Explainer
Why WinCC RT V13 is missing from the TIA V15 catalog
Short answer
TIA Portal V15 only lists WinCC RT device versions from its own generation — 14.0.0.0 and 14.0.1.0 appear, 13.0.1.0 does not. You cannot install the older version into the catalog. A station on RT V13 stays on V13 engineering, or the whole WinCC station migrates to a V15-compatible runtime; Professional and Advanced behave differently.
On this page
TIA Portal V15 does not list WinCC RT 13.0.1.0 in its hardware catalog, and no support package adds it. The V15 catalog offers the runtime versions from the 14-generation — 14.0.0.0 and 14.0.1.0 — and everything newer; a 13-generation device version is outside what that catalog carries. That is a catalog rule, not a missing download: you cannot install WinCC RT 13.0.1.0 into TIA V15. If the station on machine A runs RT V13, either you engineer the WinCC part in a matching V13 environment or you migrate the whole WinCC station to a V15-compatible runtime and validate it. Which path is open depends on one thing: whether the station is RT Advanced or RT Professional. Professional cannot be compiled from a newer TIA version to an older device version; Advanced can carry different device versions in one project.
What the hardware catalog actually lists #
The hardware catalog pane shows the installed device versions in a tree, and when you add a PC station you pick the runtime branch under Simatic HMI Application and choose a version in the information pane. Each TIA Portal generation ships the runtime device versions that generation supports. V15 lists 14.0.0.0 and 14.0.1.0 for WinCC RT Advanced and RT Professional; 13.0.1.0 is not there, and there is no hardware support package that installs it. Older operator panels were dropped from V15 the same way, so a device version absent from the catalog is absent by design, not by accident.
This also means an older runtime entry cannot be recovered by copying catalog data or project fragments between installations. A project carries its target device version only if that version exists in the opening TIA version's catalog.
What a V13 to V15 conversion changes #
Converting the V13 project into V15 does not preserve the runtime target. A station written against WinCC RT 13.0.1.0 comes out of the conversion showing 15.0.0.0, because the V15 catalog substitutes the nearest supported device version rather than keeping one it does not carry. The converted project therefore targets a runtime generation the PC does not have installed.
Before editing anything, work on a copy and read two values: the device version in the converted project's PC station properties, and the runtime version actually installed on the machine A PC. If those differ, a compile and load from the converted project will fail or change the runtime behavior on a machine that is running production. The same version-matching discipline applies to panel images; the way a runtime version has to match the project target is the same check described in article:matching-an-hmi-panel-image-to-its-tia-portal-project-version.
The rule that decides: Advanced versus Professional #
The two runtime editions behave differently when device versions mix:
- RT Advanced accepts different device versions in one project. You can keep a 13.0.1.0 station in a project opened by a newer TIA version and add a second station of a different version beside it. The change-device and change-version functions on the PC station properties also work more reliably here.
- RT Professional does not accept compiling from a newer TIA version to an older device version. Once you have opened a Professional station in V15 and the device has been converted to 15.0.0.0, you cannot push it back down to a 13-generation runtime. A Professional station must stay in its matching V13 engineering environment, or the runtime on the PC is upgraded so it matches what the newer TIA version compiles.
Open the original V13 project first and read the station's device type before you plan anything. If it says Professional, the catalog limitation is a hard boundary; if it says Advanced, you have room to work with mixed versions.
One station, two machines #
The stated goal is one operator station where the operator switches between machine A and machine B — one WinCC project, one runtime instance, two controller connections. That is a supported architecture: a single HMI project carries a configured connection and its own tag set for each PLC, and the screens and navigation present the two machines side by side. What it is not is two runtime projects; a PC runs one WinCC runtime instance, a limit covered in article:why-wincc-runtime-v13-cannot-run-two-instances-on-one-pc.
