IMDTouchKnowledge BaseShop main store

How-to

Set an Idle Screen Timeout That Returns to the Main Page

HMI and touchscreens Published 7 min read

Short answer

The EA9 has no screen-timeout setting: build the idle return from the panel's user-inactivity system tags. Set an Event Manager event on the inactive-minute count with the limits changed to equals and a Screen Change action to the main page, or let an on-delay timer in the PLC write the home screen number to the change-screen command word. Pick the PLC route when the period must be adjustable or bypassed at runtime.

On this page
  1. Does the EA9 have a built-in screen timeout setting?
  2. Which user-inactivity system tags does the panel publish?
  3. How do you build the timeout with an Event Manager event?
  4. Example: how fast does a five-minute idle send the panel home?
  5. When is the timeout better placed in the PLC?
  6. How do you stop the timeout from fighting a technician?
  7. What bench test proves the idle return before install?
  8. Questions asked

A C-More EA9 panel has no screen-timeout setting to switch on: nothing in the project sends an idle display back to the main page by itself. You build that idle return from the panel's built-in user-inactivity counters, and two designs work. Inside the panel, an Event Manager event on the inactive-minute count with the limits changed to equals drives a Screen Change action to the main page. In the PLC, the same counters reset an on-delay timer whose done bit writes the home screen number to the change-screen command word. Pick the event when the period is fixed and you want no PLC changes; pick the PLC timer when maintenance must adjust or bypass the period at runtime.

Does the EA9 have a built-in screen timeout setting? #

No — the EA9 has no built-in idle-timeout parameter: what the panel gives you is the raw material, three user-inactivity counters, a current-screen status word and a change-screen command word, and you assemble the return to the main page from those pieces.

The counters sit in the built-in system tag list — you select them from it, you do not create them. The same list carries the screen words the PLC route needs. From those primitives the choice is simple: the Event Manager event changes screens entirely inside the project, with the period fixed at download time, while the PLC route trades a few tags and a timer for a preset maintenance can tune live. Everything below builds both, and each route ends with the test that proves it before the panel reaches the floor.

Which user-inactivity system tags does the panel publish? #

Three built-in counters — an hour count, a minute count and a second count — measure the time since the screen was last touched; the tag list names the minute tag SYS USER INACTIVE MIN COUNT, and any touch zeroes all three.

The documentation describes the hour counter simply as the number of hours since the screen was touched, and the minute and second counters behave the same way at their own scale: zero right after a touch, climbing while nobody touches the panel. Select each one from the system tag list in the tag database and map it to the controller address your logic uses — and map only the ones in use, because every mapped tag adds traffic to the driver scan.

How do you build the timeout with an Event Manager event? #

Set the trigger on the inactive-minute count with the comparison limits changed to equals, enter the timeout in minutes, then swap the default alarm action for a Screen Change action pointed at Other Screen and your main page.

  1. Open the project and, in the programming software's Navigation window, select the Function tab and double-click Alarm Action to open the Event Manager Database.
  2. Add a new event.
  3. Select the trigger tag from the built-in system tag list: SYS USER INACTIVE MIN COUNT for a minutes-based timeout.
  4. Change the trigger limits to the equals comparison.
  5. Enter the timeout in minutes — 5 for a five-minute return.
  6. Add a Screen Change action, choose Other Screen, and pick the main page.
  7. Delete the auto-created Alarm action; this event should navigate silently. An alarm entry on every idle-out puts a banner over the screen you just tried to clear — the same crowding covered in working around the C-more EA9 alarm banner covering buttons.
  8. Save and download the project to the panel.

Equals is the whole trick:

Comparison limits Behavior at and past the target Result
= True for the single update that reaches the target, false afterward One clean screen change — use this
> Stays true from one step past the target onward The screen change re-fires on every update
>= Stays true from the target onward Same repeat-firing, one step sooner

Because any touch zeroes the counters, the event re-arms itself: after the return to the main page it waits a full period again before firing. One caution before this goes to production: field reports have singled out release 6.70 of the programming software, so prove the event on a bench panel running your exact software and firmware pair and keep the last known-good project file before any download.

Example: how fast does a five-minute idle send the panel home? #

Five minutes of idling is 300 seconds of waiting: the last touch lands at 13:58:12, the inactive-minute count steps 1, 2, 3, 4, 5, and the event fires at the count of 5 — 13:58:12 plus 300 seconds — landing the panel on the main page at 14:03:12.

The arithmetic, laid out: 5 minutes × 60 seconds/minute = 300 seconds of idling, and 13:58:12 plus 300 seconds is 14:03:12, which is when the main page appears. Now suppose the operator comes back and touches the panel at 14:01:47 — every counter zeroes at that instant and the wait restarts, so the return moves to 14:01:47 plus 300 seconds, which is 14:06:47. The touch is the cancel: nothing needs disabling, and the event simply re-arms.

When is the timeout better placed in the PLC? #

Move the logic into the PLC when the preset must change at runtime or maintenance needs a bypass: tie the inactivity count to a tag, use it to reset an on-delay timer, and write the home screen number to the change-screen command word when the timer finishes.

