Why two Vijeo Designer HMIs cannot share one user list

HMI and touchscreens Published 5 min read

Short answer

No. Vijeo Designer 6.2 keeps its user list in each terminal's own runtime data, and no I/O Manager driver exposes accounts or passwords as variables, so an Ethernet link between two HMIG3U panels synchronizes variables and the clock, never users. Either download one identical list to both terminals at every change, or centralize authentication on panel PCs.

On this page
  1. What the I/O Manager driver actually carries
  2. Why accounts cannot ride the link
  3. The panels can still share the machine
  4. Option 1: one list, maintained twice
  5. Option 2: centralized authentication on panel PCs
  6. The decision, case by case
  7. Questions asked

Two Vijeo Designer 6.2 terminals cannot share one user list. Each HMIG3U keeps its accounts in its own runtime data, and the I/O Manager driver route you found exposes process variables and terminal data such as the clock, never user records, so free RJ45 ports plus an Ethernet link cannot carry the synchronization. With the stated constraints - no transit through the controller, no removable media, no maintenance PC during operation - full runtime user synchronization is not achievable on this pair of terminals. Two real options remain: administer one identical list and download it to both panels at every change, or change hardware class to centralized authentication on panel PCs.

What the I/O Manager driver actually carries #

The path you started down is real, but its scope is external variables: tags declared in the project and exchanged with equipment, the same mechanism as adding a Modbus RTU driver and external variables in Vijeo Designer. The terminal data documented to cross that path is a different kind: a Schneider Electric procedure, FA290175, synchronizes the terminal clock from a Modbus equipment node selected in the I/O Manager. So the equipment-to-terminal synchronization that exists covers variables and the clock. There is no driver, node type or documented function whose address space includes user accounts.

Vijeo Designer user management is internal to each target and independent between targets, and the vendor documentation shows where the accounts live. Per Schneider Electric FAQ FA225803, after any change to security data - user names, groups or passwords - all runtime data on the terminal must be deleted before the change takes effect. Accounts are therefore part of each panel's runtime data store, refreshed by a download, not a database with a communication address. Nothing in that store is exposed to a driver, so there is nothing for one HMI to write and nothing for the other to poll. The number of documented mechanisms that transfer or centralize user-management data between standalone Vijeo Designer targets is zero.

The one documented hook that moves login state off a terminal is a login macro writing the active user's name to a PLC tag, covered in sending the active HMI user to the PLC with a login macro. It reports a name after a successful login; it creates no account, changes no password, and the controller route is barred by this project's constraints anyway.

The panels can still share the machine #

Nothing here forces a single-panel design. Two panels controlling one machine over Ethernet is workable practice - see connecting two HMI panels to control one machine - with each terminal holding its own equipment connections. The split is clean: everything declared as a variable can be shared or routed; the account list is the one object that stays per-terminal. Design security on that boundary instead of fighting it.

Option 1: one list, maintained twice #

Keep both HMIG3U terminals. Define the complete user set once in the project's user groups, download the project to both terminals, and treat every later change - addition, removal, password reset - as a design-time edit followed by a download to each panel, with the runtime-data deletion that FA225803 requires before the change takes effect. Because a maintenance PC is barred during operation, these changes belong in planned windows.

Illustrative example: assume 14 accounts and 8 security changes a year (2 additions, 2 removals, 4 password resets). Every change is applied twice, so 8 changes a year x 2 terminals = 16 downloads each year, each paired with a runtime-data clear on that panel. The failure mode is divergence: apply a year of changes to one panel only and 8 of 14 records are wrong on the other - 8 / 14 = 0.57, or 57 percent of the list. Because both panels act on the same machine, an operator removed from one terminal but not the other still has access at the other: treat every revocation as two downloads, or as not performed.

Decision: accept this option when changes are infrequent and can wait for a planned stop. At the example rate, 16 downloads and 16 runtime clears a year is the honest cost of staying on this hardware.

Option 2: centralized authentication on panel PCs #

The documented centralized route is a server holding the credentials, with industrial panel PCs authenticating against it at the machine. This is a change of hardware class, not a configuration of the HMIG3U pair: the terminal-local user store is replaced by a network account source. On PC-based panels the same requirement is normally met with domain-style authentication, the pattern described in centralized domain login configuration on PC-based panels, where one account source serves every station and a revocation applies everywhere at once.

Decision: choose this when account changes are frequent, when revocation must take effect at both screens immediately, or when an audit expects a single account source. You are buying an architecture, not a setting.

The decision, case by case #

  • Keep the two Vijeo Designer 6.2 terminals only with a single authoritative list, changed at design time and downloaded to both panels in the same window, never edited at runtime on one panel.
  • Move to panel PCs with centralized authentication as soon as revocation timing or audit requirements outgrow double downloads; at roughly one account change a month or more, the download and runtime-clear load dominates.
  • Stop searching the driver list for a user-synchronization function: within Vijeo Designer 6.2 there is none, and the free Ethernet ports on the terminals do not change that.

Questions asked

Is there a script or system variable that reads the user database so I can build my own synchronization?

None is documented. The address space a driver reaches covers the external tags you declare and terminal data such as the clock; account records are not in it. A homegrown sync would depend on an undocumented interface, which is exactly what a regulated site should not place between operators and machine access.

What does divergence between the two lists look like on the floor?

A password that works on one screen and is rejected on the other, or an operator who can open a function on one panel that the other blocks. Because both panels act on the same machine, treat an account removed from only one terminal as still active everywhere.

Would a newer Vijeo Designer version synchronize users between terminals?

Treat the per-terminal user store as a design property of the product line rather than a 6.2 defect: no version is documented to transfer or centralize account data between standalone targets, so an upgrade is not the fix. The documented centralized route is authentication served to PC-based panels.

What else does the runtime-data deletion rule cost on each panel?

Runtime data on that terminal is consumed by the change, so logs and other stored runtime content are lost with each account edit, not only with full downloads. Schedule security changes knowing that every one clears the panel runtime data before the new accounts take effect.

Keep reading

  • How-to

    Using Vijeo Designer 6.2 to program an HMISTU series HMI

    HMISTU terminals sit outside the Easy HMI offer that Vijeo Designer Basic programs, and no communication setting adds them. Install regular Vijeo Designer 6.2, take it to the SP12 service pack level, confirm the complete terminal reference appears in the target list, then build and transfer.

    HMI and touchscreens

  • Explainer

    Why one HMI password opens buttons at two security levels

    On a Delta DOP-B, security is one hierarchy from level 0 to level 7: a password registered at level 5 authorizes elements at level 5 and every level below it, including level 3. Two momentary buttons on this panel therefore cannot carry mutually exclusive passwords. Keep the ladder when a senior operator may press both buttons; move to a platform that assigns permissions per user when credentials must be exclusive.

    HMI and touchscreens

  • Troubleshooting

    Fixing Vijeo Designer Error 1850 Secondary Drive Not Found

    Error 1850 on an HMIG3U appears because the project assigns a data file to a Secondary or Optional drive this target does not define; it supports only the Main drive with an SD card. Move the data file's location to Main, rebuild, and the download completes. No hardware switch enables the missing locations.

    HMI and touchscreens

Why You Cannot Set a Custom PanelView 5310 Screen Saver Image