IMDTouchKnowledge BaseShop main store

Troubleshooting

WinCC RT Professional to Advanced tag binding loss

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

WinCC RT Professional contains an OPC channel by default: it works as a client over OPC DA and OPC UA and, with the channel activated, also serves as an OPC UA server, so an OPC requirement alone is no reason to move to RT Advanced. A test that passes on Advanced but fails on Professional has a role, identity or certificate difference to find. If a cross-project copy-paste already stripped the screen references, convert the original project with the Change device/version command instead of re-associating every binding by hand.

On this page
  1. What the installed runtime actually supports
  2. Stage the OPC test before changing the runtime family
  3. Why a cross-project copy-paste empties the bindings
  4. The supported path: convert the device inside the original project
  5. Worked example: pricing the manual repair
  6. Decision, case by case
  7. Questions asked

WinCC RT Professional does support OPC. The runtime contains an OPC channel by default and works as a client toward servers with data access support over both OPC DA and OPC UA; with the channel active and the runtime started, it also serves as an OPC UA server. So the request to talk OPC in a project on a CPU 1515-2-PN, engineered in TIA Portal V13, is not by itself a reason to rebuild the PC station as WinCC RT Advanced. A test client that connects through an Advanced station but fails on the Professional one points at a difference in role, identity, certificate trust or network path, not at a missing interface. And once the switch has been made with a straight cross-project copy-paste, the damage is predictable: the screen objects and animations arrive intact, and every one of the 700 tag bindings arrives empty. The repair runs through the supported device conversion, not through re-associating screens by hand.

What the installed runtime actually supports #

WinCC RT Professional brings its OPC channel by default. That channel gives the runtime client access to OPC servers with data access support, over OPC DA and OPC UA alike. The server side is documented as well: the SIMATIC HMI and OPC UA documentation includes WinCC RT Professional as an OPC UA server for typical applications, and the same OPC basics documentation covers RT Advanced and RT Professional side by side. The two families differ in scope, not in the presence of OPC.

Three pieces decide whether it runs on your machine:

  • The OPC channel has to be activated for the runtime. With it active and the runtime started, the OPC UA server service OpcUaServerWinCC comes up together with the runtime; it is not something you start by hand against a stopped runtime.
  • When the runtime connects out as an OPC UA client, the remote server has to identify the runtime's client certificate as trustworthy before the session opens. Certificate exchange is part of the first connection, not an optional extra, and the same trust logic applies in reverse when the runtime serves an external client.
  • OPC DA rides on Windows COM/DCOM, so launch and access permissions attach to the exact account the client runs under.

Read these against the release actually installed, not against the product name. The Professional and Advanced labels are not an OPC capability test; the documented roles of the installed release are.

Stage the OPC test before changing the runtime family #

Separate the test into stages, because each stage exercises a different part of the path and a failure at one says nothing about the others:

  1. Discovery — the test client lists the server or endpoint. Nothing listed means the channel is not active, a component is missing or the endpoint address is wrong.
  2. Connection — the session opens. A failure here happens before any tag is involved; check certificate trust for OPC UA, DCOM launch and access permissions for OPC DA.
  3. Browse — the client lists the exposed items. A session that opens but browses nothing points at namespace exposure or access rights.
  4. Read — items return values with quality codes. Bad quality means the server is reachable but the underlying PLC connection or the item address is wrong; the checks in when WinCC OPC UA browsing works but runtime gets no values cover this stage directly.
  5. Update — a tag you deliberately change in the PLC arrives changed at the client, which closes the loop on subscription behavior.

Record five things for every run: the role tested, the interface (OPC DA or OPC UA), the target computer, the Windows account the client runs under, and whether the path is local or remote. In the case behind this article, the same test tool connected through Advanced and failed on Professional, so the explanation sits in one of those five recorded items. If the open question is which side must serve, HMI OPC UA server vs client: which direction works walks that decision.

One safety note: run these tests with a read-only test client and the machine's outputs in a safe state, because a session with write or subscription rights can move live I/O.

Why a cross-project copy-paste empties the bindings #

An HMI tag is a named variable definition with a data type and a connection assignment. A binding is the reference from a screen property, an animation or a script to that tag. Pasting screens from a project whose PC station runs WinCC RT Professional into a new project whose station is rebuilt as WinCC RT Advanced carries the visible object and its animation settings, but each reference field points into a tag table that does not exist at the destination. The graphics and animations survive; the reference fields arrive empty.

Recreating the tags under identical names in the destination does not refill fields that were stripped at paste time. The reference is stored as a link, and a link that could not resolve when the screen arrived stays empty even after a matching tag appears; an unresolved-but-present reference and an emptied field need different repairs. This is also why the compile list, not the screen picture, is the real inventory of the damage: compile the destination project and every broken reference appears with its object location.

The supported path: convert the device inside the original project #

TIA Portal converts the device entry within one project, and that conversion moves the tag table and the screens together. In the project tree, open the shortcut menu of the PC station's device entry and run the device-change command, documented in current TIA Portal versions as Change device/version, then pick the target station in the Change device dialog. The same principle covers migration out of WinCC flexible: the documentation states that the project moves by changing the HMI device to a type supported by WinCC, not by rebuilding it project by project.

