SIWAREX HMI example projects for WinCC Professional
Short answer
Yes: the vendor's SIWAREX FAQ lists an example for PC-based WinCC next to the TP700 Comfort Panel project, and a WP351 example exists for WinCC Unified. Qualify the download against three documented facts — engineering tool and version, runtime target, SIWAREX model — then carry its weighing functions across through one verified path: module to CPU1214, CPU1214 to the 1513, 1513 to HMI external tags, rebound from a mapping list.
On this page
- Is there a SIWAREX example that runs in WinCC Professional?
- What has to match before the example counts as compatible?
- How does weighing data get from the module on the CPU1214 to the screens?
- Which PLC interface do the new external tags need?
- What is the fastest way to rebind the example's tags?
- How do you prove the ported screens before the machine runs them?
- What keeps a weighing command safe when the chain is down?
- Questions asked
A SIWAREX example for PC-based WinCC exists: the SIWAREX FAQ entry 109477602 on the vendor's support portal lists one alongside the TP700 Comfort Panel project, and a separate WP351 example ships for WinCC Unified. The catch is that "PC-based WinCC" names neither WinCC Professional, a TIA Portal version, nor a runtime target, so the download has to be qualified before any of its screen objects is reused. This article gives the four facts that must match, sets one deliberate data path from the module on the CPU1214 through the 1513 to the HMI external tags, and replaces the object-by-object tag grind with a mapping list. The Comfort Panel example stays useful as a functional reference even where it cannot open in your Professional environment.
Is there a SIWAREX example that runs in WinCC Professional? #
Yes — the SIWAREX FAQ entry 109477602 lists an example for PC-based WinCC alongside the TP700 Comfort Panel project, and a separate ready-for-use WP351 example exists for WinCC Unified.
What is documented and what is only a label: the Comfort Panel example you already found is built for WinCC Advanced, while "PC-based WinCC" covers more than one runtime family, because a PC runtime of Advanced and WinCC Professional are different targets that share the TIA Portal shell. The differences between the WinCC versions are what decide whether an example opens, runs or merely reads well, so read the entry's own statement of tool, version and target before downloading anything.
Decision: if the entry names a tool and runtime target that match your installation, download the example and use it as the base project; if it names something else, keep it as a functional reference for the weighing screens' logic and rebuild on your own target.
What has to match before the example counts as compatible? #
Four documented facts decide it: the engineering tool the example names, the TIA Portal version it was saved in, the runtime target it was built for, and the SIWAREX module model it drives — any single mismatch makes it a reference, not a starting project.
Tool and version: a project saved in a newer TIA Portal version does not open in an older one, and the FAQ entry states the version its examples were built in. Run the same check described in checking the HMI engineering software before a panel replacement, because an example that cannot open cleanly is worth less than no example.
Runtime target: the target decides which objects and runtime functions execute at all. A Comfort Panel project and a WinCC Professional project are different targets even inside the same TIA Portal, so an object that ran on the TP700 has no automatic right to run on the PC.
Module model: a WP231 example documents the WP231's PLC interface and a WP351 example the WP351's; the layouts are model-specific, so tags taken from the wrong module's example do not rename cleanly — they misname.
Decision: all four match, use it as your base; one differs, take its screens as a functional reference and rebuild unsupported functions with Professional objects, because a successful import is never proof of runtime compatibility.
How does weighing data get from the module on the CPU1214 to the screens? #
Verify three boundaries in order — SIWAREX module to CPU1214, CPU1214 to the 1513, 1513 to the HMI external tags — and give the HMI exactly one connection, to the 1513, so no screen value depends on the module's local interface.
"Remote I/O" describes where the module sits, not how its values cross to the main PLC: the module interface and the controller-to-controller exchange are separate boundaries with separate owners. The usual split holds — the HMI displays and initiates, the controllers own the sequence and the permissives — as set out in how an HMI and a PLC divide the work in a control system.
Verify each boundary on its own evidence:
- SIWAREX module to CPU1214 — inspect the hardware configuration and the weighing program's interface; the process value must respond to a controlled load change while the module reports a valid operating state.
- CPU1214 to 1513 — inspect the configured data exchange and the program mapping; the 1513's value must follow the 1214's without unexplained scaling, with exchange health travelling alongside the data.
- 1513 to HMI — inspect the connection and the external tag assignments; every screen value must resolve to a defined item of the 1513 interface with valid quality.
Decision: expose one defined weighing interface on the 1513 — values, status, commands, responses — and point the HMI there; open a direct HMI-to-CPU1214 connection only when a weighing command must bypass the main PLC, and write down which controller owns each command if you do.
Which PLC interface do the new external tags need? #
Group the interface into measurements, status, commands and responses, and take data type, engineering unit, scale and validity for each group from the installed module's PLC interface documentation — never from the example's tag names.
| Interface group | Record from the module and controller declarations | HMI treatment |
|---|---|---|
| Measurements | Data type, unit, scale, usable range | Numeric field with matching unit and precision |
| Status | Validity bit, operating state, exchange health | Visible state indication, gating command availability |
| Commands | Allowed operations, encoding, initiating conditions | Controlled write through the defined command interface |
| Responses | Acceptance, completion, rejection, fault information | Operator feedback from the controller's response |
Compare every row against the module's own interface description and both controllers' declarations: the same measurement must carry equivalent engineering values and matching validity states in the CPU1214 and the 1513. A number without its validity bit tells the operator nothing, because it could be a live measurement, a stale leftover or a communication artifact. The module manual is the source for data types and command encoding; the example only shows how one screen once used them.
