IMDTouchKnowledge BaseShop main store

Explainer

Reusing HMI Screens Across Different PLC Projects

HMI and touchscreens Published 8 min read

Short answer

You do not need to write a screen generator. Keep one master HMI application, repoint its PLC connection when the next machine uses the same address map, remap tag addresses centrally in the tag editor when it does not, and standardize the PLC-to-HMI interface with option bits so each machine shows only the screens for the options actually installed.

On this page
  1. Why a screen generator is the wrong first project
  2. Match the editor to the terminal family first
  3. Compare the PLC interface before touching a screen
  4. Repoint the connection when the address map matches
  5. Remap tags in the tag editor when addresses differ
  6. Standardize the interface with option bits
  7. Example: masking screens for a machine that calls 20 of 50
  8. Deploy the copy and prove it on the bench
  9. The decision, case by case
  10. Questions asked

You do not need to write a program that generates HMI screens to speed up similar jobs. Keep one master application and reuse it three ways: repoint its PLC connection when the next machine uses the same address map, remap tag addresses centrally in the tag editor when it does not, and standardize the PLC-to-HMI interface with option bits so one common application hides or reveals screens per machine. A generator only automates decisions you still have to make — the interface between controller and panel — and it adds a second tool to maintain. This article walks the editor-based workflow, the interface standard that makes one application serve a whole machine family, and the decision for each job-to-job case.

Why a screen generator is the wrong first project #

An external generator has to produce a project file that the panel's editor accepts and that downloads cleanly to the terminal. Unless the vendor documents an import or automation interface, that means reverse-engineering a proprietary format that changes between editor versions, so the utility becomes a second tool you maintain forever. None of the documented PanelView tooling takes general-purpose code in place of the editor: the editors, the documented transfer utilities and the documented migration paths are the supported surface.

The generator also does not remove the real work. Before any screen exists, someone decides what the panel reads, what it writes, how commands are handed over and which options exist. That PLC-to-HMI interface is the reusable asset. Build a generator only after that interface is stable and a documented generation or import route exists; automating an unstable mapping reproduces errors faster.

Match the editor to the terminal family first #

"PanelView" alone does not pick the tool, and the engineering tool, the target model and the firmware are separate checks. PanelView Standard terminals run applications built in PanelBuilder — PanelBuilder 32 on the later Standard models. PanelView Plus uses FactoryTalk View Studio for Machine Edition, PanelView 5000 uses Studio 5000 View Designer, and PanelView 800 uses Connected Components Workbench. Rockwell also documents conversion paths between families, such as moving a PanelView Standard application onto a PanelView Plus terminal, or a PanelBuilder 1400e application into FactoryTalk View ME, and older families document their own transfer utilities, such as the PanelView 1200 Transfer Utility.

Terminal family Engineering tool What reuse looks like
PanelView Standard PanelBuilder, PanelBuilder 32 Copy the application, repoint the connection or remap tags in the tag editor
PanelView Plus FactoryTalk View Studio for Machine Edition Edit the project, or convert a legacy PanelBuilder application by the documented migration
PanelView 5000 Studio 5000 View Designer Rebuild in View Designer or follow the documented migration path
PanelView 800 Connected Components Workbench Edit in the tool the project was built in

If all you have is the deployed application on the terminal, establish the documented upload or transfer path for that family before planning any automated edit. Without an editable project, none of the reuse moves below exist.

Compare the PLC interface before touching a screen #

Take the tag list from the working application and lay it against the next job's PLC. Check five things, not just tag names: the address, the data type, the scaling and units, the command handshake — momentary pulse or maintained bit — and what each status value means. A numeric entry can communicate correctly and still write the wrong engineering quantity, and a button on a valid bit misbehaves if one machine latches commands while the next expects a pulse.

That comparison sorts every job into one of four cases:

Job-to-job situation What it means What you do
Same addresses and meanings, different controller Only the connection is job-specific Copy the master, repoint the connection, keep tags and screens
Same meanings, different addresses Objects reference job-specific mappings Remap in the tag editor, verify each affected object
Same addresses, different meanings The interface is not actually common Fix the interface definition before reusing anything
Machines differ by installed options One common application needs per-machine masking Option bits decide which screens each machine sees

Repoint the connection when the address map matches #

This is the cheap case and it is the one that pays first. Save the master under a job-specific name — never edit the master itself — change the copy's communication configuration to the new controller, then run validation. Every screen, tag name and alarm keeps working because nothing about the data moved.

If your jobs share a PLC family, standardize the address map once so every new job is a copy, a repoint and a download.

Remap tags in the tag editor when addresses differ #

When the next machine uses different addresses, edit mappings in the tag editor instead of opening screen objects one at a time. Objects reference tags, so the screens stay intact while the tag editor absorbs the new addressing; editing objects directly is slower and breaks the reuse you are trying to keep. For each changed tag, re-check data type and scaling — a correct address with the wrong type passes a connection test and corrupts values in service. Keep a job mapping worksheet, one row per tag with name, address, type and scaling; that worksheet, not a code utility, is what keeps the edits consistent. The guide on reusing a PanelView HMI file with a different PLC walks this tag-migration case step by step.

Standardize the interface with option bits #

When machines in a family differ mainly by installed options, stop editing the application per job. Write down the functions common to every machine, group the parameters that travel together, and for each exposed value record: its operator-facing purpose and PLC location; its data type, units, scaling and valid range; whether the panel reads it, writes it or both; for commands, how the PLC accepts, acts on and clears the request; and which option makes it applicable.

