WinCC Professional V15 multiuser client runtime setup

HMI and touchscreens Published 5 min read

Short answer

In TIA Portal V15, a WinCC Professional multiuser application is a client/server runtime split: one PC runs WinCC Runtime Professional as the server that owns the PLC connections, and each operator station runs a runtime client pointed at that server. The WinCC Explorer workflow from V7 does not apply, and installing the engineering package alone gives no PC a runtime role.

On this page
  1. What multiuser means in WinCC Professional V15
  2. Licenses: engineering is not runtime
  3. The setup order
  4. Example: one runtime server and three operator stations
  5. Firewall and name resolution
  6. Start-up checks on the bench
  7. Questions asked

In TIA Portal V15, a WinCC Professional multiuser application is a client/server runtime split: one PC runs WinCC Runtime Professional as the server that holds the loaded project and owns every PLC connection, and each operator station runs a runtime client pointed at that server. You configure all of it inside TIA Portal — the WinCC Explorer client-project workflow from WinCC V7 has no equivalent here. Installing the WinCC Professional engineering package on a PC gives that PC no runtime role at all; the runtime software and its licensing are separate per station. This article gives the role split, the setup order, the firewall step that gets skipped, and a worked station count.

What multiuser means in WinCC Professional V15 #

Multiuser describes two different things, and the guides you find online often mix them. Multiuser engineering means several engineers work on one project stored on a project server; you set that up under TIA Portal's settings in the multiuser area, where you add a server connection for the project. Multiuser runtime means several operator stations display and operate one running application; the server PC executes the project with WinCC Runtime Professional and supplies process data to the clients. Your question is the runtime case.

If your references are WinCC V7 guides, note that the Explorer-based server/client procedure cannot be transplanted step for step: the version differences between the Explorer products and the TIA Portal products are laid out in WinCC Explorer vs Advanced, Professional, Flexible and Unified. Build this system with the Professional workflow inside TIA Portal, not with any standalone HMI tool.

Licenses: engineering is not runtime #

A WinCC Professional entry in the installed-software list proves engineering is present; whether runtime is present is a different check, covered in Does a WinCC Professional entry mean SCADA runtime is installed. Commit to this before touching the network: the server PC needs WinCC Runtime Professional installed and licensed for its server role, and each client PC needs the runtime client role installed and licensed for its role. Check every station's installed components and licenses with the Siemens license management tool, and match the engineering release, the runtime release, and the operating system against the Siemens compatibility documentation for V15. The engineering seat can sit on the server PC or on a separate laptop; either is fine as long as each PC holds what its role requires.

The setup order #

Work in this order; a client cannot rescue a server that is not running:

  1. On the engineering PC, create the project in TIA Portal V15 with WinCC Professional.
  2. Insert a WinCC Runtime Professional PC station for the server. Configure its PLC connections, tags, screens, and alarms there — the server owns all process communication. If the server reaches an S7-1500 as an OPC UA client instead of through an integrated driver, that link is configured in TIA Portal as well; Connect an S7-1500 to SCADA over OPC UA from TIA Portal walks through that setup.
  3. Insert a WinCC client station for each operator PC. In each client's runtime settings, assign the server and select which server screens the client displays.
  4. Compile, resolve every error, then load the server station to the server PC and start WinCC Runtime Professional there.
  5. Load each client project to its operator PC and start the runtime client there.
  6. Verify values end to end, server first, then clients.

Keep the load destination explicit at steps 4 and 5: a valid project loaded to the wrong PC still leaves the intended server or client unavailable.

Example: one runtime server and three operator stations #

Suppose the machine has three operator PCs at the line plus one server PC in the electrical room. The station count is 1 server + 3 clients = 4 runtime stations. The PLC connections are configured once, on the server; if each of the 4 stations instead ran its own standalone project, you would configure and maintain 4 copies of the same connection list. The clients are 4 − 1 = 3 client projects, each carrying only its server assignment and screen selection, because each client displays the server's data rather than collecting its own. The engineering work happens in one seat of TIA Portal V15 with WinCC Professional, on the server PC or a separate laptop. That is the whole point of the split: one connection list to maintain, three thin clients to add or replace.

