Selection guide
Which WinCC version configures a KTP700 Basic panel
Short answer
A KTP700 Basic is engineered by WinCC Basic inside TIA Portal, and V13 is the first release that carries the second-generation Basic Panels. WinCC flexible 2008 cannot insert the panel, so an existing flexible project moves to TIA Portal. An S7-300 CPU absent from the TIA catalog is configured in STEP 7 Classic instead and does not change the HMI software choice.

On this page
- The supported software chain
- Why WinCC flexible 2008 cannot insert the panel
- Which engineering edition to install
- Picking the exact device in the catalog
- The missing S7-300 CPU is a separate decision
- Working the case: KTP700 Basic, WinCC flexible 2008 and an S7-300 CPU
- The decision for each case
- Questions asked
A KTP700 Basic is configured with WinCC Basic inside TIA Portal, and V13 — the first release that carries it — or any later release is the whole answer to the version question. WinCC flexible 2008 cannot insert this panel: it belongs to the second generation of Basic Panels, a family that flexible predates. If the S7-300 CPU next to it is missing from your TIA Portal catalog, that is a STEP 7 Classic matter with its own documented route, and it is no reason to move the HMI back to flexible. What follows is the selection table, the edition decision and the case worked through with its arithmetic.
The supported software chain #
The panel carries order number 6AV2123-2GB03-0AX0 on its nameplate: a second-generation Basic Panel with key and touch operation, a 7 in TFT display in 65536 colors and a PROFINET interface, all stated on its data sheet.
Its device documentation, the Basic Panels 2nd Generation manual, is a WinCC (TIA Portal) document, and the WinCC engineering overview with document ID 99684510 assigns the Basic Panels to the WinCC Basic edition. V13 is the first TIA Portal release that carries the second-generation family, and every release after it keeps the device. One footnote in the manual matters when you pick a later release: certain device functions require an HMI device image compatible with WinCC (TIA Portal) V14 or higher, and some exist only on devices with a PROFINET interface — this panel has one. The chain is therefore fixed: TIA Portal, the WinCC Basic edition, and the device taken from the hardware catalog.
Why WinCC flexible 2008 cannot insert the panel #
WinCC flexible 2008 was completed before the second generation existed, so the panel is absent from its device catalog, and the engineering system has no compile target and no device image for it. Importing a library item does not help: a library delivers screens and objects, not the device integration an engineering system needs to compile for a panel. The smaller sibling hits the same wall, which is why the KTP400 Basic Color PN is missing in WinCC flexible as well.
The remedy is a TIA Portal project, not a flexible workaround: move the HMI work across the documented migration of a WinCC flexible project to TIA Portal. If both packages must share one engineering PC, mind the install order, because adding WinCC flexible to a PC that already runs TIA Portal is a known way to break the TIA installation — the failure behind why installing WinCC flexible breaks TIA Portal.
Which engineering edition to install #
Inside TIA Portal, WinCC comes in editions — Basic, Comfort, Advanced and Professional, plus Unified for the newer Unified panel line — and the engineering overview lists which functions each one carries. For this panel the edition answer is the smallest one: WinCC Basic. The boundary is also hard. Under WinCC Basic the hardware catalog offers Basic Panels only, which is why TIA Portal V14 shows only Basic panels under WinCC Basic when a Comfort device is wanted. WinCC Comfort covers the Comfort panels and includes the Basic scope; Advanced and Professional engineer PC runtime stations, not panels.
| Engineering software | KTP700 Basic status | Decision |
|---|---|---|
| WinCC flexible 2008 | Not in the device catalog; cannot be inserted | Keep it only for the older panels it supports; move this project to TIA Portal |
| TIA Portal V13 with WinCC Basic | First release that carries the device | The supported choice; insert the exact catalog entry |
| TIA Portal V14 and higher with WinCC Basic | Device carried in every later release | Same choice on a newer release; image-dependent functions need the compatible image |
| TIA Portal with WinCC Comfort | Included in the Comfort scope | Install when Comfort and Basic panels share one project |
| STEP 7 Classic V5.6 SP2 HF10 | Not an HMI engineering tool | Install only for the S7-300 CPU 317-2EJ10-0AB0 |
Picking the exact device in the catalog #
Insert the panel as a new HMI device in the project and search the hardware catalog for the KTP700 Basic entry. Several 7 inch devices sit under near-identical names in that catalog, so match the entry against the order number on the nameplate, 6AV2123-2GB03-0AX0, before you build a single screen on it. The device image on the panel must then match the project version — the same relationship covered in matching an HMI panel image to its TIA Portal project version. An older image on the panel is the easy direction, because it is updated as part of download preparation. A panel that carries a newer image than an old project expects is the awkward direction, and that is the case where downgrading a KTP700 Basic image to the version the project targets is the fix.
