Replacing an MP277 Touch Panel with a Panel PC
Short answer
A Panel PC 677 can replace an MP277, but as a migration, not a swap: retarget a copy of the project with WinCC flexible Advanced (a Powerpack upgrades an existing Standard license), then buy a PC Runtime license sized to the project's PowerTag count. The engineering license on the development PC does not authorize Runtime on the Panel PC.
On this page
- Why the panel image will not run on the PC
- Bring the engineering edition up to Advanced
- Save the editable project and count the PowerTags
- Change the device type to the PC target
- Worked example: the 12-inch screen against the 10-inch MP277 screen
- License the Runtime on the Panel PC
- Fit the hardware and prove it on the bench
- The decision for each case
- Questions asked
Yes — a SIMATIC Panel PC 677 with a 12-inch touch screen can take over from an MP277 10-inch touch panel, but as a migration, not a swap. The MP277 runs a runtime image compiled for that panel; the 677 is a PC, so the application must be retargeted to a PC target with WinCC flexible Advanced and licensed again. Three items make it work: an Advanced engineering edition (if yours is Standard, the upgrade is a Powerpack license, not a second full package), a PC Runtime license bought separately and sized to the project's PowerTag count, and a mechanical and communication check. Close all three before the old panel leaves the cabinet.
Why the panel image will not run on the PC #
The runtime file on the MP277 was compiled for that device type and executes on the panel's built-in runtime. A Panel PC instead runs WinCC flexible PC Runtime as an application under Windows. No cable or setting translates between the two: the project's device type has to be changed in the engineering software and the project compiled again for the PC. So the job is re-engineer, re-license, refit — in that order, because the last two steps are purchases you cannot size until the first one shows what the project needs.
Bring the engineering edition up to Advanced #
The licensing documentation requires a License Key for the WinCC flexible Compact, Standard and Advanced editions from 2005 onward, and a Standard key does not unlock the Advanced functions the PC target needs.
- On the engineering PC, read which WinCC flexible edition is installed and licensed: Standard or Advanced.
- If it is Advanced, skip to the project steps below.
- If it is Standard, buy the upgrade. Siemens documents Standard-to-Advanced as a Powerpack license — for WinCC flexible 2008 it is explicitly a license upgrade, not a software reinstall — and it builds on the key you already own instead of adding a second full engineering license.
- Prove the upgraded edition by opening a copy of the MP277 project before any downtime is scheduled.
Save the editable project and count the PowerTags #
The retarget needs the editable engineering project. A backup file that restores the MP277 is not necessarily one — confirm the engineering software actually opens what you have. If nothing editable survives, there is nothing to convert and the screens must be rebuilt; that path is replacing an old HMI when no project files exist.
Then record the number the Runtime license will be sized by: open the project's information in the engineering tool and write down the PowerTag count, and re-read it after the device change, since the converted project is the one that must fit under the license. What a PowerTag is and how it is licensed is covered in how WinCC defines and licenses PowerTags.
Change the device type to the PC target #
Work on a copy and keep an untouched archive of the original.
- In WinCC flexible Advanced, use the device change function to move the project from the MP277 device to the PC target.
- Work through the conversion messages one by one. A function tied to the old panel hardware may have no PC equivalent; fix the object it names rather than deleting the feature just to get a clean compile.
- Recheck everything with a path or a driver in it — controller connections, scripts, alarms, recipes, archives, file destinations — because storage and communication on a PC differ from the panel's.
- Compile until no errors remain, generate the runtime file for the PC, and start it on the Panel PC; the workflow from there is running a WinCC flexible 2008 project in PC Runtime.
Worked example: the 12-inch screen against the 10-inch MP277 screen #
Inputs #
- Old display diagonal: 10 in, the MP277 being replaced.
- New display diagonal: 12 in, the proposed Panel PC 677.
- Assumption: both screens have the same aspect ratio; neither figure here fixes it, and the area ratio below holds only under that assumption.
