Why a WinCC 7.0 Project Will Not Import into WinCC Flexible

HMI and touchscreens Published 5 min read

Short answer

A WinCC 7.0 *.MCP project cannot be imported into WinCC flexible 2008; that tool only accepts WinCC V6.2 projects. The working path is two stages: upgrade the project to WinCC 7.2, migrate it to TIA Portal with the WinCC V7 migration tool, then verify the target panel runtime before replacing the IPC677C.

On this page
  1. Why does WinCC flexible 2008 report "not a WinCC V6.2 project"?
  2. Which migration path does a WinCC 7.0 project actually take?
  3. What must be installed on the configuration PC before migrating?
  4. How do you migrate the project step by step?
  5. Can the migrated project run on an MP377 or TP1500?
  6. Will a new panel fix the two-hour IPC677C restart?
  7. What do you test before pulling the IPC677C out?
  8. Questions asked

A WinCC 7.0 *.MCP project cannot be imported into WinCC flexible 2008 Advanced SP3. That import expects a WinCC V6.2 project, so it reports the file is not a WinCC V6.2 project and stops. The working route is two stages: upgrade the project to WinCC 7.2, then run the WinCC V7 migration tool into TIA Portal, and only then decide whether an MP377 or TP1500 can run the result.

Why does WinCC flexible 2008 report "not a WinCC V6.2 project"? #

The message means exactly what it says: the import wizard only accepts WinCC V6.2 projects as source, and a WinCC 7.0 *.MCP file fails that version check before any conversion starts. WinCC 7 and WinCC flexible are separate product lines, so no retry or repair of the file changes the outcome.

Do not read the message as corruption. The project is intact; it simply does not belong to the flexible product line. Confirm the project version inside the existing WinCC installation on the IPC677C, keep the original *.MCP file untouched as your rollback copy, and stop attempting the flexible import route altogether.

Which migration path does a WinCC 7.0 project actually take? #

The path is WinCC 7.0 to WinCC 7.2 on the engineering PC, then WinCC 7.2 to TIA Portal with the WinCC V7 migration tool. Two transitions, two separate version checks. The second stage is not the flexible import that failed; it is a different workflow written for WinCC V7 projects.

Manufacturers document this distinction: TIA Portal's migration documentation covers migrating WinCC V7 projects as its own procedure, separate from the WinCC flexible migration covered elsewhere. If your source were a flexible 2008 project, you would follow a different route entirely, described in the guide on migrating a WinCC flexible project to TIA Portal.

What must be installed on the configuration PC before migrating? #

The configuration PC needs the source environment, the intermediate WinCC 7.2 environment, and the target TIA Portal version with its migration support installed, in that order. The manufacturer's WinCC Migration Guide lists, per TIA Portal version, exactly which software must be present on the configuration PC before a migration can start.

Plan the PC as a dedicated migration station: keep the original WinCC 7.0 installation for reference, install WinCC 7.2 for the first stage, and install the TIA Portal release you intend to standardize on. Mixing versions on a production engineering PC invites the kind of coexistence conflicts that break TIA Portal installations, so use a separate machine or a clean image if you can.

How do you migrate the project step by step? #

Run the stages in order and verify each one before starting the next. Skipping the intermediate upgrade is the most common cause of a failed conversion.

  1. Preserve the source. Copy the WinCC 7.0 *.MCP project, its databases and any external files to backup media, and record the IPC677C configuration and connected controllers. Work on the copy.
  2. Upgrade to WinCC 7.2. Open the project copy with WinCC 7.2 and complete its upgrade workflow. The project must open and run without unresolved migration errors in WinCC 7.2 before you continue.
  3. Inventory what you have. List screens, tags, alarms, scripts, recipes and communication connections, and flag anything that depends on the PC-station environment of the IPC677C rather than on plain HMI runtime.
  4. Migrate to TIA Portal. Run the WinCC V7 migration tool from the TIA Portal environment against the WinCC 7.2 project, following the documented preparation and execution steps in the migration chapter.
  5. Review the conversion report. The report names objects that converted cleanly and those needing manual correction; work through each flagged item before compiling.
  6. Compile the migrated project. A clean compile in TIA Portal is the gate to hardware selection, not a formality.

If the report flags recipe or screen objects, the notes on MP377 to TP1500 recipe migration and on the negative visibility range error during an MP377 to TP1500 migration cover two conversions that surface repeatedly in exactly this kind of project move.

Can the migrated project run on an MP377 or TP1500? #

Select the panel only after the project compiles, because compatibility depends on the model, its runtime options and the TIA Portal version the project landed on. A project that migrates into TIA Portal is not automatically runnable on every TIA-capable panel; the destination device must support the runtime functions and interfaces the project uses.