Firewall and name resolution #

Runtime communication between the server and its clients fails at three different layers, so test them in order. First, each client needs a route to the server: unique IP addresses on the same subnet or a configured route between them. Second, each client must resolve the server's computer name, because the client projects address the server by name — from a client, ping the server's name and confirm the reply comes from the server's address, and fix name resolution (DNS or the client's hosts file) if the address answers but the name does not. Third, the firewall must allow the runtime traffic. Only the Windows Firewall is approved for operation with WinCC; once it is enabled, run SIMATIC Security Control again on both the server and the clients so it adapts the security settings. Disabling the firewall or typing in guessed port numbers is not a commissioning fix — the tool exists to create the documented rules.

Start-up checks on the bench #

Prove the system before the machine goes live. Put the server and one client on an isolated bench with verified, non-safety-related test tags, the way you would for Testing HMI Simulation Against a Live PLC, and run these checks:

  • The server runtime starts on the server PC, opens the start screen, and follows a changing PLC value, so a frozen display cannot masquerade as a healthy connection.
  • The client connects to the intended server by name and shows the same changing value.
  • A write from the client reaches the PLC and reads back — on the bench, on a test tag only.
  • Disconnecting the client and restarting it reconnects to the running server without a server restart.

When all four pass on the bench, load the remaining client projects and repeat the connection and write checks at each operator station. If a client shows valid screens but invalid values while the server is healthy, the fault is in that client's server assignment or in name resolution, not in the PLC connection.

Questions asked

Does each client station need its own PLC connection?

No. The server owns every controller connection, and each client only displays and operates the server application. If the server shows live values but a client shows invalid ones, check that client's server assignment and whether the client PC resolves the server's computer name, not the PLC driver or the connection settings.

Can the engineering PC and the runtime server be the same PC?

Yes. One PC can hold TIA Portal V15 with WinCC Professional for configuring the project and also run WinCC Runtime Professional as the server. Engineering and runtime stay separate installations with separate licensing on that PC, so confirm both roles with the Siemens license manager before start-up.

Can I reuse a WinCC V7 Explorer client project here?

No. WinCC Professional lives inside TIA Portal and has no WinCC Explorer, so the V7 client-project procedure does not carry over. Rebuild the server station and the client stations in the V15 project, then load the server to the server PC and the client projects to the operator PCs again.

What firewall changes does the multiuser system need?

Only the Windows Firewall is approved for WinCC operation. After you enable it, run SIMATIC Security Control again and let it adapt the security settings for the runtime communication. Do not disable the firewall or hand-enter port numbers as a commissioning shortcut; the tool creates the documented rules for you.

Keep reading

  • Troubleshooting

    Checking WinCC OPC registrations after a 7.0 setup

    After a WinCC 7.0 setup, the file C:\Documents and Settings\All Users\Documents\Siemens\SimaticSecurityControl#tmpRules.xml records the installed components and their executable paths, including the three OPC servers and OpcEnum.exe. A missing entry there is the first thing to check when OPC communication fails; the fix is a setup repair, never a hand edit.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Professional Shows No Data From PLCSIM

    The runtime window opening with static screens means the runtime process runs but its path to the simulated CPU does not. Point the access point in Set PG/PC Interface at PLCSIM or the matching TCP/IP route, compile the PC station, connect the TIA project to PLCSIM, and put the CPU in RUN before the runtime starts.

    HMI and touchscreens

  • How-to

    Connecting an Omron CV1000 PLC to WinCC over an OPC server

    Classic WinCC has no Omron CV-series channel, so the working route is an OPC server that speaks Host Link to the CV1000 and OPC DA to WinCC. Configure the server against the PLC first, prove one read, then build WinCC tags from the server's item addresses. Use the documented CV1000-CPU01-EV1 Host Link reference values: ASCII, 7 data bits, even parity, 2 stop bits, unit 00, 9600 or 19200 bps.

    HMI and touchscreens