on its own?

The app's store listing describes temporary, time-limited access, so a visitor or maintenance credential can end by itself instead of waiting for an administrator to delete it. Set the limit in the app, then verify on the panel that the session really ends when the limit passes; the panel's user management still decides what the account may do while it lasts.

Which Ethernet RFID readers work with PM-LOGON Unified?

With a central UMC domain, PM-LOGON Unified accepts the three USB readers and alternatively TCP/IP-capable readers operated on Ethernet. The vendor maintains the supported Ethernet reader list in its PM-LOGON FAQ. Check a candidate reader against that list before ordering, because a reader that is not on it will not authenticate against the domain.

Is an alias login as secure as a password login?

No secret is involved: the alias only names the account, so anyone who can drive the alias variable, for example through the keyswitch wired into the PLC, selects that user. Use alias login for convenience on trusted hardware, restrict who can write the alias variable in the PLC program, and keep password or card login for privileged accounts.

What happens when an RFID card is lost?

The card is only a credential that resolves to an account, so remove the card assignment in the panel's user management and the account keeps working with its password. Because the card carries the account's full permission set, assign cards only to accounts whose rights you would hand to the card holder, and treat a lost card like a shared password.

Why is the password deleted after a parameter login with WechseleBenutzer?

The system function removes the password from the HMI variable or input field immediately after execution so the credential does not linger in the runtime, where a trace, a recipe or a screen export could expose it. Feed the password from a variable that nothing else logs, and keep the input field masked on screen.

Keep reading

  • Troubleshooting

    Why an Edge app does not autostart on a Unified Comfort Panel

    An Industrial Edge app on a Unified Comfort Panel starts on its own only if its containers carry a restart policy such as unless-stopped. Installation alone does not set one, and an HMI Runtime button can open an app's interface or send it a command, but it cannot start a stopped container.

    HMI and touchscreens

  • How-to

    Printing images and PDFs from a Unified Comfort Panel

    A Unified Comfort Panel has no built-in function that prints the runtime screen or a document to a printer. Print through the panel's LibreOffice install: open the PDF directly, or wrap a JPG in a one-line HTML file, then submit with -p or --pt and automate via runLibreoffice.sh. Use the CUPS lp command only after the printer queue prints a known-good file on the panel.

    HMI and touchscreens

  • Explainer

    RFID card login on a Comfort Panel with PM-LOGON Basic

    PM-LOGON Basic, supplied inside the free SIMATIC HMI Option+ package, adds RFID card login to a SIMATIC Comfort Panel through a SIMATIC RF1000 reader on the USB interface, and user administration stays local on the panel. Binding a card UID to a Windows user belongs to full PM-LOGON with SIMATIC LOGON, which is a different product and a different account architecture.

    HMI and touchscreens