Troubleshooting

Why Basic Panel Simulation Crashes at Startup in TIA Portal V15

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

A crash that repeats on a fresh single-screen project is a fault in the installed Basic-panel simulator or WinCC runtime on the engineering PC, not in your screens. Reported TIA Portal V15 cases stopped crashing after the panel device version was changed to 14.0.0, which calls an older simulator already installed on the PC. Capture the Windows crash record before any reinstall.

On this page
  1. Confirm the fault is not your screens
  2. Capture the crash record first
  3. What reported fixes did not change
  4. The workaround: run the panel at device version 14.0.0
  5. Acceptance test before you call it fixed
  6. Questions asked

When a fresh, single-screen project still crashes the simulator at the same startup point, the fault is in the installed simulator or runtime on the engineering PC, not in your screens. In reported TIA Portal V15 cases, the Basic-panel simulation for KTP400 and KTP700 targets terminated at startup every time while Comfort-panel simulation on the same PC ran normally. The workaround that restored work: keep the panel's device version at 14.0.0 so the simulator calls an older, already installed simulator instead of the one that fails. Before you touch anything else, capture the Windows crash record, because it names the failing executable and decides whether anything you reinstall can even help.

Confirm the fault is not your screens #

Run this test before editing any production screen. It takes ten minutes and it moves the fault boundary from project content to the PC runtime:

  1. Create a new project with only the failing HMI target and one simple starting screen. No imported screens, no scripts, no libraries, no dual-monitor configuration.
  2. Compile the target and start the simulation.
  3. Watch whether the starting screen stays open or the process terminates at the same point as the production project.
  4. Restart the PC fully and repeat once, so a stranded runtime process cannot fake the result.

In the reported cases, even this minimal project crashed immediately, so screen navigation, scripts and project graphics were ruled out as the first diagnostic branch. Keep the same target family throughout: simulating an RT Professional target exercises a different runtime path than simulating a Basic panel, and a pass from one does not clear the other.

Capture the crash record first #

A file named StackHash_0a9e next to pdlrt.exe is a Windows crash-bucket label, not a component diagnosis. Open the Windows application log and read the two entries Microsoft documents for this situation: Event ID 1000 names the faulting application, faulting module and exception code, and Event ID 1001 is the Windows Error Reporting record for the same crash. Write down the faulting application, the faulting module, the exception code and the timestamp, and check that every attempt reports the same values. In the reported cases the faulting application was pdlrt.exe, the WinCC runtime process, at every startup.

That record decides your next move. If the module and exception code are identical on every attempt, the fault is repeatable inside one component and no amount of screen editing will change it. If you see a WinCC runtime crash on real Comfort hardware instead of in simulation, that is a different failure path, covered separately in the article on fixing HMIRTM.EXE runtime crashes on a Comfort panel.

What reported fixes did not change #

Before you spend a day on the same path, know what already failed in the reported cases:

  • Deleting the IM folder and running a rebuild compile: crash unchanged.
  • Repair install of the complete TIA Portal V15 installation: crash unchanged.
  • Full uninstall and reinstall of TIA Portal V15: crash unchanged.
  • Reinstalling the runtime software: crash unchanged.
  • Installing update 15.1.0.3: crash unchanged.

The IM-folder delete remains a legitimate test for stale generated data, and a successful compile followed by a stable launch would confirm it worked. But when compilation succeeds and the runtime still terminates at the same point, you are looking at installed components, not generated data. After one unchanged reinstall, stop: the crash record and the installed-component inventory are what a support channel needs, and another reinstall destroys nothing but time.

The workaround: run the panel at device version 14.0.0 #

This branch applies to Basic-panel simulation only. In the reported cases the failing targets were KTP400 and KTP700 with any selected firmware version, while Comfort-panel simulation stayed healthy. Siemens documents the same remedy, setting the panel firmware version to V14.0.0.0, for the related case where PLCSIM and a panel simulation lose their connection after migrating to TIA Portal V14, so the mechanism is documented: the version selection chooses which installed simulator the engineering station calls.

