Setting a Company Logo Screensaver on a PanelView Plus

HMI and touchscreens Published 7 min read

Short answer

Use the terminal's built-in Windows CE screen saver when the firmware is between 3.20.08 and 5.10.xx: put a BMP logo on the terminal and point Terminal Settings → Display → Screen Saver at it. On any firmware, build the screensaver as a FactoryTalk View ME display driven by a controller idle timer, with a full-screen transparent pushbutton to dismiss it and a 0-100 backlight tag to dim it.

On this page
  1. Where is the screensaver setting on a PanelView Plus?
  2. Which firmware versions support the built-in screen saver?
  3. What file format does the logo need to be?
  4. How do you turn on the native screen saver?
  5. How do you build the screensaver inside FactoryTalk View ME?
  6. How long should the idle time be before the logo appears?
  7. How do you dim the backlight while the logo is showing?
  8. Why does the screen saver wake up on its own or never start?
  9. Which method should you choose?
  10. Questions asked

Two roads, and the right one depends on the firmware. On classic PanelView Plus terminals the logo screensaver is already in the box: the terminal's Windows CE screen saver takes a BMP of the company logo and shows it after an idle wait, documented for firmware 3.20.08 through 5.10.xx. On anything newer, or whenever the logo should also dim the backlight and follow the machine cycle, build the screensaver as a FactoryTalk View ME display with an idle timer in the controller and a full-screen transparent pushbutton to dismiss it. This article gives both, with the numbers that decide between them.

Where is the screensaver setting on a PanelView Plus? #

It is a terminal setting, not part of the FactoryTalk View project: from Configuration mode, open Terminal Settings → Display → Screen Saver on a PanelView Plus, PanelView Plus CE, or PanelView Plus Compact terminal. Because the screen saver runs at the Windows CE level, it sits over a FactoryTalk View ME runtime exactly as it sits over any other application; nothing in the project file has to change. The same page exists on the terminal's CE desktop at Start → Settings → Control Panel → Display, on the Screen Saver tab, which is the faster path when a keyboard is attached. A terminal that boots straight into the application and offers no configuration button is its own access problem, covered in the recovery walkthrough for a PanelView Plus 600 with no config button and full flash.

Which firmware versions support the built-in screen saver? #

The documented range is firmware 3.20.08 through 5.10.xx, and since original PanelView Plus hardware supports only up to 5.10, that range covers every classic terminal as shipped from the factory. All three variants, PanelView Plus, PanelView Plus CE (formerly VersaView CE) and PanelView Plus Compact, run Windows CE 4.1 underneath, and Rockwell Automation Knowledgebase article 28335 documents the screen saver across the whole family. Check the revision before you configure anything: Start → Settings → Control Panel → System shows the firmware string, for example 5.10.16. Later-generation terminals run releases above 5.10.xx, where the screen saver still exists but has alarm-related defects covered below, and on PanelView Plus 7 the practical route is the application-level method in this article with brightness and navigation driven from the controller.

What file format does the logo need to be? #

A Windows CE 4.1-compatible bitmap: BMP at 16-color or 24-bit depth, with a pixel count at or below the terminal's native resolution, because PNG and animated GIF files are not rendered by the built-in screen saver. The OS enumerates bitmaps from the \Storage Card\Screensaver folder or from the \Windows directory, so the file has to sit in one of those two places to appear in the selection list. Match the terminal's native pixel count; 640×480, 800×600 and 1024×768 cover the classic family, and an oversized file gets clipped or refused outright. Center the artwork on a black field so it reads from across the aisle.

How do you turn on the native screen saver? #

Copy the BMP to the terminal, set the wait time and the password option from Terminal Settings → Display → Screen Saver, and ten minutes of wait is the right default for an operator-facing panel. The full sequence:

  1. Copy the logo BMP into \Storage Card\Screensaver or \Windows on the terminal.
  2. Enter Configuration mode and open Terminal Settings → Display → Screen Saver (or Start → Settings → Control Panel → Display, Screen Saver tab, on the CE desktop).
  3. Select the logo file from the screen saver list.
  4. Set Wait to the idle delay; 5, 10, 15 and 30 minutes are the sensible values, and 10 minutes suits a panel operators pass all shift.
  5. Set Password Protected to None so any touch restores the running display without a login prompt.
  6. Prove it at the bench: leave the terminal untouched for the wait time and confirm the logo fills the display edge to edge.

