Which WinCC option licenses carry over across TIA Portal versions

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

WinCC Logging, WinCC Recipes and WinCC Audit keys for WinCC Runtime Advanced, and WinCC Audit keys for Comfort and Mobile Panels, are version-independent and stay valid from TIA Portal V11 through V18. SIMATIC ProDiag keys are covered from V14. Upgrade the portal without buying new option keys, then verify engineering, runtime and device support separately.

On this page
  1. The option keys that carry over
  2. Where the range is documented
  3. The ProDiag boundary
  4. Worked example: an upgrade from V13 to V17
  5. What an option key does not decide
  6. Keeping the key reachable
  7. The decision
  8. Questions asked

Keep the option keys. WinCC Logging, WinCC Recipes and WinCC Audit license keys for WinCC Runtime Advanced, and the WinCC Audit key for SIMATIC Comfort and Mobile Panels, are version-independent: Siemens documents them as valid across TIA Portal from V11 through V18, and SIMATIC ProDiag keys follow the same rule from V14. Upgrading the portal does not by itself force new option keys. What an option key does not carry — the engineering license, the runtime license, the migrated project, the device support — is checked separately, and this article ends with the decision for each layer.

The option keys that carry over #

WinCC options generally have version-independent license keys: the entitlement is not locked to a single TIA Portal release within its documented scope. The licensing documentation states the rule in both directions, and the current licensing chapter, titled Licensing STEP 7 and WinCC, adds that version-independent WinCC option keys can also be used for future versions. The table is the documented list.

Licensed runtime or device Option with a version-independent key Documented validity
WinCC Runtime Advanced WinCC Logging TIA Portal V11 through V18
WinCC Runtime Advanced WinCC Recipes TIA Portal V11 through V18
WinCC Runtime Advanced WinCC Audit TIA Portal V11 through V18
WinCC Runtime Advanced SIMATIC ProDiag from V14 through V18
SIMATIC Comfort and Mobile Panels WinCC Audit TIA Portal V11 through V18
SIMATIC Comfort and Mobile Panels SIMATIC ProDiag from V14 through V18

The option name alone is not the entitlement; the licensed runtime or device category is part of it, so an Audit key for the PC runtime and an Audit key for a panel are separate line items. The list covers these combinations and no others: a differently named option, or a different runtime family such as a SCADA system, sits outside the rule.

Where the range is documented #

Siemens publishes a per-release validity table for WinCC options in the licensing chapter of the SIMATIC STEP 7 and SIMATIC WinCC manual for each release. The first documented statement ran from V11 through V16, with V15.1 listed explicitly alongside V15 — a release that is easy to overlook when you inventory what a plant actually has installed. Compatibility was then confirmed for V17, and afterwards for V18, in the licensing chapters of the corresponding manuals. The current chapter's statement about future versions is the documented basis for any release after V18.

The ProDiag boundary #

SIMATIC ProDiag appears in the list at V14, for WinCC Runtime Advanced and for SIMATIC Comfort and Mobile Panels alike. A version-independent key cannot create a feature that a release lacks: licensing compatibility and feature availability are separate checks. Below that release there is no ProDiag to license; from that release onward the key carries through the documented range like any other option key.

Worked example: an upgrade from V13 to V17 #

Example, with hypothetical keys — a planning check, not a measured test. A machine runs TIA Portal V13 with WinCC Runtime Advanced on its operator PC. Installed option keys: WinCC Recipes V13 and WinCC Audit V13. The plan moves the engineering station and the runtime to V17.

  1. Identify each entitlement by option name and runtime scope: Recipes for WinCC Runtime Advanced, Audit for WinCC Runtime Advanced.
  2. Run the range check. Both options carry version-independent keys documented for the span from V11 through V18, and V13 ≥ V11 while V17 ≤ V18, so the whole move sits inside the range. Decision: keep both keys — the upgrade needs no new option licenses.
  3. Change one input and the decision changes: a target of V19 falls outside the documented range, and the move then rests on the current chapter's future-version statement, to be confirmed on the upgraded runtime at commissioning.
  4. Clear the other layers before the download: engineering and runtime entitlements for V17, the migrated project and target device support are separate decisions, covered in the next section.

What an option key does not decide #

An option license authorizes one additional function. It does not authorize the configuration software, the runtime itself, or anything about a project or a device, so classify a licensing message by layer before acting:

Symptoms and the layer each belongs to:

What reports the problem Layer Decision
An optional function asks for a license after the upgrade Option Keep the key; check identity, runtime scope and key location
The engineering station reports a licensing fault Engineering Fix at that layer; replacing the option key will not help
The runtime reports a licensing fault before any option is used Runtime Fix at that layer; the option keys are not involved
A download or compilation fails on the panel Project or image Fix as a version or image problem, not a license problem

A missing or misplaced key shows up at runtime as the demo mode message; the missing-option-license case behind that message is covered in Why Your HMI Runtime Shows a Demo Mode Message.