Before converting anything, secure an editable copy of the source; the preparation steps in HMI replacement: recover the project before converting cover exactly that. After the conversion, compile and repair only what the compiler lists.

If the copy-paste damage already exists, the order is: go back to the original Professional project, whose tags and bindings are intact, convert it with the device-change command, and discard the pasted screens in the Advanced project. Nothing gets re-associated unless the compiler reports specific objects.

Worked example: pricing the manual repair #

Treat the pace as an example assumption, not a measured benchmark: at a conservative 30 seconds per binding to open the object, find the emptied reference field, pick the tag from the table and confirm it compiles, the 700 bindings of the case cost 700 × 30 s = 21,000 s of editing, and 21,000 s ÷ 3,600 s/h ≈ 5.8 h, before the compile, the screen tests and whatever corrections the compile turns up.

The total moves linearly with the assumed pace: at 15 seconds per binding it is 2.9 h, at 60 seconds it is 11.7 h. That is the labor the device-change conversion performs inside the tool in one pass, leaving a repair list of only the objects the compiler flags. Use the example pace to rank repair options; if a hand repair does happen, re-time it on the first screen and re-price the rest from that measurement.

Decision, case by case #

  • OPC is the requirement and the project runs WinCC RT Professional: keep Professional. Pick the direction first. As a client, activate the OPC channel and connect over OPC DA or OPC UA. As the server for an external SCADA, activate the channel, start the runtime, confirm OpcUaServerWinCC is running, and let the server trust the SCADA client's certificate.
  • The test passes on Advanced and fails on Professional: fix the recorded difference, whether account, certificate trust, DCOM permissions or local versus remote path, instead of changing the runtime family. A connection fault is not a capability gap.
  • The switch already happened and the bindings are gone: convert the original Professional project with the device-change command and discard the pasted screens; the tag table and the references come through together.
  • Manual re-association becomes the path only when no original project survives, and then the compile list priced in the example above is the scope of the job.

Questions asked

Does WinCC RT Professional really support OPC?

Yes. The runtime documentation states that WinCC RT Professional contains an OPC channel by default and uses it as a client toward servers with data access support, over OPC DA and OPC UA. The same OPC basics documentation covers RT Advanced and RT Professional side by side. With the channel active and the runtime started, the OpcUaServerWinCC service comes up on its own. A failed connection is a configuration problem to diagnose, not proof of a missing interface.

Why did the OPC test client connect to RT Advanced but fail on RT Professional?

Record the role tested, the interface, the target computer, the Windows account the client runs under and whether the path is local or remote, for both runs. A difference in any one of them explains the split result. Two usual suspects: for OPC UA, the remote server has to trust the runtime's client certificate; for OPC DA, DCOM launch and access permissions have to cover the exact account. An interactive engineering account can pass where the production service account fails.

Can I recover the lost bindings by recreating the tags under the same names?

Not by itself. A pasted screen stores its reference as a link into the destination tag table, and a link that could not resolve when the screen arrived shows up empty. Creating a matching tag afterwards does not refill the field; the reference has to be set again on the object property, animation or script. Check one object per screen type first, then decide between hand repair and converting the original project.

How do I switch the PC station to RT Advanced without losing the tags?

Stay inside the original project and let the tool convert the device. Screens and the HMI tag table convert together, so the references stay attached. Save the converted project under its own name, compile, and repair only the objects the compiler lists.

Which OPC role does my architecture actually need?

Follow the data direction. If the external SCADA has to read your HMI tags, WinCC runs as the OPC UA server and the SCADA connects as its client. If your HMI has to read another system, WinCC needs its OPC client channel toward that server. Server capability never implies client capability, so confirm the exact role on both sides before changing the runtime family.

Keep reading

  • Explainer

    Why WinCC RT V13 is missing from the TIA V15 catalog

    TIA Portal V15 only lists WinCC RT device versions from its own generation — 14.0.0.0 and 14.0.1.0 appear, 13.0.1.0 does not. You cannot install the older version into the catalog. A station on RT V13 stays on V13 engineering, or the whole WinCC station migrates to a V15-compatible runtime; Professional and Advanced behave differently.

    HMI and touchscreens

  • How-to

    SIWAREX HMI example projects for WinCC Professional

    Yes: the vendor's SIWAREX FAQ lists an example for PC-based WinCC next to the TP700 Comfort Panel project, and a WP351 example exists for WinCC Unified. Qualify the download against three documented facts — engineering tool and version, runtime target, SIWAREX model — then carry its weighing functions across through one verified path: module to CPU1214, CPU1214 to the 1513, 1513 to HMI external tags, rebound from a mapping list.

    HMI and touchscreens

  • Troubleshooting

    Downloading a TIA Portal project to multiple HMI panels

    A TIA Portal download targets one HMI device, so the only one-action way to load several panels is one HMI device per panel in the same project, all panels in Transfer mode, then select the devices and download once. With a single device, repeat the download per address or ship a Pack & Go package, and a panel the engineering PC cannot reach loads through S7 routing on the CPU.

    HMI and touchscreens

Why WinCC Professional Images Turn White in Runtime