IMDTouchKnowledge BaseShop main store

Selection guide

Selecting a Compact HMI for ControlLogix Over Ethernet

HMI and touchscreens Published 7 min read

Short answer

Select a compact HMI only by a documented ControlLogix tag-based EtherNet/IP client driver plus its matched software and firmware set: the C-More CM5-T4W documents ControlLogix through 1756-ENBT or 1756-ENET/B bridges with CM5-PGMSW 8.0 or later, and PanelView 5310 terminal firmware from the same release pairs with View Designer 8.01.00 and needs Logix firmware 27 or later. CompactLogix-only support, such as the PanelView 800 documented list, disqualifies a terminal for this station.

On this page
  1. The driver test that qualifies or disqualifies a terminal
  2. Documented compact candidates compared
  3. Buy a matched set, not a terminal
  4. Worked example: one offload station
  5. Commission the connection before the screens
  6. When both compact gates fail
  7. The decision, case by case
  8. Questions asked

Pick the terminal by its documented ControlLogix tag driver and the software and firmware set that driver is matched to, not by screen size or purchase price. Two compact paths document that match today: the AutomationDirect C-More CM5-T4W, whose cut sheet lists an Allen-Bradley EtherNet/IP Client tag-based driver covering ControlLogix and requires CM5-PGMSW version 8.0 or later, and the Allen-Bradley PanelView 5310, whose matched terminal firmware in the View Designer 8.01.00 release requires Logix controller firmware 27 or later. A terminal whose supported list names CompactLogix or Micro800 only, such as the PanelView 800, is disqualified for a ControlLogix station at any screen size.

The driver test that qualifies or disqualifies a terminal #

An RJ45 jack proves a network, not a controller. What reads a ControlLogix tag is a client driver inside the HMI, and on third-party terminals that driver carries a supported-controller list. Beijer Electronics documents the architecture of its Allen-Bradley Ethernet/IP driver, version 4.32, in one line of intent: the HMI's Ethernet/IP driver acts as the master and the controller serves the data. If a candidate's list names CompactLogix and Micro800 with no ControlLogix entry, the terminal cannot serve this station.

Insist on a tag-based client. A tag-based driver reads named controller tags, so the display shows the same inhibit bit the pump logic evaluates, and a driver that imports the controller's tag database beats one that makes you type every address by hand. When a package offers no driver for your controller at all, when the HMI software has no driver for your PLC covers the legitimate workarounds.

CompactLogix-only support is a hard stop. The PanelView 800's supported Logix section names selected CompactLogix 5370 and 5380 controllers and no ControlLogix models, so it fails this application on the driver test alone, before price or screen size enter the comparison.

Documented compact candidates compared #

Two compact terminals document a ControlLogix tag path with a named software set; everything else in the small-panel field has to prove it model by model.

Terminal or route Documented ControlLogix fit Matched software and firmware Consequence
C-More CM5-T4W Allen-Bradley EtherNet/IP Client, tag-based; included ControlLogix setups bridge through 1756-ENBT or 1756-ENET/B CM5-PGMSW 8.0 or later; one 10/100Base-T port Committed compact pick when the chassis bridge matches
PanelView 5310, 6-inch 2713P-T6CD1 Logix controllers at firmware 27 and later, with the matched terminal firmware from the View Designer 8.01.00 release Studio 5000 View Designer 8.01.00; 100 user-defined screens; up to 4,000 Logix-based alarms; one Ethernet port Rockwell-native pick; the gate is controller firmware, not the bridge
PanelView 800 Supported Logix section lists selected CompactLogix 5370/5380 only Firmware 5.011 and later: 50 screens, 400 tags, 400 alarms Disqualified for ControlLogix at any capacity
Beijer panels, Allen-Bradley Ethernet/IP driver v4.32 Allen-Bradley EtherNet/IP controllers; the HMI acts as master iX project built on the documented driver version Confirm ControlLogix on the exact supported list before ordering
Red Lion Kadet, Maple Systems, C-more Micro Not verified here Depends on model Maybe list until current documentation names ControlLogix for the exact model
Panel PC with an OPC server ControlLogix, CompactLogix, SLC 500, PLC-5 and MicroLogix over EtherNet/IP PC runtime plus OPC client, no RSLinx Fallback when both compact gates fail

The PanelView 5310 is programmed in Studio 5000 View Designer, not FactoryTalk View Machine Edition, so an existing Machine Edition application does not transfer to it; which HMI software works with which HMI panel hardware maps those pairings by manufacturer. Kadet, Maple Systems and C-more Micro panels stay on the maybe list until the exact model's current documentation names ControlLogix.

