Viewing a Vision Camera Image on a Comfort Panel HMI
Short answer
A Comfort Panel has no video decoder, so the FQ2 image reaches the panel as a web page: enable the camera's built-in web server, display that page in the panel's browser object on a 1 to 2 second reload, and pass fail judgments through PLC tags. Continuous live tuning belongs on a PC running the vendor's setup software.
On this page
A Comfort Panel cannot decode a live video stream, so connecting an FQ2 smart camera to it is not a search for the right cable or player. The camera runs its own inspection, judges each trigger and serves its own web pages; the panel's job is to display one of those pages and the pass and fail tags that arrive through the PLC. Enable the camera's built-in web server, point the panel's web-page display object at it, and let it reload every 1 to 2 seconds, which is enough to re-aim the lens after the mounting bracket moves. Continuous video is a different job for different hardware. What follows: the limits that set the architecture, the setup on both devices, the arithmetic that shows the network is never the constraint, and the decision for each job.
Why the panel shows stills, not video #
The Comfort Panel runs an HMI runtime, not a Windows desktop, and that runtime has no decoder for MJPEG, H.264 or RTSP. There is no video player object to place on a screen and no stream to subscribe to. The FQ2 is built the same way from the other side: it is a self-contained inspection node — lens, lighting control, processor, I/O and judgment logic in one housing — and its Ethernet services expose inspection results and its own configuration pages, not a broadcast feed. The FQ2-S/CH user's manual documents the live image display through the camera's built-in web server and through the PC setup software; that is the only live picture in this integration, and it was never a video stream in the first place. Accept refreshed stills as the panel's picture, and every choice below follows from it.
The camera's web server is the image source #
Set the camera side up first, from an engineering PC, before the panel is involved:
- Enable the web server function in the camera's Ethernet communication settings; the FQ2-S/CH user's manual documents the live image display that runs on it.
- Give the camera a fixed address on the machine network — for example 192.168.1.50 — outside your controller's address range, so the assignment never depends on a DHCP lease.
- Open that address in a PC browser, confirm the live monitor page loads, and wave a part through the field of view to see the frame update.
- Create a read-only login for viewing and keep inspection parameter changes behind an engineering account.
The camera triggers, inspects and judges whether or not anyone is watching the page. The web server is a read-only window on work the camera already did, which is why the display can be added, removed or disconnected without touching the inspection.
Displaying the camera page in the panel viewer #
On the panel, put the web-page display object — the HTML viewer in the screen editor — on its own camera-setup screen, not on the production screen. Enter the camera's page address as the object's URL and set the reload cycle to 1 to 2 s. Each viewer object reloads its page on its own cycle, so a second camera means a second object and twice the reload traffic, not a shared stream.
Two cautions earned on real jobs. Pages built on heavy scripting can render fine on an engineering PC and still come up blank or half-drawn in the panel's viewer — the same failure family as why an HMI trend shows no curves but the PC web page does — so prove the camera page inside the panel viewer during commissioning, while the laptop is still on site. And the pattern itself, one device hosting a page that a panel merely displays, is the same one as running a PLC-hosted visualization on a remote HMI panel PC, so the same screen-design habits apply: give the page its own screen and let operators reach it deliberately.
What the reload cycle costs #
One FQ2, one viewer object, as an example. Take a page image of about 40 kB — an example size for an inspection JPEG; save one frame from your own camera's page and use that number instead. The arithmetic:
- 40 kB × 8 bits per byte = 320 kbit per frame
- 320 kbit ÷ 2 s = 160 kbit/s at a 2 s reload, or 320 kbit/s at a 1 s reload
- 160 to 320 kbit/s against a 100 Mbit/s industrial Ethernet link is 0.16 to 0.32 percent of line rate
Ten cameras on one panel would land near 1.6 to 3.2 Mbit/s, still low single digits in percent. The wire is never the constraint here; the panel viewer's reload cycle is. That is why a cycle below 1 s buys nothing you can see and only takes runtime from the HMI application.
