Which software configures a KP1200 Comfort panel
Short answer
A SIMATIC HMI KP1200 Comfort is configured with WinCC Comfort inside TIA Portal, from V11 onward; WinCC flexible 2008 SP3 has no device support for it, so nothing can be created or transferred from flexible. Pick the WinCC Comfort edition or higher, align the project's device version with the panel image, and transfer over the panel's PROFINET interface.
On this page
- The nameplate names the engineering tool
- Why WinCC flexible 2008 SP3 is a dead end
- Which WinCC edition inside TIA Portal is enough
- Align the release, the device version and the panel image
- Worked example: will the project fit the user memory
- Two packages in one plant
- The decision for each case
- Questions asked
You configure a SIMATIC HMI KP1200 Comfort with WinCC Comfort inside TIA Portal, and with nothing else. The panel is configurable as of WinCC Comfort V11, so every TIA Portal release from V11 on can hold it, while WinCC flexible 2008 SP3 has no device support for it at all: no target to select, no compile, no transfer. If your engineering PC runs only WinCC flexible, the fix is not a cable, driver or service pack - it is TIA Portal with at least the WinCC Comfort edition, plus a project whose device version matches the image on the panel. What follows shows why the flexible route is closed, which WinCC edition is enough, and the decision for each starting point.
The nameplate names the engineering tool #
Read the product designation before you touch software. The KP1200 Comfort is a Comfort Panel with key operation: a 12-inch widescreen TFT display with 16 million colors, a PROFINET interface and an MPI/PROFIBUS DP interface, 12 MB of user memory, and Windows CE 6.0 under its runtime. The same designation states the engineering requirement outright - configurable from WinCC Comfort V11.
That clause is the compatibility decision in compressed form. The Comfort generation and the WinCC Comfort package arrived together, and the panels' screens, keys, connection setup and runtime image exist only in the TIA Portal device catalog. Comfort is not a higher trim of WinCC flexible, and an older panel with a similar diagonal and a similar name shares none of its engineering path.
If the nameplate shows a different model, stop here: this article answers only for the KP1200 Comfort, and a project configured for a look-alike panel proves nothing about the device on your bench.
Why WinCC flexible 2008 SP3 is a dead end #
An engineering package configures only the devices in its device catalog. Each entry carries device-specific support: the screen objects the panel understands, its communication configuration, and the runtime components the transfer writes onto it. WinCC flexible 2008 SP3 comes from the flexible generation, which predates the Comfort Panels; its catalog ends with the devices of its own era. With no KP1200 Comfort entry there is no device to add and nothing to compile, and the flexible transfer tool holds no runtime image it could write to that panel.
No cable, driver update or reinstall changes this, because the missing piece is device support inside the package, not a connection. It arrives only with the tool generation written for the panel - here TIA Portal from V11.
Keep one distinction clear: if WinCC flexible 2008 SP3 refuses one of your older projects with a version conflict, that is a separate fault with its own repair, described in this WinCC flexible 2008 SP3 project version incompatibility fix. Resolving it opens no path to the KP1200 Comfort.
Which WinCC edition inside TIA Portal is enough #
TIA Portal is the engineering frame; the WinCC edition licensed inside it decides which panels you can configure. The editions step up as Basic, Comfort, Advanced and Professional.
| WinCC edition | Configures the KP1200 Comfort? | Why |
|---|---|---|
| Basic | No | Covers the Basic Panels only |
| Comfort | Yes | The minimum edition, Comfort Panels from V11 |
| Advanced | Yes | Includes the Comfort engineering scope |
| Professional | Yes | Includes the scopes below it |
Two practical readings. If your catalog shows only Basic panels, the license is the reason, the same behavior covered in why TIA Portal V14 shows only Basic panels under WinCC Basic. And the minimum is WinCC Comfort: an existing Advanced or Professional license already covers this panel. The licensing list names Basic, WinCC Comfort, WinCC Comfort Combo, WinCC Advanced and WinCC Advanced Combo; the Combo variants bundle a STEP 7 license for the PLC side, which suits the engineer who configures controller and panel together.
Align the release, the device version and the panel image #
Three separate things must agree before a transfer works.
The engineering release: anything from V11 on configures the panel, so install a current release with its newest service pack rather than a first build - Comfort Panel fixes land in service packs, and a documented case is the WinCC f(x) trend view on a TP1200 Comfort losing historical data when acquisition paused, tied to timestamp handling around TIA Portal V11 SP2.
