Keep using your WinCC Comfort V15 license with TIA Portal V14

HMI and touchscreens Published 6 min read

Short answer

You do not need to buy any new license. Install the WinCC Comfort V14 engineering component beside your TIA Portal V14 Basic installation; the WinCC Comfort V15 floating license authorizes V14 and V15. The 21-day STEP 7 Professional V15 trial only covers temporary PLC editing in V15, not your Comfort Panel HMI work.

On this page
  1. What you actually have installed
  2. Why the KP700 Comfort is missing in V14
  3. Symptoms, causes and actions
  4. Which software arrangement fits which job
  5. Installing WinCC Comfort V14 step by step
  6. Keeping V14 and V15 project copies under control
  7. The decision
  8. Questions asked

You do not need to buy a V15 Basic license, a V15 Professional license, or any upgrade. Your WinCC Comfort V15 floating license is also valid for WinCC Comfort V14, so the fix is to install the WinCC Comfort V14 engineering component beside your existing TIA Portal V14 Basic installation and let the license manager pick up the V15 floating license. Siemens' WinCC migration guide states that a purchase of WinCC (TIA Portal) V15 provides a license that is also valid for V14 and V13. The catch is coverage direction: it works downwards, not upwards, so a V14 license would not authorize V15 work. Keep the V15 installation on the same PC; the two releases coexist, and the 21-day STEP 7 Professional V15 trial that came with the package only licenses temporary PLC editing in V15, not your Comfort Panel HMI engineering.

What you actually have installed #

Your starter kit for the KP700 Comfort included the SIMATIC WinCC Comfort V15 software package. After installing it on the PC that already runs TIA Portal V14 Basic, the Automation License Manager shows two new entries: a permanent WinCC Comfort Version 15.0 floating license and a time-limited STEP 7 Professional Version 15.0 trial.

These are two different entitlements. The WinCC Comfort floating license is permanent and covers HMI engineering in V15 and V14. The STEP 7 Professional trial is a separate, 21-day entitlement that covers PLC engineering in V15 only. Before the trial expires, V15 looks fully licensed because both editors are open; after day 21, only HMI editing in V15 survives on permanent rights.

Why the KP700 Comfort is missing in V14 #

A TIA Portal license does not install the editors it authorizes. TIA Portal V14 Basic shows only the device families its own license covers, which is why Basic Panels appear and the KP700 Comfort does not. The same reason TIA Portal shows only Basic panels under WinCC Basic applies here: the Comfort device catalog and HMI editor live in the WinCC Comfort component of the matching release, article:why-tia-portal-v14-shows-only-basic-panels-under-wincc-basic.

Installing WinCC Comfort V15 added HMI engineering to the V15 environment, not to your V14 installation. Each release integrates its own components. To add the KP700 Comfort to a V14 project, the PC needs the V14 WinCC Comfort software installed. The V15 floating license then authorizes that V14 component without any new purchase.

Symptoms, causes and actions #

  • KP700 Comfort unavailable in the V14 project: TIA Portal V14 Basic is installed but the WinCC Comfort V14 component is not. Install WinCC Comfort V14; the V15 floating license activates it.
  • V15 permits both PLC and HMI work right after installation: the package added a permanent WinCC Comfort V15 license and a temporary STEP 7 Professional V15 trial. Plan work around the 21-day trial limit.
  • V15 PLC editing stops after 21 days: the STEP 7 Professional trial expired. Continue HMI engineering under the WinCC license, and buy a STEP 7 V14-to-V15 upgrade only if you need permanent V15 PLC editing.
  • V14 Basic still opens your existing PLC projects: that floating license is unaffected. Keep V14 for licensed PLC work.
  • Two TIA Portal releases on one PC: V14 and V15 are separate installations. Open each project copy in its intended release.

Which software arrangement fits which job #

Engineering job Software arrangement License used What to buy
Edit the KP700 Comfort HMI in a V14 project TIA Portal V14 Basic plus WinCC Comfort V14 V14 Basic license plus the V15 WinCC Comfort floating license Nothing
Edit only the HMI in V15 after the trial expires WinCC Comfort V15 installation WinCC Comfort V15 floating license Nothing
Edit PLC logic permanently in V15 STEP 7 V15 engineering software A permanent STEP 7 V15 entitlement The V14-to-V15 STEP 7 upgrade, only for PLC work
PLC and HMI work in V14 V14 Basic plus WinCC Comfort V14 V14 Basic license plus the V15 WinCC Comfort floating license Nothing

Buying STEP 7 Professional V15 just to keep editing the panel is the wrong correction. Professional licensing matters only when the V15 PLC functions you need exceed what your V14 Basic license covers. Buying a separate WinCC Comfort V14 license duplicates an entitlement your V15 floating license already provides.

