Why You Cannot Set a Custom PanelView 5310 Screen Saver Image

HMI and touchscreens Published 7 min read

Short answer

No. The PanelView 5310 is a PanelView 5000-series terminal, and its screen saver is a terminal-level function locked to the supplied Allen-Bradley logo: Rockwell Automation Knowledgebase article QA39771 states the image cannot be changed. Images imported into the project stay inside the FactoryTalk application and never reach the screen saver; for custom idle artwork, build an application-controlled idle display in Studio 5000 View Designer.

On this page
  1. The screen saver belongs to the terminal, not the application
  2. Read the symptom before touching files
  3. Prove it at the terminal in five steps
  4. Use the built-in screen saver when the logo is acceptable
  5. Build custom idle artwork in the application
  6. Where a custom screen saver image is supported
  7. What not to spend time on
  8. Verify the workaround before you call it done
  9. The decision, case by case
  10. Questions asked

No — the PanelView 5310 cannot display a custom screen saver image, and the chase ends here. The 5310 is a PanelView 5000-series terminal, and its screen saver is a terminal-level function fixed to the supplied Allen-Bradley logo; Rockwell Automation Knowledgebase article QA39771 answers this directly: the screen saver image on a PanelView 5000 terminal cannot be changed. The image you imported belongs to the FactoryTalk application, and no terminal setting can point the screen saver at it — the path-like value that renders blank is not a supported image selector. You have two workable outcomes: accept the supplied logo with the built-in screen saver, or build an application-controlled idle display in Studio 5000 View Designer that carries your artwork while the application runs.

The screen saver belongs to the terminal, not the application #

Two subsystems share that display, and they do not exchange content. The downloaded application owns its displays, graphic objects, navigation and imported images; a bitmap renders only on a display that references it, and importing the file publishes nothing at terminal level. The screen saver belongs to the terminal configuration and keeps its supplied logo no matter which application is running. That boundary is why your image can render correctly on an operating screen while the saver stays untouched.

The documentation matches the behavior. User manual 2713P-UM001_-EN-P covers enabling the screen saver and adjusting its settings on page 53, and defines no procedure for installing or selecting a replacement image. The same family boundary appears elsewhere: the 5310 loads applications built in Studio 5000 View Designer rather than the MER runtime files of the PanelView Plus family, which is why a PanelView 5310 reports an MER file as not a valid device.

Read the symptom before touching files #

Match what you see on the glass to the cause:

  • The Allen-Bradley logo appears after inactivity — the terminal screen saver is working as designed, and its image is not replaceable.
  • Your image shows on an operating display but never in the saver — it is application content, and that is where it stays.
  • A path-like value in the saver settings renders as blank text — that display is not an image assignment mechanism, so there is no missing file to hunt.
  • The saver never activates — check the enable state and the inactivity setting in the terminal configuration before anything else.
  • A custom idle screen appears while the application runs but not outside runtime — that is application logic, not the terminal saver.

A blank path value does not by itself indicate a failed transfer, a wrong filename or a bad format. The fault you were looking for does not exist; the unsupported handoff between application content and the terminal feature is the entire problem.

Prove it at the terminal in five steps #

  1. Place the imported image on an ordinary display in the project and run the application. If it renders there, the project holds a usable graphic and the file is fine.
  2. Stop touching the terminal and wait out the configured inactivity interval. The supplied logo appearing confirms the screen saver itself works.
  3. Open the terminal configuration and check the screen saver's enable state and its adjustable settings, as the manual describes.
  4. Look specifically for an image-selection control. A text value, status field or apparent path is not one, and the manual defines none.
  5. Close with the authoritative answer: QA39771, a TechConnect-level knowledgebase entry, states the PanelView 5000 screen saver image cannot be changed. If the logo appeared on schedule in step 2, stop troubleshooting file formats — the feature already works as designed.

Use the built-in screen saver when the logo is acceptable #

If the requirement is only that the terminal goes idle after inactivity, the built-in feature already satisfies it:

  1. Enter the terminal configuration on the terminal.
  2. Enable the screen saver.
  3. Set the inactivity behavior to the value the machine specification calls for, and read the configured delay back from the terminal instead of assuming it.
  4. Return to the application and leave the terminal alone through one full interval to confirm.

Accept the supplied image. That is the whole supported procedure on this series; everything beyond it is the application workaround below.

Build custom idle artwork in the application #

When branding or operating instructions must appear during idle time, the custom path is an application display, not the screen saver. In the Studio 5000 View Designer project, create a display, place the imported image on it, navigate to that display on an application-defined idle condition, and give it a deliberate return action when activity resumes.

Two design rules keep it honest. An idle screen hides live graphics by design, so hold off navigating to it while any alarm the operator must act on is active. And the terminal screen saver can still activate over the application if their conditions overlap, so the two timers have to be coordinated.

Worked example, with illustrative values you would replace with your configured ones: last touch at 0 min, application idle timeout 5 min, terminal screen saver set to 10 min. The custom display appears at 0 + 5 = 5 min. The terminal logo fires at 0 + 10 = 10 min and then covers the custom artwork for the rest of the idle period. To keep your image visible, disable the terminal screen saver or move its inactivity past the custom display's full window: with a 30 min terminal setting and the same 5 min timeout, the custom display owns 30 − 5 = 25 min before the logo can appear.