Then build one common application containing every option's screens and let the PLC decide what the operator sees. The PLC holds a bit for each installed option, and screen calling or visibility is conditioned on those bits, so a panel can carry the whole family while each machine exposes only what it has. The PLC-calls-screens pattern is not PanelView-specific: changing WinCC Flexible screens from the PLC is the same idea in another ecosystem. For a worked version of one application serving many machines, see how one spare HMI panel covers seven machines.

One limit belongs here: hiding a screen or a button is operator convenience, not a machine safety function. The PLC must reject, in logic, any command the installed equipment cannot accept, and hard safety functions stay independent of HMI visibility and navigation.

Example: masking screens for a machine that calls 20 of 50 #

Inputs: the case is a machine family built from one common application that holds 50 screens, with every option programmed; the machine in front of you installs the options covered by 20 of those screens; the PLC selects screens by writing a screen-number value. These figures describe an application organization for this kind of family, not a capacity rating of any terminal.

Rule: the selection value must span every screen the application contains, and per-machine visibility comes from the option bits, not from separate applications.

Arithmetic: screens never called on this machine: 50 − 20 = 30. Selection width: the value must reach index 49; 2^5 = 32, which is below 50, and 2^6 = 64, which covers it, so a 6-bit screen-number value spans the application. What moves the width: past 64 screens the same value needs 7 bits, because 2^7 = 128.

Result: one 6-bit selection value, with 30 screens masked per machine by option bits.

Decision: when a machine calls 20 of a 50-screen master, a 6-bit screen-number range plus option bits replaces per-machine applications entirely — build the master once, commission each machine by setting its installed-option bits, and the screens for absent options never open. If a job's screens differ in meaning rather than in presence, no bit count fixes it; correct the interface definition first.

Deploy the copy and prove it on the bench #

Make the smallest change the branch allows: copy the master, set the connection, adjust only the mappings or option configuration the job needs, and run the editor's validation to catch invalid references before anything ships. Deploy through the documented transfer method for that terminal family.

Then prove the result on an isolated bench rather than a running line: verified test tags in a test controller project, a real write from every control, a cable pull to watch how the panel reports data quality, and a restart to confirm it comes back on the right screen. A final counter value shows the panel caught every event; timestamped intermediate readings show how long updates actually took. Treat the pass limits you set as your own example values — they are not vendor ratings.

The decision, case by case #

  • Same address map, new controller: copy the master, repoint the connection, keep every tag — one dialog and a validation pass.
  • Different addresses, same meanings: remap in the tag editor, verify type and scaling per tag, keep the worksheet current.
  • Same addresses, different meanings: stop; correct the interface definition first, then reuse.
  • Machines differ by installed options: build the option-bit master and commission each machine by setting bits, not by editing screens.
  • Only a deployed application in hand: recover or upload by the documented path for that family, or plan a rebuild in its own editor, before any automation.

No branch ends at a screen generator. The interface definition is the asset, the family's editor is the tool, and the option bits are what let one application serve the whole machine family.

Questions asked

Can one HMI panel talk to two different PLCs at once?

Yes, when the panel's documented drivers, ports and connection limits support both controllers on that terminal or runtime; count operator stations by the job each one needs to do. Screen reuse is about the interface, simultaneous connections about the driver list and connection budget. Verify both in the documentation for the exact panel before promising a combined station.

How should I manage the master application and its job copies?

Store the master read-only or under version control, name each copy with the job and the date, and record which master version every deployed copy came from. A field fault on one machine then traces to the exact master it was built from, and a fix propagates by re-copying and redeploying instead of by hunting through per-job edits.

Do option bits survive a PLC program revision?

Only if the revised program keeps those bits at the same addresses with the same meanings. Treat the option-bit map as part of the PLC-to-HMI interface: when a program change moves or repurposes a bit, update the interface document and re-verify screen calling and visibility on a bench before the machine ships.

What proves a remapped tag before startup?

Write a known value from the panel to a test address and read it back in the PLC, then force a value in the PLC and watch the panel display update. Run both directions for every remapped tag on an isolated bench with verified test tags, because a wrong scaling factor or data type passes offline validation and corrupts values in service.

Does screen reuse change when the machines use different PLC brands?

The workflow stays the same, but the file does not carry over. One HMI editor builds for one target family, so a different PLC brand usually means a rebuild in a different HMI tool against the same standardized interface. Keep the interface document with addresses, data types, scaling, handshakes and option bits, and the rebuild becomes re-entry work, not a redesign.

Keep reading

  • Troubleshooting

    HMI Screen Goes Blank for Seconds Then Recovers

    A blank of a few seconds that recovers on its own, and survives a project reload, points first at a PLC-controlled backlight, screen-saver or visibility tag being overwritten at runtime. Separate backlight loss from a panel restart by checking the rear status LEDs and tracing the tags the Reset action writes before swapping hardware.

    HMI and touchscreens

  • How-to

    Where to Set HMI Project Version and Author in Vijeo Designer

    Vijeo Designer has no equivalent of Machine Expert's Project Information option, and opening both projects together transfers nothing: the HMI shows PLC metadata only if the PLC writes it into variables. Put the HMI release designation and author on a dedicated information screen as fixed text, archive the source under the same number, and read the screen back on the panel after every download.

    HMI and touchscreens

  • How-to

    How to Convert a WinCC Project From 1024x768 to 800x600

    WinCC has no tool that converts an existing 1024x768 project to 800x600 automatically: you set the smaller picture size, then move and resize objects screen by screen. Because both resolutions are 4:3, the runtime adapt option scales everything uniformly to 78.125% with no distortion - usable as an interim display, but do the manual relayout for a permanent station.

    HMI and touchscreens