Troubleshooting
Why an HMI Panel Reverts to Its Old Address at Startup
Short answer
The panel boots with the address stored in its downloaded HMI project, not the one typed into its setup screens, so a local edit cannot survive a restart. Copy the package A backup project, change the panel station address and controller connection to package C's values, compile, and download it again over PROFIBUS with the panel in transfer mode. Clear the duplicated station address before expecting the SCADA link back.
On this page
The address comes back because it is not stored where you are changing it. When the HMI runtime starts, it loads its communication configuration from the downloaded project, and that configuration replaces the panel-side value you set. A panel moved from compressor package A to package C therefore boots as a package A station every time until the package A backup project itself is edited: set the panel's station address to C's free one, point the controller connection at C's PLC, compile, and download the project again with the panel in transfer mode. Treat the SCADA outage as the same fault first, because a duplicated station address takes an entire PROFIBUS segment down. The sections below explain the ownership mechanism, work through a station-map check, and give the edit-and-download order that makes the change stick.
Why the panel boots back at A's address #
Two settings sit behind the symptom, and they are not the same setting. The station address says who the panel is on the PROFIBUS segment. The controller connection in the project says which PLC the panel talks to and through which interface. Changing the address in the panel's own screens touches neither the project's connection entries nor what the runtime loads.
Runtime is the executing HMI application, as distinct from the panel's setup and transfer screens. When runtime starts it reads its communication configuration from the project stored on the panel, and package A's project still carries A's address. That is why the change never survives a restart: the winning setting lives in the project. Any change that must survive a restart is a project change, and a project change always ends in a new download to the panel — why an HMI edit needs a new runtime download explains what actually gets transferred and when.
Check what the backup actually is #
A backup is one of three things: the editable engineering project, a compiled runtime file, or a device restore image of the panel's current state. Only the editable project can be repointed. A compiled runtime carries A's connection settings as fixed data, and a restore image reproduces the panel exactly as it sat in A's cabinet, A's address included; neither exposes the connection for editing.
If what you hold is not the editable project, stop before planning edits and recover the engineering source from the maintenance archive, because a compiled download file and a restore image cannot be turned back into one. When no editable project exists anywhere, the job stops being an address edit and becomes the replacement path described in replacing an old HMI when no project files exist. If your engineering seat has since moved to TIA Portal, a WinCC flexible source can be migrated into it rather than re-created.
Read the panel nameplate and compare it with the target device configured in the project before any conversion: screen size and key layout alone do not establish project compatibility.
Worked example: a panel that boots at station address 4 on package C #
Inputs, all example values — read your own from C's PLC hardware configuration, the SCADA station list and the backup project:
- Package C segment: C's PLC as DP master at station address 2, the SCADA computer's communication processor at station address 4, and the position C's old HMI held, station address 10.
- Package A backup project: panel station address 4, controller connection targeted at the DP master at station address 2.
- PROFIBUS operating addresses run from 0 through 125 per station; address 126 is reserved for commissioning and 127 is not permitted.
The rule: every live station on one PROFIBUS segment must hold an address no other live station on that segment holds, and one collision faults the entire segment, not just the two stations involved.
The arithmetic. Startup map with A's project loaded: PLC master 2, SCADA processor 4, moved panel 4. Address 4 appears twice — a duplicate — so the segment faults, live values freeze and the SCADA link drops with it. After the edit the map is 2, 4 and 10: each address appears once, and 10 lies inside the operating range and is not the commissioning address.
The result: the panel belongs at station address 10 on package C's segment, with its controller connection still pointed at the DP master, which is now C's PLC.
The decision and its threshold: one duplicated address anywhere on a segment is a bus-wide fault, so this map check comes before any driver, tag or SCADA diagnosis. If the startup map shows the same address on two live stations, correct the project's address and re-download before anything else. An operating address outside the permitted range, or the commissioning address left in normal running, is the same class of error and gets corrected the same way.