Installing WinCC Comfort V14 step by step #

  1. Record the current license state. In the Automation License Manager, identify the permanent WinCC Comfort Version 15.0 floating license, the TIA Portal V14 Basic license, and the 21-day STEP 7 Professional Version 15.0 trial. Do not treat the trial as part of the permanent entitlement.
  2. Protect your projects. Make independent copies before opening anything in another release; keep the V14 copy for V14 work and a separate copy for any V15 work.
  3. Obtain the WinCC Comfort V14 installation package through an official Siemens distribution or support channel. The installer and the license are separate items, and the license you already hold.
  4. Install WinCC Comfort V14 on the PC that already runs TIA Portal V14 Basic. Select the V14 product component, not a rerun of the V15 package.
  5. Leave WinCC Comfort V15 installed if you still want V15 HMI engineering. The two releases coexist.
  6. Confirm license recognition. Start the V14 environment and check that the V15 floating license authorizes the installed V14 Comfort component.
  7. Open the V14 project copy and add the KP700 Comfort from the now-visible device catalog.
  8. Test the two license paths separately: PLC editing in V14 under the Basic license, Comfort HMI editing under the WinCC license. In V15, separate HMI work from PLC work so the expired trial does not mask a missing permanent STEP 7 entitlement.

Keeping V14 and V15 project copies under control #

Coexistence solves licensing and editor availability, not project interchangeability. A project saved in V15 moves forward and cannot be reopened in V14 the same way; Siemens' own compatibility documentation notes that projects from versions before V14 cannot be opened directly with much later releases, and the same one-way rule applies between V14 and V15. Keep the untouched V14 backup until both the HMI and PLC portions have been reopened, compiled and checked in the intended environment. If V15 offers a migration step, apply it only to the designated V15 copy. If you later move the project to a runtime PC instead of the panel, the same release discipline applies to the runtime, article:run-a-tia-portal-v14-hmi-on-wincc-runtime-advanced.

The decision #

Keep V14 Basic, install WinCC Comfort V14, and let the V15 floating license cover it: that answers the original question for panel engineering at no extra purchase. Treat the V15 installation as HMI-only once the 21-day STEP 7 Professional trial expires, and buy the STEP 7 V14-to-V15 upgrade only when you genuinely need permanent V15 PLC editing. Do not buy V15 Basic or Professional for the HMI work itself.

Questions asked

Does a WinCC Comfort V15 floating license authorize WinCC Comfort V14?

Yes. Siemens documents that a purchase of WinCC (TIA Portal) V15 includes a license that is also valid for V14 and V13, so the same floating license activates the installed V14 Comfort component. The license covers downwards only: a V14 license would not authorize V15 engineering.

Why did a STEP 7 Professional V15 trial appear in my license manager?

The WinCC Comfort V15 package installs a time-limited STEP 7 Professional V15 trial alongside the permanent WinCC Comfort floating license. The trial gives you 21 days of PLC editing in V15. When it expires, the WinCC Comfort V15 license still authorizes HMI engineering in V15 and V14, but V15 PLC editing needs its own STEP 7 entitlement.

Can TIA Portal V14 and V15 run on the same PC?

Yes. Each release installs as a separate engineering environment and they coexist on one machine. Open each project copy in the release it belongs to, and keep an untouched V14 backup of any project you also work on in V15, because saving in a newer release moves the project forward.

Why is my KP700 Comfort not listed in TIA Portal V14 Basic?

TIA Portal V14 Basic only shows the panel families it licenses, such as Basic Panels; Comfort Panels need the WinCC Comfort engineering component of the same release. Installing WinCC Comfort V14 adds the Comfort device catalog and HMI editor to your V14 environment, and the V15 floating license activates it.

Do I need STEP 7 Professional V15 to edit the KP700 Comfort panel?

No. Comfort Panel HMI engineering needs a WinCC Comfort license, which your V15 floating license provides for V14 and V15. STEP 7 Professional becomes relevant only if you need V15 PLC engineering functions beyond your V14 Basic license after the trial expires.

Keep reading

  • Troubleshooting

    Why TIA Portal V14 shows only Basic panels under WinCC Basic

    TIA Portal V14 lists no Comfort Panels when the installed engineering scope is WinCC Basic, which supports the Basic Panel family only. Comfort Panels need at least WinCC Comfort, so install that edition first; an HSP then covers a single missing model and never the family-wide gap.

    HMI and touchscreens

  • Explainer

    Which software configures a KP1200 Comfort panel

    A SIMATIC HMI KP1200 Comfort is configured with WinCC Comfort inside TIA Portal, from V11 onward; WinCC flexible 2008 SP3 has no device support for it, so nothing can be created or transferred from flexible. Pick the WinCC Comfort edition or higher, align the project's device version with the panel image, and transfer over the panel's PROFINET interface.

    HMI and touchscreens

  • Explainer

    Why KTP400 Basic Color PN is missing in WinCC flexible

    The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.