How-to
OP177B to Comfort panel migration path in TIA Portal
Short answer
You cannot retarget an OP177B inside WinCC flexible: Comfort panels do not exist in its device catalogue. Migrate the WinCC flexible 2008 project into TIA Portal first, then use Change Device/Version to retarget it to a TP700 Comfort, or to a KP700 Comfort if the machine needs physical keys.

On this page
- Why the device change does not work in WinCC flexible
- What to have ready before the migration
- Migrating the project into TIA Portal
- Migrating a WinCC flexible 2008 OP177B project to a TP700 Comfort
- Choosing between TP700 Comfort, KP700 Comfort and KTP700
- Checking the migrated project before it goes on the machine
- Questions asked
You cannot convert an OP177B project to a Comfort panel by changing the device type inside WinCC flexible, because WinCC flexible's device catalogue predates the Comfort family and has no retarget function for it. The supported path has two stages: migrate the WinCC flexible 2008 project into TIA Portal, then use Change Device/Version in TIA Portal to retarget it to the replacement panel, such as a TP700 Comfort. That also answers the panel question: retarget to the TP700 Comfort for a touch-only machine, to the KP700 Comfort if operation depends on physical keys, and only to a lower-cost Basic panel after you have verified the project uses no Comfort-only functions.
Why the device change does not work in WinCC flexible #
The OP177B is configured in WinCC flexible, and WinCC flexible only offers devices from its own generation. A TP700 Comfort, KP700 Comfort or KTP700 Basic PN simply does not appear in that catalogue, so there is no setting to click. If you open an old project in a newer tool and the device entry is rejected, that is the same underlying cause described in the article on why a WinCC flexible Runtime device type is not valid for this version (article:why-a-wincc-flexible-runtime-device-type-is-not-valid-for-this-version): the project must be carried forward by migration, not edited in place.
What to have ready before the migration #
Before you start, gather three things:
- The editable WinCC flexible 2008 source project. A runtime backup taken with a transfer tool is not an editable project; the article on why a ProSave backup cannot migrate a Panel PC ProTool project (article:why-a-prosave-backup-cannot-migrate-a-panel-pc-protool-project) explains the backup-versus-source distinction that applies here too.
- A TIA Portal installation that includes WinCC Comfort, because Comfort panels are engineered with WinCC Comfort. The general procedure is the same one covered in how to migrate a WinCC flexible project to TIA Portal (article:how-to-migrate-a-wincc-flexible-project-to-tia-portal).
- The original program and connection data for the controller, so you can verify the HMI connection after the retarget.
The vendor's WinCC Migration Guide documents the OP 77B and OP 177B among the WinCC flexible 2008 project sources that migrate to WinCC in TIA Portal, so the OP177B project you have is a supported starting point. Keep an untouched copy of the source project; migration creates a new TIA Portal project and leaves the original file as your archive.
Migrating the project into TIA Portal #
Work through the migration in this order:
- Open TIA Portal and start the migration command, selecting the WinCC flexible 2008 project file as the source.
- Let TIA Portal convert the project. It builds a new project containing the screens, tags, alarms and connections from the OP177B configuration.
- Read the migration log. Every reported entry is a place where the converter changed or dropped something; resolve them now, before any device change.
- Compile the migrated project and correct any remaining errors. A clean compile is your baseline before retargeting.
Do not proceed to the device change until the project compiles. Retargeting a project that already carries unresolved migration messages makes the resulting fault list impossible to attribute.
Migrating a WinCC flexible 2008 OP177B project to a TP700 Comfort #
This worked case uses the inputs from the migration at hand: a WinCC flexible 2008 project configured for the OP177B, TIA Portal with WinCC Comfort as the engineering software, and the TP700 Comfort as the target, which moves the operator interface from the 6-inch OP177B display the project was built around to a 7-inch touch display.
The rule in words: import first, retarget second. Migration brings the project into TIA Portal while it is still bound to the OP177B device entry; Change Device/Version then replaces that device entry, and TIA Portal automatically selects the latest version of the chosen device.
The steps and the result:
- With the migrated project open, double-click Devices & Networks in the project tree.
- Select the HMI device entry, which still shows the OP177B, in the device view.
- Select Change Device/Version from the device shortcut menu and choose the TP700 Comfort.