The device package: TIA Portal V21 brings no new device versions for Comfort and Basic Panels and delivers them as separate packages. On a V21 engineering PC, download the Comfort Panels package from SIOS, the Siemens Industry Online Support portal, or the KP1200 Comfort will not appear in the catalog even with the right license.
The device version versus the panel image: the project targets a specific device version, and the panel runs the matching image. When they disagree, the transfer refuses or demands a panel update; the procedure for matching an HMI panel image to its TIA Portal project version applies here unchanged.
Decision: set the project to the device version that matches the installed image, or update the panel image with the documented Siemens update files - and back up the running application before any image update.
Worked example: will the project fit the user memory #
The user memory is the hard ceiling for the compiled runtime project, so check it before every transfer, and especially after a migration, because converted flexible projects often grow. Worked example with illustrative numbers: after compiling, TIA Portal reports a runtime project of 9 MB. Headroom: 12 MB - 9 MB = 3 MB. As a fraction: 3 MB / 12 MB = 0.25, so 25 percent of the memory stays free for later screens, recipes and scripts.
The decision from those inputs: at 9 MB you transfer. If a later compile reports 13 MB, the project is over the ceiling by 13 MB - 12 MB = 1 MB, the engineering system flags it, and you cut screens or archives - or move to a panel with more memory.
Two packages in one plant #
Plants that grew up on WinCC flexible usually keep it for the panels it supports and add TIA Portal for the Comfort generation. That works with one warning: the two packages clash on a single engineering PC, and installing WinCC flexible breaks TIA Portal V13. Decision: give flexible its own engineering PC, or apply that article's fix before sharing one machine.
If the KP1200 Comfort replaces an older panel and you want its screens and tags, migrate instead of redrawing: how to migrate a WinCC flexible project to TIA Portal converts the content into a TIA Portal project, after which you change the target device to the KP1200 Comfort and review every conversion message. Work from a copy of the flexible source project - migration is one-way, and a backup file stored on the old panel is a restore image, not an editable project.
The decision for each case #
- Only WinCC flexible 2008 SP3 installed: it cannot configure this panel, and no update will make it. Install TIA Portal with at least the WinCC Comfort edition.
- TIA Portal with WinCC Basic: the Comfort Panels are absent from the catalog by license. Move up to WinCC Comfort; Advanced or Professional also qualify.
- Fresh TIA Portal V21 with the panel missing: download the Comfort Panels device package from SIOS before blaming the license.
- Transfer refused over a version mismatch: align the project's device version with the installed panel image, or run the documented image update - back up the application first.
- Screens to carry over from flexible: migrate a copy, retarget to the KP1200 Comfort, review the conversion messages, then compile and transfer.
- Both panel generations on site: keep flexible on a separate engineering PC for the old panels; the packages clash on one machine.
One operating rule covers every case: a transfer interrupts the runtime, so put the panel on the bench or in a planned window - the machine has no operator screen while a transfer runs.
Questions asked
How do I transfer the project to the KP1200 Comfort once it compiles?
Over the panel's PROFINET interface. Put the panel and the engineering PC in one subnet first, for example 192.168.1.10 on the panel and 192.168.1.50 on the PC, then enable transfer on the panel and load from TIA Portal. The MPI/PROFIBUS DP interface is normally reserved for the controller connection.
Is the KP1200 Comfort part of the Unified Comfort Panel family?
No. Unified Comfort Panels are a later generation engineered with WinCC Unified inside newer TIA Portal releases, and their projects do not open with WinCC Comfort. The KP1200 Comfort stays on the WinCC Comfort path described here. Do not pick a Unified device in the catalog because the names look similar; the runtime and the engineering scope are different.
Does Windows CE 6.0 mean WinCC flexible Runtime could run on the panel?
No. The operating system does not choose the engineering tool. The KP1200 Comfort runs the WinCC Comfort runtime that belongs to its TIA Portal project, with Windows CE 6.0 underneath; flexible-era panels also ran a Windows CE variant for the flexible runtime. A shared operating system across generations proves nothing about project compatibility; the device catalog entry decides.
Can one TIA Portal project hold the KP1200 Comfort and older panels together?
Yes, as long as each older panel has its own entry in the TIA Portal device catalog; HMI devices sit side by side in one project. Panels that exist only in the WinCC flexible catalog stay in flexible projects, so check each model against the TIA Portal catalog before you plan a single-project cleanup.