IMDTouchKnowledge BaseShop main store

Troubleshooting

Downloading a TIA Portal project to multiple HMI panels

HMI and touchscreens Published 7 min read

Short answer

A TIA Portal download targets one HMI device, so the only one-action way to load several panels is one HMI device per panel in the same project, all panels in Transfer mode, then select the devices and download once. With a single device, repeat the download per address or ship a Pack & Go package, and a panel the engineering PC cannot reach loads through S7 routing on the CPU.

On this page
  1. Why a download reaches one device, not the network
  2. Check the project for one HMI device per panel
  3. Batch download on one subnet
  4. When the scan finds fewer panels than expected
  5. Panels the PC cannot reach: download through S7 routing
  6. Pack & Go for panels away from the engineering station
  7. Verify the batch before you leave
  8. The decision for each setup
  9. Questions asked

Nothing in TIA Portal broadcasts one project to every panel it finds on the network. A download always targets one HMI device and the compiled project stored under it, so the number of panels a single action can load equals the number of HMI devices in the project. Set the project up that way and the batch works: one HMI device per panel with its own IP address, every panel in Transfer mode, then select all the devices and download once. With only one device for identical panels, copy it once per panel, download the same device once per address, or ship a Pack & Go package to the machine. A panel the engineering PC cannot reach loads through S7 routing on the CPU, which for a V13 project next to a STEP 7 V5.5 CPU 416F-3 means the routing configuration in the S7 project, not a direct PC-to-panel path.

Why a download reaches one device, not the network #

A WinCC (TIA Portal) project stores one compiled runtime configuration under each HMI device object, and the download dialog addresses that device through the subnet and IP address in its properties. Selecting several HMI devices turns one download action into a scan for each selected device's address, loading them one after the other — as close to a broadcast as TIA Portal gets. There is no Siemens utility that sweeps the network and pushes one project into every panel it finds, and a panel with no HMI device in the project has nothing to receive no matter how often you scan. Decision: the panels that must share one download action need one HMI device each, each carrying the IP address its physical panel actually uses.

Check the project for one HMI device per panel #

Open the project tree and count HMI devices against the panels on the wall.

  • One device per physical panel: the batch download in the next section works as it stands.
  • One device shared by several identical panels: a multi-select download cannot address the extras. Copy the device once per panel and continue, or keep the single device and run the same download once per address, changing the target each time.
  • Several devices built separately, one per panel with different content: they still batch in one action; each device simply loads its own compiled project.

Copying a device keeps its screens, tags and alarms; the copies differ in name, IP address and, where relevant, their PLC connection settings. Keep one master device for edits and re-copy after changes, or maintain every copy deliberately — drift between copies is the standing cost of this path. Decision: copies when you want the whole fleet loaded in one sitting; per-address repeats when you want the project tree left alone.

Batch download on one subnet #

A panel in Transfer mode has left runtime, so the machine runs without its operator screens until the load finishes — schedule the batch for a stop or a watched window.

  1. Compile every HMI device, hardware and software, and clear every error first; a device that fails to compile interrupts the batch.
  2. On each panel, open the Control Panel, select 'Service and Commissioning' > 'Transfer' and make sure 'Enable transfer' is activated, so the panel waits on its transfer screen.
  3. Select all the HMI devices in the project tree and start the download to device.
  4. In the loading dialog, confirm each device resolves to the IP address of its physical panel through the adapter that sits on the panel subnet.
  5. Start the load; each panel takes its project and restarts into runtime while the batch continues on its own.

A panel that answers the engineering PC directly loads over the ordinary transfer path — Use the Transfer Dialog Not a NetPro Connection for HMI Download explains why a NetPro connection is the wrong vehicle for it.

Worked example: four TP1500 panels, one action #

Take a V13 project whose master device serves a TP1500 at 192.168.10.11 (example addresses throughout) and three identical panels beside it. Copy the master three times, rename the copies by location, and enter 192.168.10.12, 192.168.10.13 and 192.168.10.14 in the copies' properties. Put the engineering PC at 192.168.10.5 with subnet mask 255.255.255.0. The arithmetic: a 255.255.255.0 mask makes 192.168.10.1 through 192.168.10.254 one local subnet, so the PC and all four panels sit in the same broadcast domain and one interface scan reaches all four. One download action then loads four compiled projects back to back — the same bytes as four separate transfers, in one sitting instead of four trips. Keeping the single device instead means four full downloads with the target address changed between runs: the bytes do not change, only the number of visits.

When the scan finds fewer panels than expected #

A scan that reports fewer devices than the project holds is a network finding, not a project finding. Work down this list:

  • The dialog's interface selection is not the adapter on the panel subnet — the one holding 192.168.10.5 in the example. Pick the right adapter and rescan.
  • A panel is still in runtime and ignores the scan. Put it into Transfer mode and rescan.
  • The panel does not answer the address you set. Ping it; if a different address replies, the panel has fallen back to an old one, and Why an HMI Panel Reverts to Its Old Address at Startup covers that fault.
  • The panel answers but refuses the load. That is an image and project version mismatch, and Matching an HMI Panel Image to Its TIA Portal Project Version is the fix path.
  • No reply at all: check cabling and switch ports before blaming TIA Portal.