The complete sequence for configuring a static full-screen logo as the screensaver on a PanelView Plus 600 walks the same path with that display's pixel size.

How do you build the screensaver inside FactoryTalk View ME? #

Create one display that carries the logos, cover it with a full-screen transparent pushbutton, and navigate to it when the controller says the machine has been idle; this works on any firmware and gives you control of dismissal and dimming. The build:

  1. In FactoryTalk View Studio, create a display, SS_Corporate in this example, with a black background, set to periodic update at 1000 ms if anything on it changes.
  2. Center the company logo at roughly 20 percent of display height, and put the customer logo at about 70 percent if the site wants both.
  3. Draw a transparent pushbutton covering the entire display, 1024×768 on a 15-inch terminal, with security set to None.
  4. On the pushbutton's Release event, navigate back to the previous display, or explicitly to the main overview screen.
  5. Add a small hidden touch target in one corner so maintenance can bypass the logo without waiting out the timer.
  6. Leave idle detection to the controller, not the HMI, because the HMI's tag cache can mask short bursts of activity, and test the whole sequence on a bench download.

How long should the idle time be before the logo appears? #

Commit to 10 minutes on a staffed line and 30 minutes in a low-traffic area: at 600 one-second counts the logo appears after exactly 10.0 minutes with no touch and no machine cycle, and 1800 counts gives 30. Run the counting routine in a periodic task at 1000 ms so one increment is one second:

// Illustrative tag names - declare in the controller
screen_idle_timer  : DINT := 0;     // seconds with no touch and no cycle
TouchDetected      : BOOL := FALSE; // set by the panel's touch activity
MachineCycleActive : BOOL := FALSE; // set by the machine state logic

// Periodic task, 1000 ms period
IF TouchDetected OR MachineCycleActive THEN
    screen_idle_timer := 0;
ELSE
    screen_idle_timer := screen_idle_timer + 1;
END_IF;

In FactoryTalk View Studio, put the navigation on the main displays: go to SS_Corporate when screen_idle_timer reaches the threshold. The arithmetic is the whole design: 300 counts × 1 s = 5 min, 600 counts × 1 s = 10 min, 1800 counts × 1 s = 30 min. The quick proof, without waiting ten minutes: hold both BOOL inputs false and the count reads 60 after 60 s; force TouchDetected true and it holds 0. With the HMI's default 250 ms tag polling, the count and the reset reach the screen within about a quarter second of the real event.

How do you dim the backlight while the logo is showing? #

Write a 0 to 100 percent value to the terminal's local backlight tag, where 100 is full intensity and 0 is blank, and step it down while the logo screen is up; any touch writes 100 straight back. The tag sits with the terminal's HMI device tags in FactoryTalk View Studio, so the same write works from the pushbutton release that clears the screen. One illustrative ramp that reaches a readable floor in two and a half hours: start at 100 and subtract 10 points for every 15 minutes of continued idle, 10 steps × 15 min = 150 min = 2.5 h, and stop at a floor of 20 so the logo never disappears entirely. Touch resets the ramp to 100 through the same event.

Why does the screen saver wake up on its own or never start? #

Because alarms interact with it: from firmware V5.0 onward an active alarm wakes the screen saver, and on firmware 9.00.00, 10.00.00 and 11.00.00 a remotely acknowledged alarm stops it from starting until a Rockwell patch is installed. The wake-on-alarm behavior is what you want, not a fault; the never-starts symptom is the fault, and it shows up on terminals where alarms get acknowledged from a SCADA seat rather than at the panel. The patch installs only at those three firmware levels, so the firmware gate is the first thing to check. Before you rely on any logo screen on a running line, prove at the bench that an active alarm brings the process display back on your exact firmware, because an alarm hidden behind a logo is the one failure mode that matters here.

