Why KTP400 Basic Color PN is missing in WinCC flexible
Short answer
The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.
On this page
- Why is the KTP400 Basic Color PN missing from the WinCC flexible catalog?
- Will an update or reinstall of WinCC flexible add the panel?
- Can you configure a KTP400 Basic Mono PN instead and download to the color panel?
- Which TIA Portal version supports the KTP400 Basic Color PN?
- How do you connect the panel to a STEP 7 V5.6 controller project?
- Should you migrate the STEP 7 V5.6 project or use a PLC proxy?
- How do you add and configure the panel in TIA Portal?
- What checks prove the configuration before the machine runs on it?
- Can a TIA Portal HMI project go back into STEP 7 V5.6?
- Questions asked
WinCC flexible cannot configure the KTP400 Basic Color PN, and no service pack or repair installation changes that: the panel exists as an engineering target only in TIA Portal, starting with V11 SP2. If your controller application lives in STEP 7 V5.6, two routes work — migrate that project into TIA Portal, or keep it where it is and give the TIA HMI project a PLC proxy. This article explains why the entry is missing, which version to install, how to choose between those routes, and how to configure and verify the panel. The device you will select in the catalog carries order number 6AV6647-0AK11-3AX0.
Why is the KTP400 Basic Color PN missing from the WinCC flexible catalog? #
Because WinCC flexible never contained this device: the KTP400 Basic Color PN is a TIA Portal-only target, first configurable in V11 SP2, and its device definition was never added to any WinCC flexible release, so the two monochrome KTP400 entries you see are the complete list. A catalog entry is not a label — it is the device description the compiler builds against, covering the screen model, the available objects and the transfer format. The panel itself is a 4.3-inch widescreen TFT with 256 colors, key and touch operation and a PROFINET interface, and only TIA Portal ships a description of it.
| What you see | What it means | What to do |
|---|---|---|
| WinCC flexible 2008 SP5 lists only two monochrome KTP400 variants | The installed engineering system does not contain the color PROFINET device | Move the HMI configuration to TIA Portal |
| The rating plate shows 6AV6647-0AK11-3AX0 | The target is the color PROFINET panel, not a monochrome model | Select that exact number in the TIA Portal device catalog |
| The controller application sits in STEP 7 V5.6 | PLC and HMI cannot share one WinCC flexible project | Migrate the controller project or use a PLC proxy |
PROFINET compatibility is a separate question from engineering support: the interface gives the panel a place on the network, but it cannot put the panel into a catalog that predates it.
Will an update or reinstall of WinCC flexible add the panel? #
No update adds it: WinCC flexible 2008 SP5 is the final release of that product line, and a repair installation that shows only the monochrome KTP400 entries has restored exactly the catalog it is meant to have. The missing entry is a product-support boundary, not a fault on your PC. WinCC flexible carries, for each panel it lists, the device description, the compiler support and the transfer workflow; none of the three exists for this target, and none can be patched in afterwards — new panel families from the same manufacturer appear only in TIA Portal. Time spent reinstalling WinCC flexible or searching for a device update for it is time lost; install TIA Portal instead.
Can you configure a KTP400 Basic Mono PN instead and download to the color panel? #
No: the monochrome entries are different hardware, and a project compiled for one of them is built for that device's screen model and transfer format, so the color panel will not accept it as its runtime — picking a look-alike entry only moves the failure to download time. Family resemblance and screen size prove nothing about project compatibility; the entry you compile against is the device that must be connected at transfer. A project that must run on the color panel therefore starts in TIA Portal. An existing project for the monochrome variant is converted as a TIA Portal migration in which the screens are remapped for the color display, and that conversion is covered in migrating a KTP400 Basic Mono PN backup to a Color KTP400.
Which TIA Portal version supports the KTP400 Basic Color PN? #
V11 SP2 is the first version that supports it, and every later release keeps the Basic Panels in its catalog, so choose the version by what the controller migration needs and treat V11 SP2 as the floor. The panel is not the constraint; the controller project is. A migrated controller application is maintained in any version from that first supporting release onward, so a plant standardized on a later version engineers the panel there without going back to V11. If the device is still absent from an installed V11 catalog, the device catalog is completed with a hardware support package, and the install error that blocks that package on TIA Portal V11, together with its fix, is covered in KTP400 Basic Color HSP install fix for TIA Portal V11.
How do you connect the panel to a STEP 7 V5.6 controller project? #
Through one of exactly two supported routes: migrate the STEP 7 V5.6 project into TIA Portal so PLC and HMI share one project, or leave it in classic STEP 7 and represent its interface inside the HMI project with a PLC proxy. The classic tool has no editor for this device and cannot host its HMI project, so the integration you may remember from older panels — one project holding both PLC and HMI — is not available here; the two routes are what replace it. When you migrate, panels already engineered in WinCC flexible come across in the same step, as described in how to migrate a WinCC flexible project to TIA Portal. There is no third route: no export from TIA Portal that the classic tool imports, and no gateway hardware that substitutes for missing engineering support.