Decision: no external tag enters the project until its row in this table is filled from the module documentation and checked against both controllers.
What is the fastest way to rebind the example's tags? #
Build a mapping list first — one row per example function naming its destination PLC item — then apply it through the tag table and the reuse features of your installed version; every instance that shares a tag rebinds in one pass instead of one edit per object.
- Inventory every tagged dependency, visible and hidden: I/O fields, button press and release events, visibility and color animations, alarm triggers, scripts. Hidden references survive long after the visible fields are corrected.
- Create the HMI connection to the 1513 — an S7 connection over Ethernet — and prove it on a known controller value with valid quality before a single example object is imported.
- Create the external tags from the mapping list, with connection, data type and access direction exactly as written.
- Import or rebuild the screens, then rebind through the tag table and reuse features rather than object by object; rebuild whatever the import drops with Professional objects instead of trusting the import.
- Compile and inspect: no unresolved tags, no unsupported functions, no leftover references to the example's connection.
The finished list is also the record for the next person who ports these screens. Decision: if you catch yourself retyping the same tag name on object after object, stop and extend the mapping list — the list is the work, the objects are its output.
How do you prove the ported screens before the machine runs them? #
Prove it on the bench: simulate the project first, then run the real chain with a test weight and a forced connection loss, so screen logic, scaling and quality behavior are each demonstrated before the machine sees them.
TIA Portal documents simulation for RT Professional among its compile-and-load targets, alongside Basic Panels, Panels, Comfort Panels and RT Advanced, so the ported screens can be exercised without touching hardware. Simulation exercises screen logic and tag bindings, not the live driver path to the 1513; when a simulated project shows no data at all, the cause is usually in the simulation setup, as in when Runtime Professional shows no data from PLCSIM.
Worked example with illustrative values — use the test weight your calibration check already uses. Apply a 10.000 kg test weight at the module. The expected chain reads: module tag on the CPU1214 = 10.000 kg, interface tag on the 1513 = 10.000 kg, HMI external tag = 10.000 kg with the validity bit true. Chain error = 10.000 kg - 10.000 kg = 0.000 kg; if the 1513 instead shows 100.00, the controller-to-controller copy has applied a factor of 10 (10.000 × 10 = 100.00), and the fix belongs where the copy is made, never in the HMI tag.
Break the HMI-to-1513 connection while a weight is displayed: the driver timeout and the tag's data quality govern when the value stops being valid, and the screen must follow the quality flag instead of freezing the number. Run command tests with the process in a defined safe state — a bench test that writes live command bits to a running plant is not a bench test. Press each command object once and watch the controller rather than the screen; a button that moves nothing is the classic bench find, the same failure seen when simulation buttons do not change PLC tags.
Before the project goes onto its runtime PC, confirm the runtime side exists: the engineering install that opened the project is not a runtime, and whether a WinCC Professional entry means SCADA runtime is installed decides whether that PC needs a runtime license and a version match before anything loads.
Decision: the screens are proven when the test weight reads identically at all three boundaries with validity true, a broken connection shows as bad quality within the driver timeout, and each command button produces exactly one request and one documented response.
What keeps a weighing command safe when the chain is down? #
Keep every permissive in the controller: the 1513 must reject a weighing command whose validity bit is false or whose response handshake has not completed, no matter what the screen enables or greys out.
A successful HMI write proves communication, not command execution: the 1513 interprets the request, checks operating conditions, issues the command to the module through its documented interface and reports the outcome. Review press, release and repeated-operation events on every command object so one operator action produces exactly one request — a held button must not hammer the handshake. Show the controller's response — accepted, completed, rejected, faulted — as the button's feedback instead of an optimistic completion animation, with the validity bit visible next to the weight so a disconnected chain never looks alive. A disabled button guides the operator; the controller-side check protects the process.
Decision: an example's command objects survive the port only as initiators of defined requests; anything that embeds sequence logic or permissives in the screen is rebuilt into the 1513 program, and the HMI keeps display and initiation.
Questions asked
Is there a SIWAREX example for WinCC Unified instead?
Yes. The vendor lists a WP351 example project for WinCC Unified, described as ready-for-use, with its main display documented for verification. Match the module first: a WP351 example assumes a WP351 module, not a WP231. A Unified project does not open as a Professional project or the other way around, so for Professional work the Unified example is a reference design, not a starting project.
Can the HMI reach the CPU1214 and the 1513 at the same time?
A PC runtime can hold several controller connections within its documented limits, but each connection consumes connection resources on the CPU it contacts, and the CPU1214 has fewer of those resources than a 1513-class controller. Keep one HMI connection to the 1513 and let the controllers exchange weighing data. Add a direct connection to the module's CPU only when a command must bypass the main PLC, and record which controller owns each command.
What does the weight display show when the connection drops?
The tag's data quality goes bad while the last received value can stay on the screen, which makes a disconnected weighing chain look alive. Bench-test it: break the connection, record when quality drops — the driver timeout governs that moment — and what the field shows. Configure the object to react to bad quality and keep the validity bit visible beside the value.
Why will the compiled screens not start on the runtime PC?
Usually the runtime side is missing or mismatched. A WinCC Professional engineering install alone is not a runtime; the runtime PC needs a matching runtime license, and the project's configured runtime device version must match the runtime version installed on that workstation. Check all three before blaming the ported screens, because the port itself rarely breaks loading.