The IPC677C is a PC-based station, so some of what it does today lives outside plain HMI runtime. Compare your inventory from step 3 against each candidate panel's documented runtime, then confirm the exact model and software combination before ordering hardware. If the inventory shows PC-specific functions you cannot drop, the honest fallback is to keep the runtime on a PC: the migrated project can run on industrial panel PCs instead of a dedicated touch panel, preserving more of the original station's behavior than a panel conversion usually does.

Will a new panel fix the two-hour IPC677C restart? #

Migration changes the project environment, not the restart behavior of the machine you leave in place. The IPC677C's two-hour-plus restart is a property of that PC station; a migrated project loaded onto an MP377, a TP1500 or a different panel PC will start on that hardware's schedule, which you measure yourself before approval.

Treat the slow restart as the reason for the replacement project, not as a result the migration delivers. The restart measurement belongs in the acceptance test on the new hardware.

What do you test before pulling the IPC677C out? #

Load the migrated project onto the selected target hardware in a controlled bench setup and run the machine's critical path before scheduling the swap. Concretely:

  • Every flagged screen from the conversion report displays and operates correctly.
  • Tag values update against the real controller over the real connection.
  • Alarms trigger, acknowledge and log as specified.
  • Recipes, scripts and operator actions reach the control system with the expected results.
  • A controlled restart of the target hardware brings all HMI functions back, with the measured startup time recorded.

Keep the original IPC677C and the untouched WinCC 7.0 project as the rollback path until the target passes all of these tests. Only then decommission the old station.

Questions asked

Can a WinCC 7.0 project be converted into a WinCC flexible project at all?

No. WinCC 7 and WinCC flexible are separate engineering environments, and WinCC flexible 2008 only accepts WinCC V6.2 projects as migration sources. A V7 project fails that import with the version mismatch message, and no setting inside WinCC flexible changes that. Convert the project through WinCC 7.2 and TIA Portal instead.

Does the migration preserve my SCADA scripts and external applications?

The migration tool converts project objects such as screens, tags, alarms and scripts, but PC-station-specific items and external applications that ran beside the WinCC runtime on the IPC677C are not guaranteed to transfer. Inventory them before the first upgrade stage, and plan each one as a separate configuration task on the target platform after migration.

Can I keep the HMI on a PC instead of moving to a touch panel?

Yes. A migrated project can stay on a PC runtime instead of moving to an MP377 or TP1500, provided the runtime PC runs a supported operating system and the installed runtime matches the version the project was migrated into. This often keeps more of the original PC-station functionality alive than a panel conversion does.

Why was my direct migration attempt rejected as damaged or unsupported?

The rejection is a source-version check, not corruption. WinCC flexible 2008 Advanced SP3 reports the project is not a WinCC V6.2 project because the *.MCP file belongs to WinCC V7. Retrying the same import never succeeds; the project must first be upgraded through the WinCC V7 line before TIA Portal can take it.

Should I confirm panel compatibility with anyone before ordering hardware?

Yes. Panel runtime compatibility depends on the exact model, the runtime options the migrated project uses, and the TIA Portal version you land on. Check the model against the manufacturer's compatibility documentation, and confirm the specific model and software combination with your distributor before you commit to replacing the IPC677C.

Keep reading

  • Troubleshooting

    Fixing a WinCC 5.1 to 6.2 migration that will not log in

    The Project Migrator finishing without errors proves database conversion only. The missing login dialog comes from the Siemens Verkehrssteuerung V3.0 suite (VSTStart) and the WinCC Chipcard Terminal that were never installed on the new machine, while the lost SIMATIC S5 PMC Ethernet channel must be carried over from 5.1, because a CP 1613 with a SIMATIC S7 channel does not recreate the S5 155H link.

    HMI and touchscreens

  • How-to

    Migrating a WinCC 7.0 Project From Windows XP to Windows 7

    Install WinCC 7.4 on Windows 7, reinstall cleanly if the SP1 package fails, migrate the project through 7.2 with Project Migrator, license the runtime for 1024 tags because 128 runs demo mode, and replace the CP 5611 card with a CP 5612, which has 64-bit SIMATIC NET support. Each gate fails separately, so test each one.

    HMI and touchscreens

  • Comparison

    WinCC V7.4, WinCC Flexible 2008 and TIA Portal Compared

    WinCC V7.x is PC-based SCADA software, WinCC Flexible 2008 engineers operator panels and single PC stations and is discontinued as a standalone tool, and WinCC inside TIA Portal is the successor engineering platform alongside STEP 7. Decide by the target device and the exact project files on your engineering workstation, not by the shared WinCC name. STEP 7 is the PLC tool, not a WinCC product.

    HMI and touchscreens