How-to
SIWAREX U load cell setup on a TP900 Comfort HMI
Short answer
For a first-time SIWAREX U integration, start from the vendor's getting-started S7 project, which exists for S7-300/400 and S7-1500 in STEP 7 Classic and TIA Portal. No S7-1200 example exists, so that family needs its own validation. Wire the load cell per manual chapter 4.4.5, then calibrate through the remapped HMI screens.

On this page
- Which example project should I start from for my PLC?
- Can I use the S7-1500 example on an S7-1200?
- How do I wire the load cell to the SIWAREX U module?
- How do I get the example HMI screens onto the TP900 Comfort panel?
- How do I map the example to my real project?
- How do I calibrate the load cell through the HMI?
- How do I prove the whole chain works before production?
- Questions asked
For a first SIWAREX U weighing axis, the fast path is the vendor's getting-started S7 project, which packages the PLC integration, the message function and the WinCC flexible HMI screens in one download. It exists for S7-300/400 and S7-1500; nothing equivalent is published for S7-1200. Wire the load cell per the device manual, load the example, remap it to your project, and calibrate through the HMI.
Which example project should I start from for my PLC? #
Start from the getting-started S7 project that matches your controller family: use the STEP 7 Classic or TIA Portal variant for S7-300/400 and the TIA Portal variant for S7-1500. The download shows how a SIWAREX U is integrated into an S7 system through different slave modules and includes an S7 program with the integration and message function, plus a WinCC flexible project for visualizing and handling the module.
Pick the variant that matches your installed engineering environment and the exact slave module in your hardware configuration. If your S7-300 project lives in STEP 7 v5.x and you are considering moving it to TIA Portal, the article on which S7-300 modules TIA Portal V13 supports tells you where to check before you commit to the conversion.
Can I use the S7-1500 example on an S7-1200? #
No. The vendor's own guidance is that no SIWAREX U example project exists for S7-1200, and that the S7-1500 example might work but is not confirmed to. Treat the S7-1200 path as your own integration, not a copy of the example.
The decision per family:
| PLC family | Starting point | Constraint |
|---|---|---|
| S7-300/400 | Getting-started example, STEP 7 Classic or TIA Portal variant | Match the slave module in your hardware configuration |
| S7-1500 | Getting-started example, TIA Portal variant | Validate hardware configuration and program interfaces before adapting the HMI |
| S7-1200 | No published example | Import and validate yourself; the S7-1500 project's behavior on S7-1200 is unconfirmed |
For S7-1200, import the program, compile it against your hardware configuration, and prove communication, weight values and the message function on the bench before trusting it. If any step fails, the S7-1500 example is the wrong starting point, not a project to debug on a live machine.
How do I wire the load cell to the SIWAREX U module? #
Wire it exactly as chapter 4.4.5, Load cell connection, of the SIWAREX U device manual specifies. That chapter defines which sensors are connectable: those equipped with strain gauges meeting the conditions the manual lists.
The example project description contains no terminal numbers, conductor assignments, excitation details or shielding practice, so take all of that from the manual for your exact module. If you connect more than one load cell, the manual's connection guidance requires a junction box, with the load cells wired in parallel; the multi-cell path goes through the junction box, never directly to the module terminals. Complete the wiring before you attempt calibration: a shield left open or an excitation pair swapped will show up later as a weight reading you cannot calibrate.
How do I get the example HMI screens onto the TP900 Comfort panel? #
Convert the example's WinCC flexible visualization in your engineering tool and confirm the panel is a supported target before you plan to load it. The download includes the HMI pictures used for handling and calibrating the module, which is exactly what a first-time integrator needs, but direct TP900 Comfort compatibility is not established by the documentation, so verify the conversion in your installed software.
When the screens load, check the panel side against your controller setup the same way you would for any Comfort panel project; the article on configuring a TP900 Comfort panel with a CPU 412-5H project walks through that panel-to-CPU pairing. Treat the example screens as an implementation reference for layout and command mapping, not as a drop-in runtime.
How do I map the example to my real project? #
Keep the example's SIWAREX U integration and message-handling structure, and replace only what your machine needs. Concretely:
- Identify the PLC family, engineering environment and exact SIWAREX U slave module used in your hardware configuration.
- Open the matching example and leave its module integration and message function intact.
- Adapt PLC addresses and HMI tags to your real project, so every displayed value and operator command points at your intended data.
- Compile both the PLC program and the HMI project, then download to the bench PLC and panel.
If the HMI and PLC logic come from different source projects, the article on combining two migrated WinCC HMI projects in TIA Portal covers merging them without losing the screen-to-tag links.
How do I calibrate the load cell through the HMI? #
Run the documented SIWAREX U calibration sequence through the mapped HMI controls, in this order: complete wiring, establish PLC-to-module communication, confirm the message function reports status, then execute calibration. The example's HMI pictures show the intended workflow; the specific command sequence, calibration weights and acceptance limits come from the SIWAREX U documentation for your module, not from the project description.
As a worked bench example: place a known test mass, for example 10.000 kg, on the empty scale, enter that value as the calibration target through the HMI calibration screen, apply the mass, and confirm the module stores the adjustment. The scale then reads 10.000 kg within the tolerance your project defines; if the indicated value differs by more than that tolerance, fix wiring or scaling before adjusting anything else. Never conclude calibration from a single point alone; verify zero with the platform empty and span with the test mass.
How do I prove the whole chain works before production? #
Run a bench acceptance test with verified test weights before the scale sees product. Confirm three things separately: the HMI reads live weight from the module, operator commands reach the intended module interface, and the message function reports faults and status. Then load and unload the known mass several times and confirm the indication repeats within your project's tolerance.
If the HMI reads stale or missing values while the PLC side is healthy, separate the panel from the measurement with the diagnosis in the article on separating PLC scan time from real HMI communication faults; a communication refresh problem mimics a calibration fault exactly. The safety note that goes with all of this: a weighing axis that commands dosing or batching must fail to a safe state when the module reports a fault, and that interlock belongs in the PLC program, not in the HMI screen.
The decision, per case: S7-300/400 and S7-1500, start from the published example and remap it; S7-1200, no example exists, so budget your own integration and validation time from the start.
Questions asked
Is there a SIWAREX U example project for S7-1200?
No dedicated SIWAREX U example project exists for S7-1200. The vendor states an S7-1500 project may work on S7-1200 but does not confirm it, so treat it as unvalidated. Import it, compile it against your S7-1200 hardware configuration, and prove communication, commands and the message function on a bench before any production use.
Where is the load cell wiring for the SIWAREX U module documented?
The chapter lists which strain-gauge sensors may be connected and gives the terminal assignments and shielding practice. Do not infer conductor functions from the example project; take them from the manual for your exact module revision.
Can the example HMI screens run directly on a TP900 Comfort panel?
The example ships as a WinCC flexible visualization, and direct TP900 Comfort compatibility is not established by the vendor. Convert the project in your installed engineering tool, confirm the panel is supported as a target, remap every tag to your PLC addresses, and test each displayed value and operator command before putting the screen into service.