Rule #
For two screens of the same shape, the area scales with the square of the diagonal, while the diagonal itself scales linearly.
Arithmetic #
- Diagonal ratio: 12 in ÷ 10 in = 1.20, so the diagonal grows by 20%.
- Area ratio: (12 ÷ 10)² = 1.44, so the new screen carries 44% more area.
Result #
The new display offers 1.44 times the area of the old one.
Decision #
A 44% area difference is far beyond what the automatic screen adaptation absorbs cleanly, so treat the display change as a layout task: after the device change, open every screen at the PC's target resolution and repair stretched graphics, clipped text and controls that fell off the visible area before anything is transferred. If a screen needs more than repositioning, rebuild that screen at the new resolution instead of nudging objects.
License the Runtime on the Panel PC #
The engineering license on the development PC authorizes engineering, not execution. If a runtime license was delivered with the Panel PC, its PowerTag capacity still has to cover the count you wrote down; if the 677 arrived as bare hardware, the license is a separate purchase. For bench proof only, the licensing documentation lists a trial License Key that expires after 21 days — never leave it as the license the machine depends on.
- Where needed, buy the WinCC flexible Runtime license for the PC target with PowerTag capacity at or above that count.
- Transfer the key to the Panel PC using the vendor's licensing procedure.
- Open the Automation License Manager, highlight the Panel PC and confirm the key is listed on that device, not only on the engineering computer.
- Transfer the generated runtime file and start the application.
If the installed key's capacity sits below the project's PowerTag count, the runtime raises a PowerTag licensing error instead of running; the diagnosis for that stop is resolving WinCC flexible 2007 PowerTag licensing errors.
Fit the hardware and prove it on the bench #
A display diagonal is not a mounting dimension. Compare the installation drawings of both units — cut-out, mounting depth, clearance, supply voltage, connector positions — before the old panel comes out, and confirm the Panel PC has the physical interface the existing controller connection uses, because a shared software family does not guarantee matching ports. Check the actual unit against the release note's hardware: 256 MB of RAM as standard, second-generation Intel Pentium M processors on the Mobile Intel 915GM Express chipset, and operating front sizes extending to 19 inches — then verify that memory and operating system against the requirements of the Runtime version you intend to run. If the replacement ends up being a different PC-based unit rather than a 677, the retargeting and license steps above apply unchanged to other industrial panel PCs running the same PC Runtime.
Prove the result before the machine depends on it: run the converted application first with verified test tags, then confirm the intended project starts automatically when the Panel PC boots and comes back after a restart without exposing the desktop to operators — the full method is how to prove a PC-based HMI before replacing panel terminals. Run the very first start with the machine in a safe state, because this project has never controlled this machine.
The decision for each case #
- You already own WinCC flexible Advanced: retarget a copy, buy the Runtime license sized to the converted PowerTag count, and migrate — the 677 is a valid replacement for the MP277.
- You own Standard: add the Standard-to-Advanced Powerpack first; every other step is unchanged.
- No editable project survives: budget the screen rebuild before any hardware order, because there is nothing to retarget.
- The converted count lands above the license you planned: buy the larger license now, since an undersized key only moves the stop to the first runtime start.
Questions asked
How long can a trial license run the converted project?
The WinCC licensing documentation lists a trial License Key that is for testing only and expires after 21 days. Use it to prove the converted PC project on the bench, but have the purchased engineering and Runtime keys installed before the machine depends on the application.
What hardware did the Panel PC 677 ship with?
The Panel PC 677 release note lists 256 MB of RAM as standard, second-generation Intel Pentium M processors on the Mobile Intel 915GM Express chipset, and operating front sizes extending to 19 inches. Check the actual unit's memory and operating system against the requirements of the Runtime version you intend to run on it.
What exactly is a PowerTag when sizing the Runtime license?
A PowerTag is a process tag that the Runtime licensing rules count. Take the number from the converted project's information in the engineering tool, not from the total rows in the tag editor, the number of screens or the number of touch objects, because none of those set the license size.