Troubleshooting
Why WinCC Runtime Professional Shows No Data From PLCSIM
Short answer
The runtime window opening with static screens means the runtime process runs but its path to the simulated CPU does not. Point the access point in Set PG/PC Interface at PLCSIM or the matching TCP/IP route, compile the PC station, connect the TIA project to PLCSIM, and put the CPU in RUN before the runtime starts.
On this page
- What the static screen tells you
- Why the runtime cannot reach the simulated CPU
- Two working interface configurations
- The subnet check on the TCP/IP route
- Bring the runtime online, in order
- Checks with the readings to expect
- A 30-second proof with numbers
- Pitfalls that keep the screen dead
- When every setting checks out
- Questions asked
A WinCC Runtime Professional window that opens, draws its screens and never moves a value is not a graphics fault: the runtime process is running and its connection to the simulated CPU is not. In a TIA Portal project with a PC station runtime and the CPU in PLCSIM, two settings decide whether tags flow — the access point in Set PG/PC Interface on the PC, and the connection between the TIA project and PLCSIM. Set the access point to PLCSIM or to the matching TCP/IP route, put the simulated CPU in RUN, compile the PC station, connect the project to PLCSIM, then start the runtime simulation. Values follow within each tag's acquisition cycle as soon as both layers agree.
What the static screen tells you #
Three conditions look identical on a static screen, and they point at different layers.
| What you see | What it means | Where to look |
|---|---|---|
| Runtime window opens, I/O fields blank or at initial values, no animation | Runtime is up, no working connection to the CPU | Access point, HMI connection, project-to-PLCSIM link |
| Fields fill with invalid markers, such as hash signs | Connection is up, the tags themselves are unreadable | Tag addresses, data block access mode |
| PLCSIM in RUN but values never change, even in a watch table | The program is not executing | CPU state in PLCSIM, download |
The reported fault is the first row: the CPU program runs in simulation, the runtime window renders, nothing updates. Work the communication path before touching a single HMI tag.
Why the runtime cannot reach the simulated CPU #
WinCC Runtime Professional runs as its own Windows process. It reaches a controller through the interface assigned in Set PG/PC Interface — the access point mapped to the application the runtime uses. A physical CPU is reached through a real network adapter; a simulated CPU exists only inside PLCSIM, on the simulator's virtual interface. When the access point still names a physical adapter or an unrelated access point, the runtime opens a connection that never arrives anywhere, and every tag sits at its initial value.
Two layers must agree, and neither overrides the other: the HMI connection configured in the project (partner CPU, interface type, IP address, rack and slot) and the PC-level interface assignment. The same interface setting decides the route to real hardware, which is where WinCC Professional runtime not connecting to an S7-1500 begins its diagnosis.
A third dependency sits above both: the TIA project itself must be connected to PLCSIM. Starting the CPU simulation and the runtime simulation as two independent actions is not enough. The rule is symmetric, and why HMI simulation cannot talk to a simulated PLC is the same missing link seen from the panel side.
Two working interface configurations #
Pick one and keep both layers consistent with it:
- PLCSIM access point: in Set PG/PC Interface, assign the access point the runtime uses to PLCSIM, so the runtime takes the simulator's virtual path.
- PLCSIM over TCP/IP: set the HMI connection to Ethernet with TCP/IP, enter the simulated CPU's IP address, and assign the PC interface to the matching TCP/IP route.
Access-point names differ between PLCSIM versions and installed adapter sets. Read the exact names from the dialog on the engineering PC that runs the runtime; do not carry them over from another installation.
The subnet check on the TCP/IP route #
With TCP/IP, the simulated CPU's address and the PC-side adapter address must share a subnet. Worked check: a simulated CPU at 192.168.0.1 with subnet mask 255.255.255.0 and a PC adapter at 192.168.0.10 both sit in 192.168.0.0/24, so the pair routes. An adapter at 192.168.1.10 does not: its subnet is 192.168.1.0/24, the third octet differs, and there is no path to the CPU. Decision: place the simulated CPU on a subnet no physical adapter on the PC uses. An adapter that owns the subnet captures the traffic and produces the same silent failure as an S7-1200 showing link lights while TIA Portal cannot connect.