The result is a project whose device entry is now the TP700 Comfort, with the migrated screens, tags and alarms carried across. Every element that has no equivalent on the target is listed in the output window, and that list is your rework sheet: resize screens for the 7-inch display, reconnect the HMI connection to the controller, and reassign any function that relied on OP177B-specific hardware.
The decision: if the operator interface was touch driven, the TP700 Comfort is the retarget; if the machine's operation depends on physical keys, choose the KP700 Comfort instead in step 3 and rework the same way; if cost pushes you toward a Basic panel, verify function coverage first as described below.
Choosing between TP700 Comfort, KP700 Comfort and KTP700 #
The three candidates differ in one decision input each:
| Panel | Operator interface | When it is the right retarget |
|---|---|---|
| TP700 Comfort | 7-inch touch only | The OP177B was operated by touch and you want the documented path with the smallest rework. |
| KP700 Comfort | Keys plus touch area | Machine operation relies on physical keys; the project survives the same Change Device/Version step. |
| KTP700 Basic PN | Keys plus touch, Basic panel class | Budget rules the choice and the project uses no Comfort-only functions. |
Commit to the TP700 Comfort as the default. Deviate to the KP700 Comfort only because the machine needs keys, and to a Basic panel only after you have checked scripting options, logging, alarm behaviour and tag counts against what the project actually uses. A Basic panel runs a reduced function set, and a migration that compiles can still lack a runtime feature the old panel had.
Checking the migrated project before it goes on the machine #
A clean compile does not prove functional equivalence. One safety note before anything else: complete this verification on an isolated bench with the controller or a simulated one, and put the machine in a safe state before the first download to the panel at the machine.
Work through the checks in this order: screen navigation, tag connections to the controller, alarm configuration and operator inputs, then the HMI-to-controller connection itself. Where the project logs tags, verify the logging behaviour on the new panel against the bench test, as covered in verifying tag logging on KTP700 and TP700 HMIs. Only when the bench run matches the old panel's behaviour on navigation, alarms and operator inputs is the replacement ready for the machine cut-out.
The decision for each case: touch-only machine, migrate then Change Device/Version to the TP700 Comfort; keys required, same path to the KP700 Comfort; tight budget, test the project against a KTP700 Basic PN's function set and fall back to the TP700 Comfort the moment a Comfort-only function appears in the migration log.
Questions asked
Does the same migration path work for an OP 77B?
Yes. The vendor's WinCC Migration Guide lists the OP 77B alongside the OP177B among the WinCC flexible 2008 project sources that migrate to WinCC in TIA Portal, so the same two-stage path applies: migrate the WinCC flexible 2008 project into TIA Portal first, then retarget with Change Device/Version. The rework afterwards still depends on the target panel's key layout and display size.
Do I need WinCC Comfort to retarget the project to a TP700 Comfort?
WinCC Comfort inside TIA Portal is the engineering package used for Comfort panels, and the documented Change Device/Version workflow covers Basic Panels, Panels, Comfort Panels, RT Advanced and RT Professional. Install a TIA Portal version that includes WinCC Comfort before starting the migration, because the OP177B project cannot be retargeted from WinCC flexible itself.
What is the difference between a KP700 Comfort and a TP700 Comfort?
The prefix describes the operator interface: KP panels combine a display with physical keys and a smaller touch area, while TP panels are touchscreen only with a larger display in the same chassis class. Both accept a migrated project through Change Device/Version. Choose the KP700 Comfort when machine operation depends on physical keys, and the TP700 Comfort when the operator interface was already touch driven.
Will every screen and alarm survive the migration unchanged?
Assume review is required. A completed migration proves the project converted, not that it is functionally identical. Compile the migrated project, read the migration log entry by entry, then check screen navigation, tags, alarm configuration, operator inputs and the controller connection on a bench before downloading to the panel. The TP700 Comfort has a 7-inch display versus the OP177B, so screen layouts may need adjustment rather than repair.
Can a KTP700 Basic PN replace an OP177B?
It can as hardware, and Change Device/Version covers Basic Panels as well as Comfort Panels, but a Basic panel runs WinCC Basic with a reduced function set compared with Comfort. Before ordering on cost grounds, confirm that the project actually uses only functions the Basic panel supports: script options, logging, alarm behaviour and tag counts are the usual gaps. If any are missing, the TP700 Comfort is the safe retarget.