Keeping the key reachable #

A valid key must also sit where the component that checks it can see it. The Automation License Manager manages the keys and provides documented transfers: drag and drop, cut and paste, and a menu command. Copying files with ordinary file-management tools is not a license transfer, and a key parked on another computer or a storage medium does not entitle a runtime that cannot see it.

The procedure, and the RT versus RC difference that decides what you may move, is walked through in WinCC RT vs RC Licenses and Moving a Runtime Key. When keys disappear on an embedded IPC, the causes are laid out in Why WinCC license keys disappear on an embedded IPC. Record which key sits on which machine at handover, so a misplaced key stays distinguishable from an incompatible one.

The decision #

  • Upgrading anywhere inside the documented range with WinCC Logging, WinCC Recipes or WinCC Audit on WinCC Runtime Advanced: keep the key.
  • WinCC Audit on SIMATIC Comfort or Mobile Panels inside that range: keep the key.
  • SIMATIC ProDiag on a target from V14 up: keep the key. Earlier releases have no ProDiag to license, and no key changes that.
  • Target beyond V18: the current licensing documentation states version-independent option keys can also be used for future versions, so keep the key and confirm on the upgraded runtime that it is accepted. A refusal there points at key placement or entitlement, not at the version number.
  • Engineering, runtime, project or device faults: fix them at their own layer. An option key purchase is not the remedy for any of them.

One caution: a license mismatch is a compliance issue, not a machine fault — close it before handover rather than running production on a demo-mode runtime.

Questions asked

Is an option key issued at a newer release valid on an older portal too?

Yes. The licensing documentation gives exactly this as the example of the version-independent rule: option keys issued at V14 remain usable with the license keys of the three generations before it, and the reverse holds as well. Rolling an engineering seat or a runtime PC back to an earlier documented release therefore does not by itself invalidate WinCC Logging, WinCC Recipes, WinCC Audit or ProDiag keys.

Where do I read the validity table for one specific release?

In the manual section on the validity of licenses for WinCC options, inside the licensing chapter of the SIMATIC STEP 7 and SIMATIC WinCC manual for that release. In the V17 manual the chapter begins around page 282; in the V18 manual around page 336. The table lists, per WinCC version, which options run on which hardware and which keys are version-independent.

Does the version-independent rule cover WinCC Professional or WinCC Unified too?

No. The documented list names options for WinCC Runtime Advanced and for SIMATIC Comfort and Mobile Panels only. WinCC Professional SCADA installations and WinCC Unified have their own license structures and their own compatibility documentation, so do not extend the rule to them by name similarity. Match the option and the runtime or device category named on the key before planning to keep it.

How current is the documented range?

The statement that first listed the covered releases carries a status date of 4 March 2021. V17 and V18 were each confirmed afterwards in the licensing chapter of the corresponding manual, and the current licensing documentation adds that version-independent keys also work for future versions. Releases beyond that rest on the future-version statement rather than on a named list.

Do I have to move the option key when I replace the runtime PC?

The key stays valid, but it has to travel: move it with the Automation License Manager's documented transfer rather than by copying files, because a key left on the old machine entitles nothing on the new one. Transfer before the swap and confirm the license tool shows the option on the destination before the runtime starts.

Keep reading

  • Explainer

    Which software configures a KP1200 Comfort panel

    A SIMATIC HMI KP1200 Comfort is configured with WinCC Comfort inside TIA Portal, from V11 onward; WinCC flexible 2008 SP3 has no device support for it, so nothing can be created or transferred from flexible. Pick the WinCC Comfort edition or higher, align the project's device version with the panel image, and transfer over the panel's PROFINET interface.

    HMI and touchscreens

  • Troubleshooting

    Keep using your WinCC Comfort V15 license with TIA Portal V14

    You do not need to buy any new license. Install the WinCC Comfort V14 engineering component beside your TIA Portal V14 Basic installation; the WinCC Comfort V15 floating license authorizes V14 and V15. The 21-day STEP 7 Professional V15 trial only covers temporary PLC editing in V15, not your Comfort Panel HMI work.

    HMI and touchscreens

  • Troubleshooting

    WinCC RT Professional to Advanced tag binding loss

    WinCC RT Professional contains an OPC channel by default: it works as a client over OPC DA and OPC UA and, with the channel activated, also serves as an OPC UA server, so an OPC requirement alone is no reason to move to RT Advanced. A test that passes on Advanced but fails on Professional has a role, identity or certificate difference to find. If a cross-project copy-paste already stripped the screen references, convert the original project with the Change device/version command instead of re-associating every binding by hand.

    HMI and touchscreens

Which Vijeo Designer version edits an XBTG5230 project