Troubleshooting
Vijeo Designer Limited Edition blocks HMI download
Short answer
A standalone Vijeo Designer 6.2 session shows Limited Edition because it has no Vijeo Designer license of its own, and that unlicensed session refuses the panel download. A licensed SoMachine 4.3 environment covers HMI modules inside its machine projects, so add the HMI there and download it from SoMachine; standalone-only HMI work needs a Vijeo Designer license.
On this page
- Why does Vijeo Designer 6.2 show Limited Edition when SoMachine 4.3 is licensed?
- Why does the PLC download work but the HMI download fail?
- How do I check which edition my Vijeo Designer session is running?
- How do I download the HMI from the SoMachine 4.3 project?
- When do you actually need a separate Vijeo Designer license?
- What does the Limited or Trial edition actually restrict?
- What if the HMI download still fails from SoMachine?
- Questions asked
The Limited Edition banner is not a fault in the software, and the license that arrived by email is not the problem: SoMachine 4.3 and Vijeo Designer 6.2 are licensed separately, so a standalone Vijeo Designer session with no Vijeo Designer license of its own refuses the panel download even while the licensed SoMachine environment transfers the controller without complaint. The fix is to stop launching Vijeo Designer by itself: add the HMI to the SoMachine 4.3 machine project, build it there, and download it from SoMachine, whose entitlement covers HMI modules inside its integrated machine projects. A separate Vijeo Designer license is needed only when the required workflow is standalone HMI programming.
Why does Vijeo Designer 6.2 show Limited Edition when SoMachine 4.3 is licensed? #
Because the two products are licensed separately: a SoMachine 4.3 entitlement, even one delivered by email and properly activated, licenses the SoMachine environment and its integrated machine projects, and it does not license a Vijeo Designer 6.2 session launched on its own from the Windows start menu.
The line you saw in Help > About is a status readout, not an error dialog. When the 6.2 installation has no Vijeo Designer license of its own behind it, it runs in the vendor's demo/trial/limited mode, and the edition line in the middle of that dialog simply reports it. A valid SoMachine entitlement does not bleed over into the other product; the entitlements cover different launch contexts. The same standalone-versus-integrated split that decides which editor opens a project also decides which license applies, as covered in why a standalone HMI project will not open in your integrated editor.
Decision: an unlicensed standalone session reading Limited Edition is expected behavior, not a broken installation.
Why does the PLC download work but the HMI download fail? #
The two transfers run under two different license contexts: the controller download is issued from the licensed SoMachine 4.3 environment, while the panel download from a standalone Vijeo Designer 6.2 session is refused because that session carries zero Vijeo Designer entitlements of its own.
Run the case numbers as a license count. Entitlements installed on the workstation: 1 × SoMachine 4.3 (email-delivered, activated), 0 × Vijeo Designer 6.2. Permitted standalone panel transfers = 0, so the standalone download is refused; permitted integrated transfers = 1, so the same panel accepts the download started from SoMachine. One entitlement follows the environment you launch from, which is why the same cable and the same panel produce two different results:
- Help > About in the standalone session reads Limited Edition.
- Controller download from SoMachine 4.3: succeeds.
- Panel download from the standalone session: refused.
- The same HMI added to the SoMachine machine project and downloaded from SoMachine: succeeds.
Decision: a green controller transfer proves the SoMachine path and nothing about the HMI path; treat the controller and the panel as two separately licensed, separately deployed targets.
How do I check which edition my Vijeo Designer session is running? #
Open the standalone Vijeo Designer and read the Help > About dialog: the edition line in the middle of the dialog names the operating mode, and the words Limited Edition there tell you the session has no Vijeo Designer license behind it before you attempt any transfer.
Make this the first check, before touching cables, addresses or network settings, because it separates a licensing refusal from a communication fault in ten seconds. Record the exact edition text and the version shown in the same dialog; if you end up talking to Schneider Electric or a distributor about activation, those two lines are what they will ask for. When you work through the SoMachine project instead, no standalone launch happens at all, so the standalone edition question never comes up.
Decision: Limited Edition in Help > About plus a refused panel transfer is a license-context finding; move to the integrated route.
How do I download the HMI from the SoMachine 4.3 project? #
Add the HMI to the licensed SoMachine 4.3 machine project, open its application inside SoMachine, and start the download from SoMachine itself: the panel transfer then runs inside the licensed environment, and it needs no separate Vijeo Designer license.
- Open the SoMachine 4.3 project that contains the controller application.
- Add the HMI device to the machine project's hardware tree, selecting the exact panel model.