Judgment tags belong on the PLC path #
The picture is for people; the judgment is for the controller. The FQ2 exposes industrial Ethernet interfaces, so the PLC reads judgments, counts and measured values straight from the camera — worth doing exactly when, as here, the inspection is already configured and running its process. The panel then reads those tags from the PLC over its native driver link, and a dashboard needs no image at all.
One rule to keep, and it is the only safety-relevant one in this integration: the refreshed camera page exists for orientation and diagnosis. A stale or skipped reload is indistinguishable on screen from a good frame, so pass, fail and release decisions stay with the camera and the PLC, never with the picture.
Stored reject images over FTP #
When the operator's real question is what the part that just failed looked like, use the camera's file side. The camera stores triggered inspection images and serves them over FTP, a function its communications manual documents: set the camera to keep the image of a failed inspection and name each file with a timestamp so the newest file is never ambiguous. On the panel, a timed script task can fetch the newest file into panel storage and refresh the panel's image display object when the operator opens the review screen. Gate that fetch with a PLC tag that says the review screen is open, so files move only when someone is looking at them. The result is one stored frame per review request, not a video feed — and that matches the question a reject review actually asks.
Continuous video belongs on a PC #
If the job is real commissioning — tuning inspection parameters while watching parts move through the field of view — you want continuous video, and the Comfort Panel is the wrong machine for it. That job belongs to the vendor's PC setup software; for the FQ2 it is TouchFinder, supplied with the camera, and the product literature is explicit that it adjusts parameters in real time without stopping the machine. Run it where the work happens: a touchscreen computer mounted at the line rather than a laptop carried to the cabinet. That is the moment to specify industrial panel PCs for the cell and leave the Comfort Panel on production duty beside them. If the same project has you weighing operator-station architecture for the line as a whole, headless HMI server versus operator panel selection treats that choice directly.
The decision for each case #
Map the job to the path before you wire anything:
| The job at the panel | Display path | What the operator sees |
|---|---|---|
| Re-aim the camera after it shifts | Camera web page in the panel's viewer | Stills on the 1 to 2 s reload cycle |
| Review the last failed part | Stored image fetched over FTP into the panel's image display | One stored frame per review |
| Production dashboard: counts, judgments, measurements | Camera results as PLC tags, panel reads the PLC | Live tag values, no image |
| Tune inspections during commissioning | TouchFinder on an industrial panel PC at the cell | Continuous video |
For the question as asked — see the image on the HMI to re-orient a moved camera — the web page in the viewer is the whole answer: two documented functions on hardware you already own, and traffic that measures 0.16 to 0.32 percent of a standard link in the example above. Add the FTP review path when operators need to look at failed frames. Reserve the PC for tuning. Keep every quality decision on the tag path between camera and PLC.
Questions asked
Can a Basic Panel show the camera's web page instead of a Comfort Panel?
Yes. Any HMI that has a web-page display object can open the camera's live monitor page, and a Basic Panel is enough when someone only occasionally re-aims the camera. The Comfort Panel earns its place when the camera view sits next to reject-review screens, larger images or the production screens. Expect the same refresh pace; the panel family does not change the still-image limit.
Does the camera stop inspecting while the panel shows the image?
No. The camera is triggered from its digital inputs or over the network and inspects on its own schedule; the web page and stored files are read-only views of inspections it already completed. You can disconnect the panel without affecting a single judgment. The only wiring that touches the process is the trigger and result connection to the PLC, and the display never sits in that path.
How many cameras can one panel show this way?
As many web-page display objects as your screens can carry; there is no camera count in the license. Each viewer reloads its own camera page, so traffic grows linearly, and even ten cameras stay in the low single Mbit/s on a standard link. The practical limits are screen space and operator attention, so give each camera its own setup screen and open them one at a time.
Is there an application note from the panel vendor for this integration?
You do not need to hunt for a camera-specific note: both halves are standard documented functions. The camera's own manual covers enabling its web server and its live image display, and the panel's help system covers the web-page display object and its reload setting. Treat the project as a web page plus a tag exchange, and plan it that way from the start.