  1. Save a recoverable copy of the project before changing anything.
  2. Open the device view of the panel and use Change device-version to select 14.0.0.
  3. Compile the complete HMI target.
  4. Start the simulation and exercise every screen that used to precede the crash.

One condition decides whether this works for you: it was verified on a PC with TIA Portal V14.1 and V15.1 installed side by side. Selecting 14.0.0 calls a simulator that is already on the computer; the selection does not install one. On a PC that carries only V15, there may be no older simulator to call, so check the installed WinCC components before you count on this. Treat the version change as a simulator-selection workaround that lets work continue, not as proof that the current simulator has been repaired.

The device version you set here is the same property that matters when you later download to real hardware; the article on device version versus panel OS image explains how that version relates to the image on the panel itself.

Acceptance test before you call it fixed #

A simulation that merely shows its first screen is not an acceptance test. Run these checks on the bench, with the exact device version you selected:

  • The configured starting screen opens and stays open past the point where the crash used to occur.
  • Every screen transition you rely on completes without a runtime termination.
  • The simulation runs long enough to pass the failure point. Some reporters saw the crash only after the simulation had been used for a while, so a two-second launch check proves less than it looks like it does.

If the simulation still terminates under the older simulator, put the device version back to the intended value and take the captured crash record, with its faulting application, faulting module and exception code, to the vendor support channel. If it runs, continue work under the workaround, keep the crash record on file, and retest the default simulator after the next TIA Portal service pack, because a repaired simulator lets you return to the version your target hardware actually runs. The decision, per case: single-screen project crashes with pdlrt.exe named in the record, Basic panel target, older TIA Portal version installed, set the device version to 14.0.0 and keep working; no older simulator installed, or RT Professional target crashing instead, stop reinstalling and escalate with the record.

Questions asked

What does the StackHash_0a9e label on the crash file mean?

It is the name Windows gives the crash bucket for that failure, not the name of a defective component. The useful fields are inside the Windows application crash entry: the faulting application, which in these cases was pdlrt.exe, the faulting module and the exception code. If every attempt shows the same module and code, the fault is repeatable inside that component rather than changing with the project.

Why does the same PC simulate a Comfort panel fine but crash on a Basic panel?

Each panel class runs through its own simulator path on the engineering PC. A working Comfort-panel simulation proves that path and its runtime are healthy; it proves nothing about the Basic-panel simulator. That is why the diagnosis has to use a minimal project for the same target family that is failing, not a pass from a different target class.

Should I reinstall TIA Portal or delete the IM folder again?

Reported cases tried deleting the IM folder with a rebuild compile, a repair install of TIA Portal V15, a full uninstall and reinstall, reinstalling the runtime software and update 15.1.0.3, and the crash returned every time at the same startup point. Once the crash record shows the same faulting module and exception code after one unchanged reinstall, further undirected reinstalls only cost time; take that record to the vendor support channel.

Keep reading

  • Selection guide

    Which WinCC version configures a KTP700 Basic panel

    A KTP700 Basic is engineered by WinCC Basic inside TIA Portal, and V13 is the first release that carries the second-generation Basic Panels. WinCC flexible 2008 cannot insert the panel, so an existing flexible project moves to TIA Portal. An S7-300 CPU absent from the TIA catalog is configured in STEP 7 Classic instead and does not change the HMI software choice.

    HMI and touchscreens

  • Explainer

    Device version vs panel OS image on Unified Comfort Panels

    No migration needed for the image side: a Unified Comfort Panel may run an OS image newer than the device version selected in the project, and the runtime executes at that selected version. V18 cannot select a V19 device version regardless of the panel image, and a download that aborts without a reason is a network fault. The reported case was one IPv4 address shared by the PC and the panel.

    HMI and touchscreens

  • Explainer

    Which software configures a KP1200 Comfort panel

    A SIMATIC HMI KP1200 Comfort is configured with WinCC Comfort inside TIA Portal, from V11 onward; WinCC flexible 2008 SP3 has no device support for it, so nothing can be created or transferred from flexible. Pick the WinCC Comfort edition or higher, align the project's device version with the panel image, and transfer over the panel's PROFINET interface.

    HMI and touchscreens

Why PLCSIM V15 tags do not reach the HMI simulation