Bring the runtime online, in order #
- Open Set PG/PC Interface on the PC that runs the runtime, select the PLCSIM access point or the matching TCP/IP route, apply, close.
- Download hardware and software to the simulated CPU from TIA Portal, then set the CPU to RUN in PLCSIM.
- Open the HMI connection settings and confirm the partner CPU, interface type and IP address match the simulated CPU.
- Compile the PC station, hardware and software, so changed connection parameters reach the runtime.
- Connect the TIA project to PLCSIM.
- Start the runtime simulation — CPU in RUN first, runtime second.
- After any interface or connection change on an attempt that already ran, stop and restart the runtime simulation.
Checks with the readings to expect #
- PLCSIM CPU state: RUN with the indicator lit. Anything else and the program produces no changing values.
- Watch table online to the simulated CPU: a counter or toggled bit changes. Live values there with a static runtime localize the fault to the interface or HMI connection, because the CPU side is healthy.
- Runtime screen: an I/O field bound to the toggled tag follows the change within that tag's acquisition cycle.
- Write test: enter a value in a runtime I/O field and read it back in the watch table. Arrival proves the path in both directions. Keep write tests on the simulated CPU or an isolated bench, never on a machine that can move.
A 30-second proof with numbers #
Bench example on a V15 project. Program the simulated CPU to add 1 to an integer tag every second, and set that tag's acquisition cycle in the runtime to 1 s. Over 30 s the CPU adds 30 counts (30 s × 1 count/s = 30 counts). The display lags the CPU by at most about two cycles — one acquisition plus the screen refresh — so at any instant the runtime reads within roughly 2 counts of the CPU, and after 30 s it stands 30 counts higher than at the start. Decision: a watch table that climbs by 30 while the display stays flat proves the CPU side and condemns the access point or HMI connection; a display that tracks within 2 counts closes the case.
Pitfalls that keep the screen dead #
- Interface changed but the PC station not recompiled: the compiled runtime keeps the old connection parameters until it is compiled and the simulation restarted.
- Runtime started before the CPU reached RUN: the first connection attempt fails and tags sit at stale values; restart the runtime simulation.
- Assuming the two simulations find each other on their own: the project-to-PLCSIM link is a separate action.
- Overlapping adapters: a physical adapter on the CPU's subnet captures the traffic; disable unused adapters or move the simulated CPU address.
- Firewall or endpoint security blocking the runtime process: with everything else verified, test on an isolated engineering PC, then add the specific rules for the runtime.
When every setting checks out #
If the access point, the HMI connection, the compile and the project-to-PLCSIM link are all verified and tags still do not move, suspect the version pair. A reported case on recent releases: WinCC Runtime Professional V21 got no tag updates from PLCSIM V21, including with Update 1, and switching to PLCSIM Advanced V8.0 restored communication. Treat that as a reported workaround, not a specification — but on that version pair it is the next move after the settings, and it decides the case without touching the project.
Questions asked
Can I test the screens without any PLC or simulator running?
Yes. Use the WinCC Runtime Professional Tag Simulator: select the tags you want to simulate, then pick a simulation type and an update cycle for each tag. It stands in for the tag source only, so it proves screens, animations and internal logic, but it does not exercise the driver path to a controller. A project that passes on the tag simulator can still fail against PLCSIM.
After the fix my fields show hash markers instead of values. Is the connection still bad?
No, and that is progress. Hash markers mean the connection is up and the tags themselves are unreadable. Check that each tag's address matches the block in the CPU, and check the access mode of the data blocks the tags read; a mismatch between the runtime's addressing and the block access leaves values invalid while communication stays healthy. Recompile after correcting.
The runtime shows a licensing error at startup. Does that stop tag updates?
Treat it as a separate fault and clear it first. A documented message for this case states that WinCC Professional licensing could not be completed because the Automation License Manager is not installed correctly. Repair the Automation License Manager as Siemens documents for your installation, confirm the runtime starts without that message, and only then judge the tag path.
Do I need a second PC or a network adapter to run both simulations together?
No. PLCSIM and the runtime run as two processes on one engineering PC and meet on the simulator's virtual interface, with no cable, adapter or second node involved. The single requirement is that the access point in Set PG/PC Interface points at PLCSIM, so the runtime takes the virtual path instead of searching physical adapters.