Buy a matched set, not a terminal #

The purchase unit is five items, not one: terminal model, terminal firmware, engineering software and version, controller model, controller firmware revision. Write all five on the check sheet before anyone quotes. For the CM5-T4W the documented requirements are CM5-PGMSW version 8.0 or later and, for ControlLogix, a chassis bridged by 1756-ENBT or 1756-ENET/B, which is what the C-More help's included-models list covers. For the PanelView 5310 the chain is View Designer 8.01.00 with the terminal firmware matched to that release, and the Rockwell release note restricts that combination to Logix controller firmware 27 and later. If the controller side needs a change to meet a gate, settle it through the plant's change process before the HMI order, because the terminal is worthless without it.

Worked example: one offload station #

The station in this example is illustrative: two offload pumps, hardwired start and stop already in place, and a display that only has to show inhibit status, blocking alarms and connection health.

Check 1: the point budget #

Count what the operator must distinguish: a pump permitted to run, a pump actually running, and a display that has lost its connection. Two pumps give two inhibit-result tags and two running-feedback tags, the alarm list holds twelve individual blocking conditions, and the driver's connection status adds one more: 2 + 2 + 12 + 1 = 17 tags.

Against the PanelView 800's documented 400-tag limit that is 17 / 400 = 0.0425, or 4.25 percent, and it is irrelevant because the driver test already failed that terminal. Against the PanelView 5310's documented 4,000 Logix-based alarms, twelve conditions is 12 / 4,000 = 0.003, or 0.3 percent. At this scale capacity never decides the purchase; the driver and firmware set does.

Check 2: the firmware chain #

Give the example station a 1756-L73 at firmware revision 24.11 in a chassis bridged by a 1756-EN2T. The PanelView 5310 gate is controller firmware 27: 27.00 - 24.11 = 2.89, so the controller is 2.89 revisions below the requirement and the 5310 will not connect as installed. The CM5 gate is the bridge module: its included-models list documents 1756-ENBT and 1756-ENET/B for ControlLogix, a 1756-EN2T is not on it, and that path stays unverified for this chassis until the driver help for the CM5-PGMSW version you will run names the module.

The decision for this example: flash the 1756-L73 to revision 27 or later through the plant change process and install the PanelView 5310 with View Designer 8.01.00. One asset changes instead of two, and the 5310 does not gate on the bridge module. Had the same chassis been bridged by a 1756-ENBT, the CM5-T4W would be the pick instead, because its documented gates, software version and bridge module, would both already be met.

Commission the connection before the screens #

Both compact picks carry a single Ethernet port, so budget one free switch port on the controller network, then prove the path before building objects:

  1. Give the HMI a unique IP address, subnet mask and gateway, and confirm no other device holds that address; a duplicate address produces exactly the class of fault described in why a PC fails to reach an HMI when Wi-Fi owns its address.
  2. Select the tag-based EtherNet/IP client driver, point it at the controller, and enter any routing the chassis layout requires.
  3. Read one known, non-command status value, the inhibit result of pump 1, and compare it with an online watch of the same tag in the controller.
  4. Read the final inhibit result the pump logic already computes instead of rebuilding permissive logic in the HMI, where a second implementation can drift from the controller after the next program change. Show the individual blocking causes beside the final result so an operator can explain an inhibited pump without opening the program.

Keep every object read-only: the hardwired start and stop circuits are the operating authority at the station, and any command button added later needs its own review of authority, permissives and interaction with those circuits before it is enabled.

When both compact gates fail #

If the controller is pinned below revision 27 and the bridge is outside the CM5 list, the terminal route dead-ends without a change to the control system, and the committed fallback is PC-based visualization: industrial panel PCs run the HMI runtime at the machine while an OPC server does the protocol work, and drivers of the TOP Server class document ControlLogix, CompactLogix, SLC 500, PLC-5 and MicroLogix over EtherNet/IP without RSLinx. On that route, FactoryTalk Optix's RA EtherNet/IP driver imports tags in online and offline modes and accepts both L5X and ACD project files, which turns the 17-tag station into a tag import rather than a typing exercise.