- Open the HMI application node inside SoMachine and build it; clear any validation errors before attempting a transfer, because no communication fix will move an application that will not build.
- In the transfer dialog, select the HMI as the destination — a controller download never carries the screens with it.
- Download, then confirm the new screens appear on the physical panel.
Overwriting the panel takes the operator screens down, so keep a copy of the running application and do the transfer in a planned stop.
Decision: this integrated route is the answer for PLC-plus-HMI machines licensed through SoMachine.
When do you actually need a separate Vijeo Designer license? #
You need one when the required workflow is standalone HMI engineering in Vijeo Designer itself, with no SoMachine machine project involved: the SoMachine entitlement covers HMI modules inside its integrated projects, while standalone-only HMI programming is exactly what the separate Vijeo Designer 6.2 license entitles.
The decisions per case:
- Machine programmed PLC-plus-HMI inside SoMachine: no separate Vijeo Designer license is needed; work integrated.
- HMI-only engineering in standalone Vijeo Designer: the Vijeo Designer license is required, and the 6.2 range exists as a single license for one workstation and as a group license covering multiple seats, so match the type to the seat count.
- Activation broken or entitlement unclear: Schneider Electric or an authorized distributor handles purchase, activation repair, transfer and recovery; bring the installed versions, the Help > About edition text and the exact message.
Decision: if standalone HMI work is occasional, the integrated route costs nothing extra; buy the standalone license only when standalone is the workflow you must keep.
What does the Limited or Trial edition actually restrict? #
The limit is functional, not a 30-day clock: the unlicensed installation keeps running indefinitely, and what actually stops you is the target download, which the unlicensed standalone session refuses while the session itself still opens and edits projects.
Where the edition comes from is decided at installation time. Per Schneider Electric's installation documentation for Vijeo Designer, the wizard run from the DVD or ISO asks for a reference number and a serial number: enter both and the software installs in fully licensed mode; skip them and it lands in demo/trial/limited mode, which is the mode behind the Limited Edition line in Help > About. The edition you get is set by those two numbers at install time and by the licenses activated afterwards.
Decision: if you own a Vijeo Designer license, install or repair with the reference and serial numbers through official channels; if you do not, the integrated SoMachine route is the licensed path you already have.
What if the HMI download still fails from SoMachine? #
Then licensing is off the table and the message decides the branch: record the exact text and the stage where it appears, because a build error, a refused connection and a completed transfer onto the wrong target are three different faults with three different fixes.
- Fails during build or validation: correct the reported project errors and check the configured target against the physical panel model. If the project itself rejects the panel family, target activation is a separate step in 6.2, covered in activating the XBTOT target family in Vijeo Designer 6.2.
- Panel detected but the transfer is refused: compare the configured address with the panel's, then the transfer settings and the physical connection; the gap between a visible device and a working transfer is covered in why an HMI is detected but project download fails.
- Transfer completes but the screens are wrong: verify which application sits on which target, because the controller and the HMI remain separate deployment targets even inside one machine project.
Decision per case: build error, fix the project; detected-but-refused, fix the communication path; completed-but-wrong, fix the destination selection. None of these three is a licensing fault, and none is solved by reinstalling the software.
Questions asked
I received my SoMachine license by email, so is that why the HMI download fails?
No. An email-delivered license that activated correctly is a legitimate entitlement, and nothing about its delivery causes this fault. The cause is scope: that license covers the SoMachine environment and the HMI modules inside its machine projects, while the standalone Vijeo Designer 6.2 session you launched checks for a Vijeo Designer license that was never installed on the workstation.
How do I move a Vijeo Designer 6.2 license to another PC?
Schneider Electric documents a transfer procedure built around the Vijeo Designer License Manager tool: the license is moved off the old workstation onto a USB flash drive and imported on the new one. Use that documented transfer when a workstation is replaced, instead of reinstalling the software and expecting the activation to reappear on its own.
Is Vijeo Designer 6.2 licensed per seat or per group?
Both shapes exist in the 6.2 range: a single license for one workstation and a group license covering multiple seats, so match the license type to how many engineers need standalone Vijeo Designer access. Either entitlement applies to standalone Vijeo Designer use only; it does not extend what the SoMachine environment covers.
Who fixes an activation that is broken or an entitlement that does not match?
Schneider Electric or an authorized distributor. Before contacting them, collect three things: the installed software versions, the edition text shown in the Help > About dialog, and the exact wording of the failure message. Activation repair, license transfer and recovery go through those official channels; the integrated SoMachine route remains the working path for panel downloads meanwhile.