Which method should you choose? #

Use the built-in screen saver on any classic PanelView Plus at or below firmware 5.10, since it is a ten-minute configuration job; build the ME display when the terminal is newer, when you want PLC-controlled dimming, or when the logo must follow the machine cycle instead of a touch timer. Case by case:

  • PanelView Plus, PanelView Plus CE or PanelView Plus Compact on firmware 3.20.08 through 5.10.xx with a static logo: the native screen saver, no project change needed.
  • Any terminal where the logo must dim the backlight, track the machine cycle, or dismiss on something other than touch: the ME display with controller idle logic and the backlight tag.
  • Terminals at firmware 9.00.00, 10.00.00 or 11.00.00: the ME display, or the native screen saver plus the alarm patch.
  • PanelView Plus 7: the ME display method, with brightness and navigation driven from the controller, is the route engineers land on there.

Questions asked

Does the built-in screen saver work over a FactoryTalk View ME application, or only over CE applications?

It works over ME applications. The screen saver is a Windows CE feature of the terminal itself, configured in Terminal Settings, so it sits above whatever runtime is loaded and needs no change to the FactoryTalk View project. It also survives application downloads and runtime version changes, because it never touches them.

Can the logo be a PNG or an animated GIF?

No. The built-in screen saver renders a static, CE 4.1-compatible BMP at 16-color or 24-bit depth; PNG and animated GIF files are simply not drawn. If you want movement on the idle screen, build the logo as a FactoryTalk View ME display instead, where you control every graphic and its animation yourself.

How do I get our existing PNG logo into the right bitmap format?

Export or convert it to a 24-bit BMP at the terminal's native pixel count, 640×480, 800×600 or 1024×768 depending on the display, and keep the file at or below that size because oversized images get clipped or refused. Flatten any transparency onto a black background before converting so the logo reads cleanly on the dark idle screen.

Why dim the backlight if the logo is staying on the screen anyway?

Hours at full intensity are what age the backlight and draw the power; a logo shown at reduced brightness costs less of both. Stepping the backlight tag down during long idle periods, with any touch writing 100 back, keeps the panel legible the moment someone walks up while saving the backlight when nobody is there.

Where is the manufacturer's own procedure documented?

Rockwell Automation Knowledgebase article 28335 documents the built-in screen saver across the 3.20.08 to 5.10.xx firmware range. Viewing it requires a TechConnect support contract on the Rockwell support site; the terminal-side steps in this article follow the same configuration path if you cannot reach the article.

Keep reading

  • Troubleshooting

    Why PanelView 600 Plus Alarms Stay Blank and Configure Mode Crawls

    Blank alarms mean the alarm Trigger Type, whole-word trigger address and message value do not match the PLC bits — with Trigger Type on bit and the trigger on the whole word, the message value is the bit number plus 1. The close-to-five-minute Configure Mode exit is tag errors elsewhere in the application; deleting loaded runtime applications was tried and changed nothing. Re-map the alarms, clear every reported tag error, and both symptoms clear.

    HMI and touchscreens

  • Troubleshooting

    PanelView Plus 7 Name and Password Setup Error Fix

    The Name and Password setup error on a PanelView Plus 7 is a setup-state failure, not a rejected password, when compliant entries keep failing at the same transition. Read the exact message, run one simplified-entry validation test, capture the catalog number, firmware revision, error text, application copy and network settings, then use the documented factory reset for your catalog number and re-run setup.

    HMI and touchscreens

  • How-to

    Showing Tags From Five PLC-5 Processors on One PanelView Plus

    Yes. One PanelView Plus screen can show tags from all five PLC-5/25 processors, because each object resolves through its own shortcut to one controller's station address on DH+. Configure five shortcuts and prove one known live value from each processor before building production screens.

    HMI and touchscreens