Edit the project and download it again #
- Copy the backup project and edit only the copy, keeping package A's original untouched as the recovery baseline.
- Open the project's connection editor — in WinCC flexible that is the Connections editor under Communication in the project tree. Set the panel's own station address to package C's freed address and confirm the controller connection identifies C's PLC; where A and C used different bus settings, match C's interface parameters.
- Compile the project and clear every device, connection and tag error before downloading; a build that reports unresolved configuration errors will not reliably change the startup behavior.
- Set up the transfer path. Put the panel into transfer mode on the channel your PC adapter uses, and set the transfer on the configuration PC to the same adapter. Transferring a WinCC flexible project over MPI or PROFIBUS requires matching settings on the panel and on the configuration PC, and a PC adapter that programs PLCs does not by itself prove the panel download works — verify the pair before you depend on it.
- Download the compiled project and let the panel restart into runtime. The station address it comes up with is now the project's, which is the point.
Prove the panel now belongs to package C #
Run the acceptance checks on a bench with C's PLC or the project's simulator and verified test tags, following the bench practice in testing HMI simulation against a live PLC. Three readings decide it:
- Restart the panel twice and read the station address after each boot; it must hold C's value both times — the original symptom, now used as the pass test.
- Write incrementing values into a spare counter tag in C's PLC from the engineering side and watch it on a test screen; a moving number proves the connection reaches C's controller, a static one means the panel is still bound to A.
- Press each operator command with C's outputs inhibited and confirm in the PLC that it landed on the intended C variable.
Keep package C's outputs inhibited until every command destination is proven: a command can write successfully to the wrong variable, and a plausible-looking number can come from the wrong PLC location.
When the bench passes, seat the connector in the new cabinet and check the segment: terminating resistors switched on at both physical ends of the bus cable.
If SCADA still cannot connect after the fix #
Work down this order. Read the PLC's bus diagnostics first: with the duplicate cleared, the bus fault entry should stay clear while the panel runs. If diagnostics are clear and the SCADA link still fails, the fault has moved into the SCADA station's own configuration — the SCADA machine holds its own station address on the segment and a connection entry that may still describe the dead panel, its old address, or a communication processor that is switched off. Correct that entry to the repointed panel's address and restart the SCADA connection.
If bus diagnostics never clear, the fault is physical or still a duplicate: check the panel's connector and the terminating resistors at both segment ends, then re-read the station map from every live station, because a device you did not move — a drive, a remote I/O drop — can hold the address you just gave the panel.
Questions asked
Can I change the address in the panel's setup screens instead of the project?
No. The runtime application loads its communication configuration from the downloaded project at every start, so a panel-side value loses to the project each time. That is exactly why the address returned to package A's value after each restart. Both the station address and the controller connection live in the project: edit them there, compile, and download the project again.
What does a duplicated PROFIBUS station address do to the bus?
It drops the whole segment, not just the two stations involved. Live values freeze on every HMI on that segment, the PLC logs a bus fault, and the SCADA link fails even though its own settings never changed. PROFIBUS operating addresses run from 0 through 125, address 126 is reserved for commissioning, and no two live stations on one segment may share an address. Read the PLC bus diagnostics first; after hardware moves, a duplicate is the most common segment-wide cause.
Will a PC adapter that programs the PLC also download the panel project?
Only when the transfer is set up as a panel transfer on both ends. Put the panel into transfer mode on the channel the adapter uses, point the engineering software's transfer settings at that adapter, and confirm the driver and interface match. A transfer over MPI or PROFIBUS needs settings on the panel and on the configuration PC. A successful PLC programming session through the same adapter proves nothing about the panel download path.
What if the backup is only a compiled runtime file or a restore image?
Then there is nothing to edit. A compiled runtime file carries package A's connection settings as fixed data, and a device restore image reproduces the panel's old state exactly, package A's address included. Neither exposes the connection settings for editing. You need the editable engineering project, typically from the engineering archive or maintenance records; without it the panel cannot be repointed, only restored to behave as package A.