IMDTouchKnowledge BaseShop main store

Selection guide

What decides a WinCC replacement on a Profibus DP network

HMI and touchscreens Published 10 min read

Short answer

A gateway alone does not make a WinCC replacement compatible on Profibus DP. The decision comes from two documented checks: the new supervisory package must have a driver for the gateway's Ethernet application protocol, and the gateway's Profibus role — DP slave or master — must match the existing bus configuration. Define the data contract — mapping, byte order, scaling, write permissions, command acknowledgment — before any screen is built.

On this page
  1. The two checks that decide the replacement
  2. What the gateway is on the Profibus side
  3. The Ethernet side: protocol, not cable
  4. The data contract you write before any screen
  5. Configurable package or custom application
  6. Example: the update delay behind one operator value at a 250 ms scan
  7. The decision, in order
  8. Questions asked

A Profibus-to-Ethernet gateway does not, by itself, make a new supervisory package a working replacement for a WinCC station. Two documented checks decide it: the replacement package must ship a driver for the gateway's Ethernet application protocol, and the gateway's Profibus role — DP slave or DP master — must match the bus configuration you already run. Align those two and write the data contract before anyone builds a screen, and the migration is ordinary engineering; skip one and the gateway is an expensive cable. This article gives you the checks in the order that is cheapest to fail, a timing example with real numbers, and the decision for both routes: a configurable SCADA package or a purpose-built application.

The two checks that decide the replacement #

A WinCC station is more than screens. It carries the communication drivers, alarm handling, archiving and command logic the operators actually use, and all of it has to be replaced while the Profibus side of the network stays as it is. PROFIBUS DP, the IEC 61158 type 3 fieldbus, exchanges cyclic data between masters and the slaves configured to them. A gateway changes only the transport into the supervisory PC; it does not create compatibility with any package you point at it. Four checks decide the selection:

Check What must be true Where you verify it
Ethernet application protocol The replacement package documents a driver for the exact protocol the gateway speaks on the Ethernet side: EtherNet/IP, Modbus TCP, OPC UA or a PROFINET role The SCADA vendor's driver list, for your runtime version and operating system
Profibus role The gateway's role, DP slave or DP master, matches the existing bus: a slave joins the existing master's configuration, a master takes over the slaves The gateway datasheet, read against your current bus configuration
Data contract Every value and command has a defined location, length, type, byte order, scaling, validity and write permission, with controller acknowledgment for commands A document you write before screen work starts
Operating system The runtime, the engineering editor and the gateway driver are each documented for the target OS The vendor's support matrix for the exact release

A failed row is not a configuration problem. It is a different package or a different gateway.

What the gateway is on the Profibus side #

Read the Profibus role from the datasheet before anything else, because it decides who owns the data.

As a DP slave, the gateway holds one configured exchange with the existing master — in a machine line, normally the PLC. Every value the operators need is copied into that exchange by the PLC program, and every command is copied back out; the SCADA never addresses the bus itself. If touching the PLC program is off the table, a slave-role gateway is the wrong purchase.

As a DP master, the gateway manages the Profibus slaves itself and bridges the collected I/O to the Ethernet side. One documented EtherNet/IP-to-PROFIBUS master gateway works exactly this way, connecting DP slave devices to an EtherNet/IP control system through an internal I/O mapping, and capacity in this class is generous: one Profibus-DP master gateway line supports up to 125 slaves at bus rates up to 12 Mbit/s, with the Profibus configuration defined in its own tool, NetTool-PB. A second master is still a bus reconfiguration, not a plug-in: someone now owns the slave list, the exchange lengths and the bus parameters the old configuration owned, and that ownership is written down before the gateway is connected.

Datasheets state the role up front, so use them as the selection filter. The PLX51-PBM gateway, for example, is documented as PROFIBUS master or slave to EtherNet/IP, Modbus TCP or Modbus serial, configured in the vendor's PLX50 Configuration Utility. Role, protocol and configuration tool are all selection inputs; read them before you shortlist any software.

The gateway also retires the Profibus interface that lived inside the old station. If the current PC carries a bus card — the CP5611-class PCI card being the common WinCC case — the new PC needs no bus interface at all, only its onboard Ethernet port; the separate problem of replacing such a card in a modern PC is covered in Replacing a CP5611 PCI Card in a New WinCC Station.

Decision: if the existing PLC master stays in charge, choose a slave-role gateway and budget the PLC-program changes; if the gateway should own the bus, treat the change as a reconfiguration with a documented slave list. The configuration work that follows either choice is the same job described in Configure a PROFIBUS to EtherNet/IP gateway for HMI and PLC.