Should you migrate the STEP 7 V5.6 project or use a PLC proxy? #
Default to migration whenever the controller application passes its migration checks, and fall back to the PLC proxy only when the controller project must stay untouched in classic STEP 7, because the proxy route leaves two projects to keep aligned by hand. A PLC proxy is an engineering-time copy of the controller interface — the blocks and tags the HMI is allowed to see. It is not a runtime gateway: at runtime the panel talks to the real PLC over the normal Ethernet connection, and the proxy only feeds the HMI tag table and the compiler.
| Migrate into TIA Portal | PLC proxy, two projects | |
|---|---|---|
| Controller engineering | STEP 7 inside TIA Portal | stays in classic STEP 7 |
| HMI tags | linked symbolically to the migrated blocks | taken from the proxy's interface copy |
| After a controller interface change | recompile; broken links surface immediately | refresh the proxy, then recompile |
| Projects to back up and version | one | two, with a defined refresh step |
Choose migration for any controller code you are allowed to touch; choose the proxy for validated code under change control that must not be recompiled, and give that proxy refresh an owner and a fixed place in the commissioning procedure.
How do you add and configure the panel in TIA Portal? #
Add the device under its exact order number, 6AV6647-0AK11-3AX0, set its PROFINET address from the approved network schedule, create the HMI connection to the migrated controller or the proxy, reconcile the tags, compile, then transfer. In order:
- Read the rating plate and confirm the full order number; a different suffix is a different device until the catalog identifies it.
- Add the device from the project's device catalog and stop if the number is absent — another KTP400 variant is not a substitute; complete the catalog with the hardware support package first.
- Set the panel's IP address and subnet mask from the schedule. For example, with the panel at 192.168.0.10 and the PLC at 192.168.0.1, both masked 255.255.255.0: 192.168.0.10 AND 255.255.255.0 gives 192.168.0.0, and 192.168.0.1 AND 255.255.255.0 also gives 192.168.0.0 — one subnet, so the connection needs no gateway address. If the PLC instead sits at 192.168.1.1, its network is 192.168.1.0 against the panel's 192.168.0.0, and the panel then needs a gateway address to reach it.
- Create the HMI connection to the migrated controller, or to the proxy when the projects stay separate, using the addresses from the schedule.
- Reconcile every HMI tag with the controller definition — data type, address or symbolic reference, access direction and scaling — and on the proxy route add a repeatable proxy refresh so interface changes reach the HMI project.
- Compile the controller side first when it changed, then compile the HMI, and clear device, connection and tag errors before any transfer.
- Transfer to the panel. The image on the device must match what the project version delivers, a check covered in matching an HMI panel image to its TIA Portal project version. If the transfer fails, the causes and their fixes are collected in troubleshooting KTP400 Basic Color PN download failures.
What checks prove the configuration before the machine runs on it? #
Six checks: device identity, clean compilation, network path, controller reads, controller writes and — on the proxy route — proxy synchronization, all done with designated test tags before the panel is trusted on the machine.
- Device identity: the device configuration shows the KTP400 Basic Color PN with the order number from the rating plate.
- Clean compilation: no unsupported-device, unresolved-connection or unresolved-tag errors.
- Network path: panel and controller addresses match the approved schedule and sit in one subnet, as the worked example above shows.
- Controller reads: change a designated test value at the controller and confirm the HMI shows it with the correct data type; then drop the connection and confirm the panel flags the fault and recovers with current values, not stale ones.
- Controller writes: operate a designated nonhazardous test command and confirm the controller receives the intended value. Do the write and disconnect tests on an isolated bench or against a test tag that drives nothing, never against live machine outputs.
- Proxy synchronization: on the proxy route, change one controller interface item, refresh the proxy, and confirm the HMI project exposes the revised interface after recompilation.
Can a TIA Portal HMI project go back into STEP 7 V5.6? #
No: the workflow runs one way, because STEP 7 V5.6 has no container for a TIA HMI project — once the panel is engineered in TIA Portal it stays there, and the classic tool keeps at most the controller project, which is exactly what the proxy arrangement formalizes. So the integration to plan is the one above: TIA Portal holds the HMI and either the migrated controller or a proxy of it. Both tools can coexist on one engineering PC during the transition, but installing WinCC flexible after TIA Portal V13 damages the TIA installation, and the documented repair is in why installing WinCC flexible breaks TIA Portal V13. Panels already engineered in WinCC flexible keep their projects and connections while the color panel is served from TIA Portal — two tools on one machine, each owning its own devices.
Questions asked
Does the KTP400 Basic Color PN need a runtime license?
No runtime license is needed: the runtime belongs to the panel itself. Engineering requires WinCC Basic in TIA Portal, or WinCC Comfort or WinCC Advanced, which include the Basic functions, so a plant that already engineers larger panels needs no additional software for this device.
Is the panel's firmware replaced during the first transfer?
Yes, when the image on the device is older than the one the project version delivers, the transfer loads the newer image and the panel restarts, so allow extra minutes for that first download. The required image follows from the project version, not from whatever is newest.
Can the KTP400 Basic Color PN and older WinCC flexible panels serve the same PLC?
Yes. During staged upgrades it is normal for the TIA-engineered panel and the flexible-engineered panels to hold separate connections to one controller. Confirm that the controller's connection resources cover every panel and that tags written from more than one panel are coordinated so two operators cannot fight over one value.
Does the panel also work with S7-1200 and S7-1500 controllers?
Yes. The panel was designed as the HMI partner of the S7-1200 and is a documented connection partner for the S7-1500, so when the controller is eventually replaced the same panel and project stay and only the HMI connection is re-pointed to the new CPU.