Troubleshooting
Why Your HMI Runtime Shows a Demo Mode Message
Short answer
A demo mode banner means an enabled runtime option on the panel has no valid license: install that option's license key or disable the option. The SD card recording failure is a separate storage condition — measure archive growth and fix retention or media instead of clearing records again.
On this page
- What demo mode is telling you
- Work through the two symptoms separately
- Sm@rtService and the OPC server setting are two different checks
- Install the license or disable the option
- Why clearing the card only held for a couple of weeks
- Worked example: sizing archive growth on a card that filled in two weeks
- When recording stops and space is left
- The decision for each symptom
- Questions asked
Your panel is not broken, and the banner is not about the SD card. A demo mode message appears when the runtime checks an enabled option, finds no valid license on the device and drops into demonstration operation; the WinCC documentation gives the exit directly — install the required licenses. The card that refuses new records is a second, independent condition: the archive simply grew back into the space that was freed, which is why clearing it held for about two weeks. Fix the authorization for the banner, size the storage for the card, and diagnose each symptom with its own checks.
What demo mode is telling you #
Demo mode is a license state, not a hardware fault. At startup the runtime checks authorization for every licensed option the project uses, and if a license is missing, the runtime runs in demo mode — the documented behavior for WinCC — until the required licenses are installed. Authorization is per option: the base visualization and each extra function carry their own key, and enabling a function in the engineering project does not supply its license. That is why the banner can appear after a project change with no hardware event: someone switched on a licensed option, or a key that used to be on the panel is no longer readable. Other options behave the same way — WinCC Runtime Advanced logging, for instance, asks for its own license when the runtime starts without it.
Work through the two symptoms separately #
Capture the evidence for each symptom before changing the project or touching the card:
- Read the full banner text, including any option name it prints, and note the runtime diagnostic entries raised at the same moment.
- Compare the named option against the functions enabled in the loaded project; the banner points at the check that failed.
- List the license keys present on the panel with the license management tool, and note any key reported missing or damaged.
- The moment recording stops, record free space, the configured archive destination and the exact storage message — before deleting anything.
- Note how long recording ran after the last cleanup; a repeatable interval points at capacity, not at a random fault.
Sm@rtService and the OPC server setting are two different checks #
In a case like this one, the usual owner of the banner is the remote-service option: Sm@rtService was activated on the panel and there is no license for it, or the key that was there is corrupt. Sm@rtService gives service staff remote access to the panel over the network; the checkbox labelled Act as OPC server exposes process values to OPC client software. Selecting Act as OPC server neither supplies Sm@rtService's authorization nor tests it, so it neither explains the banner away nor rules the license fault out. Treat them as two functions with two authorizations. For each, decide whether the plant actually uses it: if nobody connects for remote service, deactivate Sm@rtService in the project and load the change; if remote access is in daily use, that option needs its license key on the panel. Run the same decision on the OPC function.
Install the license or disable the option #
Both remedies are legitimate; choose by use. The documented transfer route for WinCC panels runs through the Automation License Manager, which moves License Keys to or from the HMI device; the panel needs the key for the specific option enabled in the project. Source the key from entitlement you own or from your distributor. The two conditions need different handling: a key that is missing needs a real entitlement installed, or the unused option deactivated; a key present but corrupt needs the license tool's diagnosis and a re-transfer from the original entitlement. After either change, reload the runtime and confirm the banner stays gone from startup. The mechanics of moving an authorization onto a panel are laid out step by step in how WinCC flexible license authorization transfer to a panel works.
Why clearing the card only held for a couple of weeks #
Deleting records freed space but changed nothing about how fast the archive fills, so the write failure returned on schedule. That interval is itself a measurement: the time from cleanup to the next failure says the archive consumed all usable space in exactly that period. Capture free space and the storage message at the next stop before deleting again — once cleared, the sizing decision below has no inputs to work with.
Worked example: sizing archive growth on a card that filled in two weeks #
The inputs, with their sources:
- Usable space after the last cleanup: 12.0 GB — an example measurement; read your own from the panel's storage page.
- Cleanup to next write failure: 14 days — the fill interval reported in this case, about two weeks.
- History the application must keep: 60 days — an example planning target.
The rule in words: daily growth equals the space the archive consumed divided by the days it ran; required capacity equals daily growth times the history depth that has to survive.
The arithmetic:
- 12.0 GB ÷ 14 days = 0.857 GB/day
- 0.857 GB/day × 60 days = 51.4 GB
- 51.4 GB × 1.1 (a 10 percent margin, an example) = 56.5 GB
Result: at the measured rate, holding 60 days of history needs about 51 GB of usable archive space, or 56.5 GB with the margin.
Decision: if measured daily growth times the required history exceeds usable capacity, deleting records is not a fix — the card stops again on a fixed cycle, two weeks in this case. Choose media whose usable space clears that number, set the archive's rollover so old segments overwrite inside the capacity, or cut the logging rate until growth fits. If recording stops while free space remains, capacity is not the cause; work the media checks below. Measure growth during real production, because alarm bursts, extra archives and file overhead move the rate.
When recording stops and space is left #
Work down this list: that the panel still recognizes the card; that the card is not write-protected; that the filesystem has no errors — a card pulled during a write is the usual way those appear; that the configured archive destination points at the media actually fitted; and that the card type, capacity and formatting follow the panel's documented list. Media rules are model specific, which is what what USB stick size and file system a TP1500 Comfort panel accepts shows for one panel family. Before formatting anything, copy the records worth keeping and close the archive first: pulling a card while the runtime writes to it can corrupt the filesystem and take recent history with it.
The decision for each symptom #
- Demo banner naming an option: match the option to the project, then install its license key through the license tool or deactivate the option and reload; the banner clears when the runtime starts with valid authorization for every enabled function.
- Recording stops with the card full: size the destination so usable space clears measured daily growth times the history you must keep — 56.5 GB in the worked example — or set rollover; until then, deleting only restarts the cycle.
- Recording stops with space free: leave capacity alone and run the media checks — recognition, write protection, filesystem, destination, card type.
- Both symptoms can be true at once, as in the reported case, and they still take two separate fixes.
Questions asked
Can we keep running production while the panel shows demo mode?
Demo mode is a license state, not a hardware fault, and in the reported case the panel kept operating. Treat it as a defect to close anyway: an enabled option is running without valid authorization, so schedule the license installation or disable the option rather than leaving the banner up on a production machine.
How do I see which license keys are actually on the panel?
Use the license management tool that handles License Keys between the engineering PC and the HMI device. It shows the keys present on the target and is where a missing or damaged key gets diagnosed. Compare that list against every licensed option the loaded project enables, because each option is checked on its own.
How do I predict when the SD card will stop again?
Read free space right after a cleanup, run one full production day, and read it again. Space consumed divided by days run is the growth rate; usable capacity divided by that rate is the interval you should expect between cleanups. Measure during normal production, because alarm bursts and extra archives change the rate.
What if the banner names an option nobody remembers enabling?
Open the loaded project and check the option's function setting. Remote-service functions are often switched on during commissioning and simply left enabled. If the plant genuinely never uses the function, disable it and reload the project. If someone does rely on it, install that option's license instead of removing the access it provides.