The Ethernet side: protocol, not cable #

Ethernet carries the packets; it does not say what they mean. The application protocol defines addressing, data types, connection handling and error reporting, and the SCADA needs a driver for that protocol, not for 'Ethernet'. Gateway datasheets name the protocol plainly — one family offers EtherNet/IP, Modbus TCP or Modbus serial on the network side — and a PROFINET route exists as well, tightening the requirement further: behind a Profibus-to-PROFINET gateway the supervisory package must take a PROFINET IO controller or IO device role, which fewer packages document than Modbus TCP.

The protocol name on the gateway box is not the driver. The SCADA vendor has to document the driver for that exact protocol, on your runtime version, on your operating system, in the license tier you hold — drivers are sometimes sold as options, so confirm inclusion in writing. When the driver list comes up short, the fix is another package or another gateway, in that order of disruption; the failure mode and the way out are the same as for any missing PLC driver: When the HMI Software Has No Driver for Your PLC.

Dropping Windows is a separate requirement that fails separately. Runs on Linux has to be true for the runtime, the engineering editor, the gateway driver and every library the package loads — the editor alone proves nothing, and a package that previews screens on a Linux desktop has not passed the check. Read OS support per component, per release, in the vendor's matrix; the commissioning-day version of this failure is described in Gateway setup when a network scan finds no Linux runtime.

The data contract you write before any screen #

The data contract is a table of every supervisory value and command, written before the first screen: location in the exchange, length, type, byte order, scaling and engineering units, update behavior, validity indication, and write permission per side. Both ends interpret the same bytes, so both ends work from this page, and the PLC-side owner signs it.

The items that bite in practice:

  • Byte order and word order differ between controllers and PCs. Prove the mapping with one known 16-bit and one known 32-bit value before trusting anything else.
  • Scaling: state where raw counts become engineering units, and keep exactly one place that does the conversion.
  • Validity: define what the screen shows when the gateway reports bad quality or a DP slave drops out. A stale value is marked as stale, never displayed as current.
  • Writes: the contract marks which bytes the SCADA may write, and the controller acknowledges every command. Without an acknowledgment path the operator sees a change that never took effect. Reads fail visibly and early; writes fail silently and exactly when they matter.

Decision: no screen work starts until this table exists and both sides have signed it.

Configurable package or custom application #

Two routes replace the station: a configurable SCADA package with a documented gateway driver, or an application you build. Plants run both successfully; the difference is who owns what, permanently.

Criterion Configurable SCADA package Custom application
Gateway communication Vendor-documented driver for the gateway's exact protocol You implement, test and maintain the protocol client
Operator functions Screens, alarms, trends and user rights configured, not coded Every function implemented and tested by you
OS support Vendor matrix for runtime, editor and drivers, per release Your framework, libraries, deployment and service operation
Licensing Development, runtime, driver and capacity terms, per station Tool and library terms, plus redistribution if it leaves your control
Maintenance Vendor-supported releases and project compatibility Your source, builds, tests and documentation, indefinitely

The custom route is real: some integrators build complete supervisions with their own protocol drivers precisely to drop per-runtime licensing and to link ERP systems, using Visual Studio, Delphi or VB against a gateway's Ethernet interface. Two facts decide whether that route is yours. First, tool names establish nothing about Linux deployment — that question is answered by the framework, the communication library, the installer and the service model you actually ship. Second, the application now owns connection recovery, alarm semantics, logging, security and long-term maintenance; if nobody on your team will own those in five years, the answer is the package. When you do go custom, the mechanics of a PC application exchanging data with controller memory are a project of their own: Exchanging HMI memory data with a custom PC application.

Whichever route you take, the new supervision runs on a computer mounted where the old station was, and that is the moment to specify the hardware: the runtime, the gateway driver and every screen live on one of the industrial panel PCs that replaces the WinCC operator position, in the enclosure rating the location demands.

Example: the update delay behind one operator value at a 250 ms scan #

One number decides whether a gateway's conversion speed belongs in the purchase decision at all. Here is the arithmetic for a single operator value.

Inputs:

  • Gateway I/O conversion: below 20 ms — the documented bound on an adapter that integrates a single PROFIBUS DP slave into an EtherNet/IP network; your gateway's datasheet states its own figure.
  • Driver scan period: 250 ms — an example setting you make in the supervisory package's driver for how often it reads the gateway's image; illustrative here.
  • Not counted: the configured DP bus cycle and the screen refresh, which add on top of these two terms.

Rule: worst case, an operator sees a controller change after one conversion plus one full scan period — the change is converted first, then picked up at the next scan, and it can land just after one.

Arithmetic:

  • Staleness at the example setting: 250 ms + 20 ms = 270 ms. The conversion's share of that delay: 20 ms ÷ 250 ms = 0.08, an 8% share.
  • With the scan tightened to 100 ms: 100 ms + 20 ms = 120 ms, and the share rises to 20 ms ÷ 100 ms = 20%.