Adding machine B's 1512SP-1 PN to the operator station does not require merging PLC projects. Keep machine A's 1516-3 PN/DP project untouched — no program edits, no hardware configuration changes, no download to that CPU. The new connection, tags and screens live entirely in the WinCC project. A compile of the HMI station does not download anything to a PLC; keep the load target set to the PC station so a mis-click cannot alter a controller.
Optimized tags and the PLC proxy #
When the PLC and the HMI live in separate projects, cross-project tag access goes through the PLC proxy workflow described in the TIA Portal help under that name. It works straight away when the tags you need are in standard, non-optimized data blocks. When the blocks are partially optimized, the proxy cannot resolve the tags directly and you have to build a defined interface between the projects before anything imports cleanly. Test tag visibility and addressing in a copy of the project before committing to the architecture; do not assume tags resolve the way they do for standard blocks. A related compile-and-load failure between TIA versions and a PC station is covered in article:fixing-a-wincc-pc-station-download-comms-error-from-tia-portal-v13.
Worked example: why the reload fails #
Machine A's station is RT Professional, developed in TIA V13 against runtime 13.0.1.0. You convert the project into TIA V15. The upgrade maps the device to the nearest version V15 carries, so the PC station now reads 15.0.0.0. The PC runs 13.0.1.0. A V15 compile of a Professional station targets 15.0.0.0 and cannot target an older device version, so the load either is refused or demands a runtime update on the production PC. Version 15.0.0.0 minus 13.0.1.0 is not a rounding gap — they are different product generations with different runtime software, and V15's catalog has no 13.x entry to fall back on. The only ways out are developing in a V13 environment or upgrading the PC's runtime so it matches the converted project.
The decision #
Identify the edition first; the path follows from it:
- Station is RT Professional and machine A must stay on its installed V13 runtime: engineer the WinCC application in a matching V13 environment — an isolated installation or virtual machine with the same V13 setup is the practical way to keep that toolchain beside your current one — and add machine B's connection and screens there. Machine B's PLC project stays in its own TIA V15 project; the two meet through the PLC proxy or through non-optimized tags in a defined interface.
- Station is RT Professional and a V15 migration is acceptable: treat it as a full station migration. Convert a copy, confirm the resulting device version, arrange the matching V15 runtime and its licensing for the PC, recompile, and validate trends and alarm history before touching the production machine.
- Station is RT Advanced: check whether mixed device versions work for this project in your TIA version. If they do, add the new connection and screens without converting the old station's target version.
Whichever path you take, back up the V13 project and the runtime's archive databases before the first compile, because a successful conversion proves the project opens, not that the historical trends and alarm records survive the runtime change.
Questions asked
Is there an HSP that adds WinCC RT 13.0.1.0 to TIA Portal V15?
No. TIA Portal V15 ships the WinCC RT device versions it supports — 14.0.0.0 and 14.0.1.0 in the Advanced and Professional branches — and there is no hardware support package that adds 13.0.1.0. Do not copy catalog data or project files between installations to force the entry in. Keep the WinCC part in a V13 environment or migrate the station to a V15-compatible runtime.
Why does my converted project show version 15.0.0.0 when the original was 13.0.1.0?
The TIA Portal upgrade changed the project's target device to the nearest runtime version the new catalog offers, not the version installed on the PC. Open the converted project's PC station properties and read the device version there, then check which runtime software the target PC actually has. The project version and the installed runtime must match before you compile and load.
Can RT Advanced and RT Professional both use different device versions in one project?
No, only RT Advanced does. With RT Advanced you can place devices of different versions — for example a 14.0.1.0 station beside a 13.0.1.0 one — in a single project. RT Professional does not accept compiling from a newer TIA version to an older device version, so a Professional station must be developed in its matching V13 environment or upgraded to the newer runtime.
Can I add machine B's PLC to the old station without touching machine A's program?
Yes. One HMI project can carry a connection to each controller; the WinCC project and the PLC projects stay separate. Configure a new connection and tags for the second CPU in the HMI project only, and download just the HMI station. A compiler run on the HMI never requires a download to either PLC, so keep the download target set to the PC station.