Explainer
What an HTML5 HMI runtime lacks in its first release
Short answer
The first HTML5-based HMI runtime shipped with TIA Portal V16 (build 16.0.0.x) cannot mirror dotted PLC tag names, rejects nested anonymous STRUCTs in UDTs, restricts plant objects to the S7-1500, strips flashing from graphics lists, and blocks Alarm View, Trend View, graphics-list inputs and constants inside faceplates. Flatten nested STRUCTs into named UDTs, rename tags through a mapping export, script the flash, and pass the feature checklist on your build before committing a migration.
On this page
- Which release do these limits apply to?
- Why can an HMI tag no longer mirror a dotted PLC tag name?
- Why does a nested STRUCT in a UDT block the migration?
- Why do plant objects only work on the S7-1500?
- Which faceplate features are missing in the first release?
- What happened to flashing on a graphics list?
- What else is missing from the first release?
- Should you commit a migration on the first release?
- Questions asked
The first HTML5-based HMI runtime that shipped inside TIA Portal V16, build 16.0.0.x, cannot mirror dotted PLC tag names, rejects nested anonymous STRUCTs in UDTs, restricts plant objects to the S7-1500 family, strips flashing from graphics lists, and blocks Alarm View, Trend View, graphics-list inputs and constants inside faceplate types. Work around what you can: flatten nested STRUCTs into named UDTs, rename tags through a mapping export, and drive flashing with a scheduled script. Then pass a feature checklist on your exact build before you commit a migration, because several of these gaps were lifted only in later releases.
Which release do these limits apply to? #
These gaps describe the first HTML5-based HMI runtime that shipped with TIA Portal V16, runtime build 16.0.0.x for Unified Comfort Panels and the PC station, and Siemens removed several of them in later releases, most visibly faceplate alarm and trend views in TIA V18.
Everything below is reported behavior of that first generation, so treat it as a scope to re-verify rather than a permanent verdict. The clearest confirmed closure is documented: from TIA V18, trends and alarm views can be configured inside faceplates. For every other item on the list, open the release documentation for the exact build and service pack you install, compile a bench project, and re-test; features have moved between builds, and a limit that killed a design in the first release may be gone in the version you actually deploy.
Why can an HMI tag no longer mirror a dotted PLC tag name? #
The first release rejects the period and other special characters in HMI tag names, so an HMI tag can no longer carry the same name as the PLC tag it mirrors; a dotted PLC name such as Motor_1.Status.Running has to be renamed, typically to Motor_1_Status_Running.
The period is exactly the separator the PLC uses between UDT members, so the convention that kept the previous runtime's projects coherent — identical PLC and HMI tag names — stops being possible, and consistency checks that used to be automatic become manual comparisons.
Generate the replacements mechanically rather than by hand: export the PLC tag list, substitute an underscore for every period, and import the result as HMI tags. Keep the substitution mapping as a CSV under version control, so the next change to a PLC UDT can be diffed against the mapping and the affected screen dynamizations re-linked on purpose instead of being discovered dead at runtime.
Why does a nested STRUCT in a UDT block the migration? #
The first release rejects a UDT that contains an anonymous STRUCT nested inside another STRUCT when it generates HMI tags, so a motor type carrying a protection STRUCT and a control STRUCT fails until each nested STRUCT is extracted into a named UDT of its own.
Migration libraries hit this first, because years of engineering on the previous runtime group data with nested STRUCT declarations inside UDTs. The declarations compile fine on the PLC; the runtime refuses them when it generates HMI tags. For example, a motor type UDT_Motor carrying a protection STRUCT and a control STRUCT inside it is rejected:
TYPE UDT_Motor :
STRUCT
Name : STRING[20];
Protection : STRUCT // anonymous STRUCT: rejected
overload : BOOL;
eStop : BOOL;
END_STRUCT;
Control : STRUCT // anonymous STRUCT: rejected
start : BOOL;
stop : BOOL;
END_STRUCT;
END_STRUCT;
END_TYPE
Extract each nested STRUCT into a named UDT and reference it by name:
TYPE UDT_Protection :
STRUCT
overload : BOOL;
eStop : BOOL;
END_STRUCT;
END_TYPE
TYPE UDT_Control :
STRUCT
start : BOOL;
stop : BOOL;
END_STRUCT;
END_TYPE
TYPE UDT_Motor :
STRUCT
Name : STRING[20];
Protection : UDT_Protection;
Control : UDT_Control;
END_STRUCT;
END_TYPE
Because the named UDTs keep the same member names and data types, and the instance name is unchanged, the SCL logic is untouched. What changes is HMI work: every screen object, faceplate link and script that used the nested member path has to be re-pointed.
