Migrating a Comfort panel project to WinCC Unified V16
Short answer
TIA Portal V16 cannot convert a Comfort panel project to WinCC Unified: Change device/version lists no Unified target and nothing copies between the two project types. Run the Comfort engineering and Unified engineering in separate virtual machines, because WinCC Professional and Unified do not coexist in V16 to V18, then rebuild tags with address multiplexing, rewrite the Visual Basic scripts in JavaScript, recompose screens with screen windows, and accept one pilot screen before the full set.

On this page
- What V16 converts and what it refuses
- Build two engineering environments first
- Recreate the tags, and rebuild the multiplexed ones
- Rewrite each Visual Basic script as JavaScript
- Recompose screens with screen windows, not templates
- Worked example: rebuilding the multiplexed DBW0 tag with an index tag
- Check the configured runtime version before download
- Accept one pilot screen, then scale
- The decision for your project
- Questions asked
There is no conversion to run. In TIA Portal V16, "Change device/version" offers no Unified panel as a target for a Comfort panel, and no tag table, single tag, screen or screen object — not even a text object — can be dragged or copied from a Comfort project into a Unified project. The migration is a controlled rebuild, and it starts with two separate engineering environments, because WinCC Professional and WinCC Unified are not installable side by side in V16 through V18. Rebuild in this order: separate virtual machines, tags with address multiplexing for the indexed addresses, Visual Basic scripts rewritten as JavaScript, screens recomposed from screen windows, then one pilot screen accepted before the full set.
What V16 converts and what it refuses #
The documented device-change path is short: double-click "Devices & Networks" in the project tree, select the HMI device in the device view, then choose "Change device/version". On a Comfort panel in a V16 project the selection stops at the established panels; no Unified device appears, so the swap cannot even begin. The clipboard routes are closed as well: tag tables, individual tags, whole screens and individual objects all refuse the move from a Comfort project to a Unified project.
That matches the vendor's position for V16: Unified engineering was delivered alongside the established WinCC types, with no full project migration. The reference document is the "Guide for Migrating to WinCC Unified HMI Devices", Siemens support entry 109768002; it has been revised for later releases, so read the revision that matches your engineering version. Budget engineering time, not conversion time — the working method is the one described for rebuilding a lost HMI project from PLC tags and logic, with the old project open as the living reference.
Build two engineering environments first #
The installer states the conflict plainly: WinCC Professional cannot be installed together with WinCC Unified PC. Siemens support entry 109822246 documents the same incompatibility for V16, V17 and V18. No single workstation edits both project types, so plan two virtual machines before any engineering:
- Keep the source machine: TIA Portal V16 with the WinCC engineering that owns the Comfort project. Record the project version, panel type, firmware level and licenses in the migration register.
- Build the destination machine: TIA Portal V16 with Unified engineering and no WinCC Professional.
- Open the Comfort project on the source machine and the new Unified project on the destination, and work with both visible, because nothing transfers between them electronically.
- Confirm each environment opens its own project cleanly before rebuilding starts, and keep the source machine for as long as Comfort panels remain in service.
The split also rules out any data handover between Professional and Unified on one system — the migration register of tags, scripts, screens and alarms lives outside both tools until the destination stands alone.
Recreate the tags, and rebuild the multiplexed ones #
Recreate direct controller tags with four properties matched to the source: data type, controller connection, access direction and scaling or display format. A matching name proves nothing; the tag is equivalent only when all four agree.
The indirect addresses need a new form. The legacy multiplex pattern %DB[MUXDB].DBW0 — one tag that reads word 0 of whichever data block the MUXDB index tag names — is rejected in Unified with a message telling you to change the addressing to multiplex. The mechanism exists; the syntax does not. Unified address multiplexing lets a single tag reach a large number of PLC memory locations, with an index tag supplying the variable part at runtime. Each legacy multiplex tag therefore becomes a process tag plus an index tag, typed and ranged to cover every data block the application selects. The worked example below numbers it.
Keep three lists separate in the register: direct controller tags, multiplexed selections, and internal HMI values. Every operator display and command then has exactly one identified data source.
Rewrite each Visual Basic script as JavaScript #
Unified scripts are JavaScript; the Comfort scripts are Visual Basic. This is not a syntax swap, because the runtime object model — the objects, properties, events and services a script can reach — is different. Rebuild each script from its function, in this order:
- The triggering event that runs it.
- The input values it reads, including HMI array elements.
- The writes it makes to the controller.
- The screen changes it causes.
- Its failure behavior — what the operator sees when a write is rejected.
Two destination facts save rework. Unified scripts read HMI arrays element by element, which is why a WinCC Unified V19 script cannot read an HMI array at once; and a screen change driven by the controller is a tag function rather than script work, as shown for changing the HMI screen from the PLC in WinCC Unified.