Map three tags and the logic writes itself:

Panel tag Direction Job in the logic
Inactive second count Panel to PLC A reading of zero means a fresh touch — the timer's reset
Current-screen status word Panel to PLC Suppress the timeout while the main page is already up
Change-screen command word PLC to panel Write the home screen number here to force navigation

The logic reads like this in structured text; every name below is illustrative, so map each one to the real tag or address in your project:

// Illustrative names — map each to your panel's tags and your PLC addresses
inact_sec  : INT  := 0      // inactive second count, panel to PLC
cur_screen : INT  := 0      // current-screen status word, panel to PLC
screen_cmd : INT  := 0      // change-screen command word, PLC to panel
HOME       : INT  := 1      // main-page screen number in your project
preset_s   : INT  := 300    // idle timeout, seconds
bypass     : BOOL := FALSE  // maintenance keyswitch or login level
armed      : BOOL := FALSE  // latch for a one-time command write

activity := (inact_sec = 0)              // a touch zeroes the count
enable   := NOT activity AND NOT bypass
            AND (cur_screen <> HOME)     // nothing to do on the main page
TON_idle(IN := enable, PT := preset_s)   // on-delay, preset in seconds

IF TON_idle.Q AND NOT armed THEN
    screen_cmd := HOME                   // deliver the command once
    armed := TRUE
END_IF
IF activity THEN armed := FALSE END_IF   // re-arm on the next touch

Three details separate a working timeout from one that fights you. Reset on the level, not the edge: a zero on the inactivity count is a state, so NOT(activity) as the enable means any touch drops the enable and the accumulator clears itself. Deliver the command word once: a command word rewritten on every scan while the timer stays done pins the operator to the main page, which is the once-only discipline used for one-shot on-delay timers with pause-resume logic. And the whole shape — enable while the condition holds, act once when the timer completes — is the same pattern that runs an on-delay timer that transfers motor operation after a fixed wait.

Prove the route on the bench: preset the timer to 10 seconds, touch the panel, wait, and confirm exactly one write to the command word and one return to the main page; touch again mid-wait and confirm the accumulator clears to zero.

How do you stop the timeout from fighting a technician? #

Gate it before you deploy: a commissioning bypass bit for maintenance work and a suppression on every screen that hosts numeric entry, setpoint edits or jog controls, both built from things you already have — the current-screen status word for suppression and a spare bit for the bypass.

A forced navigation that lands during a setpoint edit or a manual jog is a process upset waiting to happen, so treat these gates as part of the design. The bypass ANDs a maintenance keyswitch bit or a login level into the enable, dropping the whole feature while a technician works and restoring it when the bit drops. Suppression costs nothing extra: the current-screen status word is already mapped for the main-page gate, so hold the timeout off on each screen number that hosts entry fields or manual controls and let it run everywhere else. Ship neither design without both gates in place.

What bench test proves the idle return before install? #

Prove the whole chain on the bench with a short preset before it touches the machine: confirm the counts move, the event or timer fires exactly once, a touch cancels the pending return, and the panel lands on the main page.

  • Watch the inactive-minute tag in monitor mode: it should step one count per minute and reset the moment you touch the screen.
  • Run the test at a 1-minute preset rather than the production value; what you are proving is firing, canceling and re-arming, not the period.
  • Confirm exactly one screen change per idle period — no repeat-firing while the condition holds.
  • Touch the panel mid-wait and confirm the pending return cancels and the full period restarts.
  • After the return, navigate away and let the full period elapse again to confirm the event or timer re-arms.

When all five observations hold, the design is ready for the production preset and the floor.

Questions asked

What changes when the timeout needs to be longer than 59 minutes?

The minute and hour counters are separate counts, not one running total, so do not rely on the minute value alone past 59. Drive the comparison from the hour count with the minute count as the trim, and prove that pairing on your firmware with a short preset before you trust it in production.

Can the idle return fire in less than a minute?

Yes — build the event on the inactive second count instead of the minute count, since the minute tag only steps in whole minutes. A 20-second return is the seconds counter with the comparison set to equals 20. Bench-test a seconds-based event before production, because a fast counter is easier for the runtime scan to step over.

Does activity on the PLC side reset the idle counter?

No. The counters measure touches on the panel screen itself, so PLC writes, alarms and background communication never reset them. Size the preset for an operator who reads without touching — someone transcribing values to a sheet — because the panel will still send them home while they are mid-read.

Why would an equals event never fire at all?

An equal-to comparison can be stepped over: if the runtime samples the tag slower than the counter increments, a scan can read one value below the target and the next scan one value above it, never the target itself. The minute count steps once per minute, far slower than the EA9 scan, so a minutes-based event is safe; prove a seconds-based one on the bench.

Keep reading

  • How-to

    Displaying a Do-More String on a C-More EA9 Panel

    Use the C-More EA9 Dynamic Text object bound to the Do-More short-string tag, and give it a trigger tag that is on whenever the text should update: ST1, the always-on Do-More system bit, works immediately, while a page C-Bit set on at page open and off at page close in the Event Manager ties the display to the open screen.

    HMI and touchscreens

  • Troubleshooting

    Why You Cannot Set a Custom PanelView 5310 Screen Saver Image

    No. The PanelView 5310 is a PanelView 5000-series terminal, and its screen saver is a terminal-level function locked to the supplied Allen-Bradley logo: Rockwell Automation Knowledgebase article QA39771 states the image cannot be changed. Images imported into the project stay inside the FactoryTalk application and never reach the screen saver; for custom idle artwork, build an application-controlled idle display in Studio 5000 View Designer.

    HMI and touchscreens

  • How-to

    Why C-more Micro Preview Screens Show Out of Order

    Preview thumbnails in C-more Micro follow the project's stored Screen Library list order, not the screen number, and Preview has no sort function. Fix the sequence by dragging entries in the Screen Library; never renumber screens, because every screen-change reference stores the number.

    HMI and touchscreens