Budget the flattening before you begin. For an illustrative library of 40 UDTs in which 25 types carry one nested STRUCT and 5 types carry two, flattening creates 25 + (2 × 5) = 35 new named UDT definitions and grows the library from 40 to 75 types — 35 new library entries to maintain, and that many member paths to re-link on every screen that used them.
Why do plant objects only work on the S7-1500? #
Plant objects in the first release bind a faceplate type to a controller data block only on the S7-1500 family, while the S7-1200, ET 200SP CPUs and classic S7-300/400 controllers are excluded even though they support the same data-block and UDT mechanisms.
The loss is structural, not cosmetic: one plant object definition is meant to serve every motor, valve or drive in the project by tying the faceplate type to a data block instance. On the excluded controllers that reuse is gone, so each device gets its faceplates instantiated manually.
Two constraints shape the S7-1500 workflow as well. The plant object works properly only when the complete instance data block is selected as its interface data type, which pulls tens to hundreds of tags into the interface for even a modest device. And clearing the "Visible in HMI" check box on individual data block items propagates to HMI tags but is not honored for plant object properties — a documented inconsistency you cannot configure away.
The decision follows directly: commit plant objects on S7-1500 projects only. On an S7-1200 machine, instantiate the faceplates manually per device or stay on the runtime that already does the job.
Which faceplate features are missing in the first release? #
Faceplates in build 16.0.0.x cannot host an Alarm View or a Trend View, cannot take a graphics list as an input parameter, cannot expose tags outside their interface to scripts, and cannot take constants as actual parameters, while copy and paste between faceplate types does not function.
Each row below is a gap reported for that build, measured against the WinCC Professional workflow you would migrate from:
| Faceplate capability | WinCC Professional | First release | Consequence at the machine |
|---|---|---|---|
| Alarm View inside the faceplate | Supported | Not supported | A motor faceplate cannot show its own alarm list |
| Trend View inside the faceplate | Supported | Not supported | An analog faceplate has no trend strip |
| Graphics list as input property | Supported | Text list only | Symbolic state display degrades |
| Constants as interface parameters | Supported | Tags only | Static configuration has to be repeated for every instance |
| Bit selection on byte, word or dword interface tags | Supported | Not supported | Visibility dynamization on a single bit is unreachable |
| Property dynamizations in the graphics editor | Visible | Not visible | Two circles set invisible in the type both render in the instance |
| Copy and paste between faceplate types | Supported | Not working | Authoring dozens of types becomes impractical |
| Script access to tags outside the interface | Full namespace | Interface tags only | Out-of-interface tags are unreachable from faceplate script properties |
Rows one and two were the first to close, in the V18 release noted above; design a first-release project as if every row were still open, then re-test on your build. The faceplate flashing property behaves oddly in the same generation: it offers Always, Never and On range violation, and selecting the range-violation mode on a Bool tag is accepted but produces no visible effect.
Trends still exist at screen level, so logged values are not lost to the release — but trend retention has to be proven before you commit, which is exactly the discipline in verifying HMI historical trend retention before committing.
What happened to flashing on a graphics list? #
The first release takes flashing away from graphics lists, so the two-state alternating graphic that the previous runtime produced with a single flashing attribute now needs a scripted substitute that toggles a tag and swaps visibility between two stacked graphic objects.