Panels the PC cannot reach: download through S7 routing #

A panel that talks to the CPU but not to the engineering PC sits on a segment the PC does not reach. For that topology Siemens states the rule directly: "The download of a WinCC (TIA Portal) project from the configuration computer to a panel should not be made via a direct connection but via an S7 routing with an S7 CPU connected in between." Three things must hold: the CPU routes between the two subnets, the panel subnet is known to the project in the network view, and the HMI connection to the CPU is integrated in the project. The transfer then starts from the HMI device with 'Online > Extended download to device...' and rides the CPU path.

The combined configuration adds a constraint: the CPU 416F-3 is configured in STEP 7 V5.5, not in TIA Portal, so the routing configuration lives in the S7 project's NetPro, and it must be loaded to the CPU before the HMI transfer can use it — What STEP 7 is in a PLC project, and which one you need sorts out which STEP 7 owns which part of a combined project. Reachability is the same subnet property on the PLC side, which is why why an S7-1200 is reachable only after TIA Portal adds a PC IP address matters whenever a node answers nothing. Decision: no ping from the PC but a live panel-to-CPU link means the load goes through the CPU, not around it.

Pack & Go for panels away from the engineering station #

When the panels are installed where the engineering station cannot go, Pack & Go takes over: the tool at the engineering PC packages the compiled HMI project into a transfer package, and a service PC with the Pack & Go loader loads the panels without the TIA Portal project present. Treat every package as a snapshot — label it with the project version and the compile date, because panels loaded on different days from unlabeled packages are how a fleet drifts. Decision: no route from the PC and no way to bring the PC to the panels means a package carried to the machine and loaded panel by panel.

Verify the batch before you leave #

Run these checks on every panel the batch touched:

  • The panel restarts into runtime and shows the start screen; no transfer screen remains.
  • The connection to the CPU comes up and live process values update, with no connection alarm.
  • The project version and compile timestamp shown on the panel match the engineering project; panels loaded in one batch carry identical timestamps.
  • A known tag on the panel equals the value in a watch table against the PLC.
  • One panel survives a power cycle and returns to runtime on its own with the new project retained.

The decision for each setup #

  • One HMI device per panel, all on one subnet: compile everything, Transfer mode on every panel, select all devices, one download action.
  • One device, several identical panels on one subnet: copy the device per panel with the real addresses and batch, or download once per address.
  • Panel reachable from the CPU only: S7 routing through the CPU, with the routing configured in the STEP 7 project of a combined configuration.
  • Panels out of reach of both PC and route: a Pack & Go package carried to the machine.
  • Scan finds fewer panels than devices: fix the network first — adapter, transfer mode, address — then the image version.

Questions asked

Does a batch download put the same content on every panel?

No. Each HMI device in the project receives its own compiled project. If you copied one master device, the copies are identical, so those panels match; if the project was built with separate devices, each panel gets its own screens, tags and alarms. The batch is one download action, never one shared image pushed to every panel.

How long does a four-panel batch take compared with four separate downloads?

The transfer time is the same, because every panel still receives its full compiled project. A batch of four runs about four single-panel transfers back to back, but in one sitting instead of four trips to the panels. Budget the same total minutes, plus a few more for the scan and the transfer-mode setup.

Can I load the panels without taking them out of runtime?

No. Schedule the batch for a stop or a watched window, and load all panels in one batch so the outage is one window rather than several.

Does Pack & Go need the TIA Portal project on the service laptop?

No. The package is created at the engineering station and loaded by a separate Pack & Go loader, so the service laptop needs the loader rather than the TIA Portal project. Keep each package labeled with the project version and compile date so panels loaded on different days stay traceable to the same source.

Keep reading

  • Explainer

    PowerTags vs the variables per device limit in TIA Portal HMI

    The variables per device limit in a panel's technical data counts every entry in the HMI tag tables, internal tags and PLC-linked tags together. A PowerTag is only a tag with an external link and is a PC runtime licensing counter, so size the project from the compile log's total tag count. The compiler can finish an over-limit build without a warning, so compare the counts yourself.

    HMI and touchscreens

  • How-to

    Editing a Delta DOP HMI project without breaking PLC comms

    Downloading a revised project to a Delta DOP panel replaces only the panel's project; the PLC program and its port configuration are untouched. The link survives because the driver and serial parameters are stored separately in each device and a revision leaves them matching. Record both sides first, then prove read and write after the download.

    HMI and touchscreens

  • How-to

    Combining two migrated WinCC HMI projects in TIA Portal

    You cannot merge two migrated WinCC projects into one TIA Portal project automatically. Pick one project as the destination and move the complete HMI device from the other by copy and paste between two TIA Portal instances, by opening the source as a reference project and dragging it in, or through a global user library. The result is one project holding two separate HMI devices, not one merged device.

    HMI and touchscreens