The decision, case by case #

  • Chassis bridged by 1756-ENBT or 1756-ENET/B and the software version under your control: the C-More CM5-T4W with CM5-PGMSW 8.0 or later is the committed pick.
  • Studio 5000 shop with the controller at firmware 27 or later, or flashable through the change process: the PanelView 5310 2713P-T6CD1 with View Designer 8.01.00.
  • Controller pinned below revision 27 and a newer bridge such as 1756-EN2T: make the smaller change, the controller flash, and use the PanelView 5310, or move the station to the panel PC route.
  • Any terminal whose supported list names CompactLogix or Micro800 only: disqualified, whatever its price.

Ranking these candidates by purchase price alone inverts that order, because the engineering software and any forced controller change dominate the real cost of the station; the same argument is made for which automation upgrades beat the lowest purchase price across automation projects.

Questions asked

Does an Ethernet port on the HMI mean it can talk to a ControlLogix?

No. EtherNet/IP is only the network. Tag access comes from a client driver inside the HMI, and that driver carries a supported-controller list. Many compact terminals ship with generic Modbus TCP or with an EtherNet/IP driver scoped to CompactLogix and Micro800 controllers. The purchase test is that list, not the RJ45 jack: no ControlLogix line, no order.

Our chassis uses a 1756-EN2T bridge. Does the C-More tag-based driver still work?

The C-More help for the tag-based client lists ControlLogix with 1756-ENBT and 1756-ENET/B bridges, plus CompactLogix with built-in EtherNet/IP. A 1756-EN2T is not on that list, so treat the path as unverified for that chassis until the driver help for your software version confirms the module. In that situation the PanelView 5310 is the committed pick, because its documented gate is controller firmware 27 or later, not the bridge.

Can a firmware update extend a PanelView 800 to ControlLogix?

No. Firmware 5.011 and later raises the PanelView 800 limits to 50 screens, 400 tags and 400 alarms, but capacity never extends the supported-controller list, which names selected CompactLogix 5370 and 5380 models. No firmware revision adds ControlLogix to that terminal, so it stays disqualified for this station at any tag count.

Is it safe to add pump start commands to this display later?

Keep it read-only. The hardwired start and stop circuits are the operating authority at the station, and the display should not be able to override them. Any command object added later needs its own review of operating authority, permissives and interaction with those circuits before it is enabled on a running machine.

How many tags does a pump-status station like this actually need?

The example station needs 17 tags: two pump inhibit results, two running feedbacks, twelve blocking alarm conditions and one connection-status variable. That is 0.3 percent of the PanelView 5310 documented 4,000-alarm capacity and 4.25 percent of the PanelView 800 400-tag limit. Capacity never decides at this scale; the driver and firmware set does.

Keep reading

  • Troubleshooting

    Connecting a CompactLogix PLC to an HMI over EtherNet/IP

    A CIP transport unsupported fault on a Generic Ethernet/IP module in a CompactLogix project means the connection was built the wrong way around. For HMI tag access, delete the module, select the panel's Rockwell PLC driver, point it at the controller IP, and rebuild the tags — no assembly instances, I/O sizes, or EDS file.

    HMI and touchscreens

  • How-to

    Replacing a Fleet of PanelView 550 Terminals on DH-485

    There is no direct swap: the PanelView 550 is Silver Series, so each terminal is a migration. The PanelView Plus 6 600 keeps the 550 cutout but needs a third-party DH-485 adapter; a Plus 6 700 takes the 2711P-RN6 but modifies the cutout. Audit all 25 catalog numbers, convert one application in FactoryTalk View Studio ME, pilot one machine, then buy the fleet.

    HMI and touchscreens

  • How-to

    Connecting an HMI to a GE Fanuc PLC Over Ethernet SRTP

    Yes. GE controllers speak SRTP, their native Ethernet protocol, on TCP port 18245, and the HMI editor's built-in GE Fanuc SRTP driver needs no Modbus TCP and no purchased add-on. VersaMax CPUs with integrated Ethernet serve SRTP only, and a Series 90-30 needs CPU firmware 8.xx before its IC693CMM321 Ethernet module will cooperate.

    HMI and touchscreens