Detecting idle yourself and controlling what the screen does is the same application-side pattern behind custom idle detection and display intensity control instead of the native screensaver, described for the PanelView Plus family.

Where a custom screen saver image is supported #

The limit belongs to the PanelView 5000 series. Other PanelView families do let you replace the artwork:

Terminal family Custom saver image Documented route
PanelView 5000, including the 5310 No Enable and time the built-in saver only
PanelView Plus 7, 6 and CE Yes Configuration menu, Terminal Settings, Display; image from USB flash media
PanelView Component Yes, firmware 1.20 and later Bitmap of roughly 20 KB named "Screen Saver" loaded to the terminal

For the Plus family, the full procedure is in setting a company logo screensaver on a PanelView Plus. If a project can still choose its terminal and custom idle branding is a hard requirement, that is the decision driver: a Plus or Component terminal takes the image natively, a 5310 never will.

What not to spend time on #

  • Re-importing the image or converting formats. Import affects application displays only; no format reaches the terminal saver.
  • Renaming the file to satisfy the blank path text. The field is not a selector, so no filename can be the right one.
  • Repeated project downloads. The application download and the terminal screen-saver resource are separate, and flashing the project again changes nothing at terminal level.
  • Hand-editing terminal files to install an image. No documented installation path exists for this series, so anything of the sort is unsupported.

Verify the workaround before you call it done #

  1. From a known starting display, confirm normal touch input and navigation first.
  2. Idle past the application timeout and confirm the custom image appears only under the intended condition.
  3. Exercise the return action and confirm it restores the correct operating screen without issuing machine commands.
  4. Repeat after an application restart, and after a controlled terminal restart if terminal settings belong to your commissioning baseline.
  5. Keep the two acceptance tests separate: the application test proves the image resource and navigation, the terminal test proves the built-in settings. Passing one says nothing about the other.

The decision, case by case #

  • You only need the terminal to go idle after inactivity: enable the built-in screen saver, set the interval, accept the logo.
  • Custom artwork must appear during idle on this 5310: build the idle display in View Designer, and disable the terminal saver or time it past the custom display's window.
  • You were following the path-like value in the settings: stop. It is not a supported selector, and no file operation will make it one.
  • The terminal is not yet chosen and idle branding is mandatory: pick a family with a documented replaceable saver image, because the 5000 series does not take one.

Questions asked

Is there a firmware release that unlocks a custom image on the 5310?

None is documented. The knowledgebase answer covers the PanelView 5000 terminal as it ships, and manual 2713P-UM001_-EN-P shows only how to enable the screen saver and adjust its timing. No release noted in that documentation adds an image-selection function, so build the idle-display workaround instead of waiting for a firmware that adds one.

Why did the path-like screen saver setting render blank text?

Because it is not an image selector. The documented settings enable the screen saver and set its inactivity behavior; none of them publishes an imported project image as a terminal asset. The blank text is the terminal telling you there is no supported assignment to make, not a report of a missing or misnamed file.

Will the terminal screen saver cover my custom idle display?

It can, whenever both timers are active. The terminal-level saver runs above the application, so either disable it while the application-controlled idle display is the intended behavior, or set its inactivity longer than the custom display's full visibility window. Confirm the winning configuration once more after a controlled terminal restart.

Which engineering software builds the 5310 application?

Studio 5000 View Designer programs the PanelView 5000 series; that is also why the 5310 rejects MER runtime files built for PanelView Plus terminals. Match the View Designer version to the terminal's firmware before starting the idle-display workaround, since a project only downloads to the target it was built for.

Does the idle display show my artwork when no application is running?

No. The idle display is runtime content: it needs the application running, its idle-detection logic and its return navigation. At the terminal configuration menu or with no application loaded, only the built-in screen saver exists, and it shows the supplied logo. Record that dependency wherever the custom artwork is promised.

Keep reading

  • Troubleshooting

    Why a PanelView 5310 Says Not a Valid Device for an MER File

    The message is a platform mismatch, not a terminal fault. An .mer file is a FactoryTalk View Machine Edition runtime for PanelView Plus 6 and 7 terminals, while the PanelView 5310 belongs to the PanelView 5000 family and runs Studio 5000 View Designer projects. Either run the .mer on a PanelView Plus or a PC with the Machine Edition runtime, or rebuild the application as a View Designer project.

    HMI and touchscreens

  • How-to

    Setting a Company Logo Screensaver on a PanelView Plus

    Use the terminal's built-in Windows CE screen saver when the firmware is between 3.20.08 and 5.10.xx: put a BMP logo on the terminal and point Terminal Settings → Display → Screen Saver at it. On any firmware, build the screensaver as a FactoryTalk View ME display driven by a controller idle timer, with a full-screen transparent pushbutton to dismiss it and a 0-100 backlight tag to dim it.

    HMI and touchscreens

  • Explainer

    Why two Vijeo Designer HMIs cannot share one user list

    No. Vijeo Designer 6.2 keeps its user list in each terminal's own runtime data, and no I/O Manager driver exposes accounts or passwords as variables, so an Ethernet link between two HMIG3U panels synchronizes variables and the clock, never users. Either download one identical list to both terminals at every change, or centralize authentication on panel PCs.

    HMI and touchscreens