Recompose screens with screen windows, not templates #
Unified has no screen templates. A repeated area such as a header is built as its own screen and placed where it is needed through screen windows; that is why screen windows replace template screens. Button styling, fonts and window appearance differ from Comfort, so visual parity is its own acceptance item — decide before rebuilding whether the old look is a requirement or a habit.
Simulation is browser-based: start it from the engineering and open a browser at localhost to see the application. Where a target line supports a graphics import, importing legacy HMI screens when migrating to a new panel shortens this stage; V16 Unified provides no such import, so screens are rebuilt by hand.
Worked example: rebuilding the multiplexed DBW0 tag with an index tag #
Inputs:
- Legacy address from the source project:
%DB[MUXDB].DBW0, whereMUXDBis an index tag carrying a data block number. - Data width from S7 addressing: DBW is a word, 16 bits.
- In S7 addressing the data block number is itself a 16-bit field.
- Destination mechanism: Unified address multiplexing with an index tag.
Rule: create one Int process tag whose address is word 0 of a data block, activate multiplexing, and bind MUXDB, recreated as an index tag, as the index. Type the index tag so it can hold every block number the application ever selects.
Arithmetic:
- Word width: 16 bits ÷ 8 bits per byte = 2 bytes, so the tag occupies byte offsets 0 and 1 of the selected block — the same slot in every candidate block.
- Signed-word ceiling: 2^15 = 32768, so the largest positive Int is 32768 − 1 = 32767.
- Block-number ceiling: 2^16 − 1 = 65535.
- Reach beyond Int: 65535 − 32767 = 32768 block numbers an Int index cannot represent.
Result: one multiplexed Int tag plus one index tag replaces the legacy pattern, reading or writing word 0 of the block the index names.
Decision: if the selection never rises above 32767, an Int index tag is enough; if any selectable block number runs higher, type the index as an unsigned word or a DInt. A multiplexed write follows the index without judging intent — an index naming an existing but unintended block writes there — so validate the index in the controller and prove writes on an isolated bench with test tags before operators get the button.
Check the configured runtime version before download #
Unified runtime compatibility runs backward: a runtime V17 or higher runs projects configured for versions back to V16. A panel delivered with a later runtime therefore runs your V16-configured project unchanged; do not raise the configured version just to match the panel. If a panel's runtime is older than the configured version, the project will not run on it — update the panel or change the configured version through the same "Change device/version" command. The configured device version and the panel's OS image are different things; the difference between device version and panel OS image on Unified Comfort panels is worth settling before the first download.
Accept one pilot screen, then scale #
Pick the screen with the most dependencies: navigation, a process value, an operator command, an alarm indication and one script-driven behavior. On an isolated bench with verified test tags, prove five things: the pilot opens from navigation, the value tracks a known controller value, the command writes to the intended tag, the alarm shows and clears, and the multiplexed tag follows the index. Every function on the pilot must pass before the remaining screens are rebuilt to the same pattern — a redesign found after the fleet is rebuilt multiplies across the fleet. The discipline is the standard one for platform migrations: IndraLogic migration to ctrlX is run the same way, as a controlled rebuild with a pilot, not as a conversion.
The decision for your project #
- The application runs on Comfort today and no project requirement demands Unified: keep it there. Maintain it in the established WinCC engineering, and use the supported migrations inside that generation when hardware changes — migrating a WinCC PC Runtime project to a Comfort panel is one such direction.
- The target is a Unified device, or this is a new application: rebuild, following the steps above — two virtual machines, tags with index multiplexing, JavaScript in place of Visual Basic, screen windows in place of templates, one accepted pilot screen.
- A mixed fleet of Comfort and Unified panels: run both engineering environments for as long as both panel types are in service, and put every new screen in the environment its panel needs.
Questions asked
Can WinCC Advanced and WinCC Unified engineering share one V16 installation?
Yes. The documented parallel-installation conflict is between WinCC Professional and WinCC Unified, for V16 through V18. V16 delivered Unified engineering alongside the established WinCC types, so a Comfort project engineered with WinCC Advanced can stay on one system; only the Professional combination forces a second virtual machine.
Why does the Unified simulation open in a web browser?
The Unified runtime is web-based. It appears as a fixed-size application rather than a freely resizable web page, so lay screens out for the panel's fixed resolution and treat browser access as a display path, not as proof that a Comfort screen will render identically.
What if the Unified panel's runtime is older than my configured version?
Compatibility runs backward only: a runtime V17 or higher runs projects configured back to V16, but an older runtime will not open a project configured for a newer version. Either update the panel to the required runtime image or lower the configured runtime version in the engineering to match the panel before the first download.
Is there a vendor tool that transfers tags or alarm texts into Unified?
A data-transfer tool for tags and alarm texts was announced during the initial V16 period, but an announcement is not an installed capability. Check the current revision of the vendor's migration guide, support entry 109768002, for what your release actually ships, and test the tool on a copy of the project before it enters the migration plan.