Worked example, with illustrative numbers: one scheduled script function inverts a shared Bool tag every 500 ms. Two stacked graphics objects dynamized on that tag alternate twice per second, so the flash period is 2 × 500 ms = 1000 ms and the blink rate is 1 Hz. Driving all 30 flashing elements of a screen from that one shared tag keeps the script at 120 toggle executions per minute, because 2 toggles per second × 60 seconds = 120, no matter how many elements use it; giving each element its own tag would multiply the executions by the element count.
A scripted flash is presentation, not protection, so any indication an operator must act on under alarm conditions stays on the PLC alarm system and its annunciation, never on a script-driven visibility toggle.
What else is missing from the first release? #
Beyond faceplates and flashing, the first release ships without a graphics IO field, without a menu and toolbar editor, and without object grouping, multi-select or layer moves on a screen — and three engineering behaviors cost real commissioning time.
- Navigation has to be built screen by screen: there is no menu and toolbar editor and no template screen, so every screen carries its own navigation functions.
- Layout work is one object at a time: you cannot group objects, select more than one, or move a selection to another layer with a single command.
- Script errors surface late: a JavaScript syntax problem often passes unnoticed until project compilation, and the reported location frequently points at an object without errors, so you search for the real fault by hand.
- SVG imports are filtered silently: TIA Portal accepts the file, then refuses some graphics at compile with the message
SVG empty or not Siemens compatible, and the online help names no supported feature set; custom SVG elements also render differently from browser to browser. - Edits are heavy: even a slight change in project structure requires a full project download and a runtime stop, so plan the upload windows into commissioning instead of discovering them live.
Should you commit a migration on the first release? #
Commit only after the screen feature checklist passes on your exact build: for a new S7-1500 machine, scope the project without faceplate alarm and trend windows; for a migrated library, flatten the nested STRUCTs first; for anything else, stay on the proven runtime.
New machine on an S7-1500 that needs no per-device alarm or trend window inside its faceplates: workable, if you scope it that way from day one and budget the tag-name mapping export, the manual navigation build and the full-download edit cycle into the engineering estimate.
Migration of an existing WinCC Professional or WinCC 7.5 library: flatten the nested STRUCTs into named UDTs before anything else, because tag generation is the first hurdle, then rebuild the faceplate types around the table above. Prove the whole screen feature checklist on a bench project before you commit — the same discipline as proving a PC-based HMI before replacing panel terminals.
Any project whose checklist fails on the installed build: stay on the current runtime. The gaps above are engineering cost you can estimate; an unproven runtime at the machine is downtime you cannot.
When a later build clears the checklist and the target becomes a PC at the machine: the runtime station is specified then, and that hardware is one of the industrial panel PCs sized for the door cut-out and the visualization load.
Questions asked
Do the same first-release limits apply to a Unified Comfort Panel and to the PC station?
Yes. These limits sit in the shared engineering and runtime generation, so a project that fails on tag naming, nested STRUCTs or faceplate interfaces fails the same way on either target. Compile against your real target early, because panel images and runtime feature sets are matched to specific TIA Portal versions, and a bench compile on the wrong target can hide a gap you will only meet at the machine.
Does flattening nested STRUCTs into named UDTs break the PLC program?
No, provided each new named UDT keeps the member names and data types of the original nested STRUCT and the instance name is unchanged, so the SCL logic resolves exactly as before. The cost is engineering work, not logic: member paths change, so every screen dynamization, faceplate link and script that referenced the old nested path must be re-pointed, and the new type definitions become library entries you maintain from then on.
Can a first-release faceplate still show its device alarms somewhere?
Yes, at screen level rather than inside the faceplate. Plant alarms keep working at controller level, and a screen-level alarm view displays them, filtered as far as the control allows. What you give up is the per-device window: a motor faceplate that opens with only that motor's alarms and events, so the operator reads the shared screen list and loses the one-device context the faceplate design assumed.
What belongs on the bench checklist before committing a migration?
Build one bench project with your real UDT library and one instance of each faceplate type, then test the failure points: tag import with dotted names, nested STRUCT generation, copy and paste between faceplate types, alarm and trend placement inside a faceplate, a scripted flash on the target hardware, and a timed small structural edit through full download and runtime restart. Anything that fails on your build gets scoped as permanently missing.