The missing S7-300 CPU is a separate decision #
A CPU that will not appear in the TIA Portal catalog is a STEP 7 fact, not a WinCC one, and it says nothing about which package the panel needs. The CPU in this case, the S7-300 CPU 317-2EJ10-0AB0, is not in the TIA Portal catalog of that release; its documented home is STEP 7 Classic, and STEP 7 V5.6 SP2 HF10 contains this CPU. The plant therefore runs two tools side by side: STEP 7 Classic for the PLC program, TIA Portal with WinCC Basic for the panel. The connection between the two is a runtime matter on the network — the panel reaches the CPU through its PROFINET interface — and which package holds the CPU program does not enter into it. Read the CPU's absence as a reason to install STEP 7 Classic, never as a reason to keep the panel in flexible.
Working the case: KTP700 Basic, WinCC flexible 2008 and an S7-300 CPU #
The case as it lands on the bench: an HMI project already begun in WinCC flexible 2008, a KTP700 Basic that will not appear in it, and a PLC whose CPU is missing from the TIA Portal catalog.
Inputs, each with its source:
- Panel on the bench: nameplate order number 6AV2123-2GB03-0AX0. Its data sheet gives key/touch operation, a 7 in TFT and a PROFINET interface.
- Display area from that data sheet: 154.1 mm wide, 85.9 mm high.
- Engineering PC today: WinCC flexible 2008 installed; TIA Portal V13 available.
- PLC: S7-300 CPU 317-2EJ10-0AB0, absent from that TIA Portal release's catalog.
The rule, in words: second-generation Basic Panels are engineered by WinCC Basic in TIA Portal, the minimum release is the first one that carries the device, WinCC flexible cannot insert them, and the CPU belongs to STEP 7 Classic, where STEP 7 V5.6 SP2 HF10 contains it.
The arithmetic. First confirm the data sheet belongs to the panel on the bench, using its display figures. With width 154.1 mm and height 85.9 mm, the diagonal is the square root of the sum of squares: 154.1 squared gives 23746.81 mm², 85.9 squared gives 7378.81 mm², the sum is 31125.62 mm², and the root is 176.4 mm. Converted, 176.4 mm ÷ 25.4 mm per inch = 6.9 in — the nominal 7 in of the data sheet, so the sheet and the nameplate agree. The version check needs one line: the available TIA Portal release is exactly the minimum release, the margin is zero, and no release upgrade is needed to engineer the panel.
Result: install WinCC Basic in the available TIA Portal release, move the screens from flexible 2008 through the documented migration, and configure the CPU in STEP 7 Classic with the service pack that contains it. WinCC flexible 2008 leaves this project entirely.
Decision and threshold: any TIA Portal release at or above the minimum that carries the device, with WinCC Basic installed, engineers this panel; anything below it — and every WinCC flexible — does not. On this bench the minimum is met with zero margin, which is workable because the panel asks for nothing newer. Budget the time for the migration itself: the flexible project crosses only through that path.
The decision for each case #
- New project, panel on the bench: TIA Portal at the minimum release or higher with the WinCC Basic edition, and the catalog entry matched to the nameplate order number.
- Existing WinCC flexible 2008 project for this panel: it cannot hold the device. Move it through the documented migration to WinCC Basic in TIA Portal, then verify the migrated tags and screens on the bench before the panel goes back into the machine — a rebuilt screen that writes to the wrong address is a production risk, not a cosmetic fault.
- A Comfort panel joining the same project: install WinCC Comfort; its scope includes the Basic Panels.
- S7-300 CPU missing from the TIA Portal catalog: configure it in STEP 7 Classic with the service pack that contains it. Two tools on one engineering PC, and no change to the panel's software.
- Panel image newer than the old project expects: bring the image down to the version that project targets before you compile and download.
Questions asked
Can the panel project move to a newer TIA Portal release later?
Yes, in one direction only. Opening and saving the project in a newer WinCC version upgrades it, and the older release can no longer open the saved copy. Archive the project before every upgrade and keep one engineering PC on the old release until the upgraded project compiles and downloads cleanly to the panel.
Do the other second-generation Basic Panels need the same software?
Yes. The KTP400 Basic, the KTP700 Basic and their color variants form one device family with one engineering path: WinCC Basic in TIA Portal. Adding a KTP400 Basic Color PN to the same project brings no new engineering software with it, and it is exactly as absent from WinCC flexible as its bigger sibling.
What happens when the panel image does not match the project version?
Before anything transfers, TIA Portal compares the image on the device with the version the compiled project needs and brings an older image up to date as part of the download. A newer image is the difficult direction: the panel will not accept the older project until the image is brought down to the version that project targets.
Does the KTP700 Basic need a WinCC runtime license?
No. A Basic Panel carries its runtime in the device image, so only the engineering side is licensed. The WinCC RT Advanced and RT Professional licenses belong to PC-based runtime stations, not to panels, and no panel runtime key is needed for this device.