Result: the scan dominates at operator rates — the conversion is a small share of the delay at the example setting and a fifth of it even with the scan halved.

Decision: buy the update rate with the scan period, which is a software setting, not with a faster gateway. A conversion under about 10% of the scan period is not a selection criterion; it enters the decision only if you set a scan period near the conversion bound, which no operator screen on a PROFIBUS DP supervision network needs.

The decision, in order #

Run the selection in this order, so the cheapest failure comes first:

  1. Document the existing bus before anything powers down: who is master, the slave list, each device's exchange, and which functions live in the PLC versus the old station.
  2. Read the gateway datasheet for role, Ethernet protocol, capacity and configuration tool, and match the role to the bus — a slave joins, a master reconfigures.
  3. Demand the SCADA vendor's driver documentation for that exact protocol, runtime version and operating system. No documented driver, no deal, whatever the demos look like.
  4. Write the data contract and get the PLC-side owner to sign it: mapping, byte order, scaling, validity, write permissions, command acknowledgment.
  5. Prove it on an isolated bench with verified test tags: reads first, then one harmless write traced end to end to its acknowledgment, then a pulled cable to watch data quality, recovery and what the screens show.
  6. Cut over with a rollback path: keep the old station installed and working as the reference until the new supervision passes acceptance on the hardware it will actually run on.

Two decisions fall out of the checks. For a team that will not maintain its own code: a configurable SCADA package with a documented driver for the gateway's exact Ethernet protocol, a gateway role that matches the bus, and Linux only if the runtime, editor and driver are all documented for it. For a team that builds and maintains software: a custom application behind a slave-role gateway, with the data contract and the acknowledgment paths written before the first screen exists.

One line of safety through all of it: machine sequencing, interlocks and protective functions stay in the controllers, and the supervisory layer must be able to fail or vanish without changing how the machine stops.

Questions asked

Does the old WinCC project convert into the new package?

Not by itself, and the gateway does not change that. Screens, alarms, trends and scripts were authored in WinCC's own formats and carry over only where the new vendor documents a WinCC import. Plan the migration as a rebuild of the operator functions against the data contract, and keep the old station running as the working reference until the new supervision passes acceptance on the intended hardware.

Can one gateway feed both the new supervision and a data historian?

Only if its documentation lists simultaneous protocols or multiple Ethernet sessions for the mode you need. Some gateways offer EtherNet/IP, Modbus TCP or Modbus serial as alternatives you configure, which means one network protocol per unit unless parallel operation is documented. If the historian can subscribe to the same protocol through a switch, the problem disappears; otherwise add a second gateway or route the data through the SCADA's own archive export.

Do I still need a Profibus card in the new PC?

No. That is the point of the gateway: the PC uses its onboard Ethernet port and the gateway handles the Profibus side. Documented master-gateway capacity — up to 125 slaves at bus rates up to 12 Mbit/s — is far beyond what a supervision station reads, so capacity does not push you back to a bus card either. The card disappears from the architecture along with the slot it needed.

What should I collect from the Profibus side before the old station is switched off?

The GSD files for every DP slave on the bus, the configured exchange lengths, the bus parameters and profile the master uses, and the PLC project that owns sequencing. A slave-role gateway needs the PLC program updated to fill its exchange; a master-role gateway needs the full slave list to rebuild the configuration in its own tool. None of this lives in the WinCC project.

Keep reading

  • Troubleshooting

    Configure a PROFIBUS to EtherNet/IP gateway for HMI and PLC

    Selecting PROFIBUS-DP Slave and EtherNet/IP Scanner in SYCON.net assigns only the gateway's own roles on each network. The link still needs the MP277 configured as PROFIBUS DP master from the gateway's GSD description, and the SLC 5/05 configured as the documented target of that scanner connection. Verify each side's status separately before mapping data; PC recognition of the gateway proves none of it.

    HMI and touchscreens

  • How-to

    Replacing a CP5611 PCI Card in a New WinCC Station

    Yes. Keep the project's channel, connection and tag addresses exactly as they are and change only the PC-side interface: install a USB or PCI Express PROFIBUS adapter the channel supports, then select it in SIMATIC PG/PC Interface and in the WinCC connection. A converter on the Ethernet port is the one option that can force tag rework, so leave it for distance or shared-access cases.

    HMI and touchscreens

  • Troubleshooting

    Connecting an HMI to an S7-400 across Ethernet and PROFIBUS

    WinCC flexible will never list an Ethernet-to-PROFIBUS connection, because an HMI connection definition binds one driver to one interface on the panel. Your three-segment path works only if the device between the two media converts the S7 protocol, and a Wi-Fi access point and router convert nothing. Add a documented Ethernet-to-PROFIBUS gateway at the router position, or change one segment; with the panel PROFIBUS-only, the gateway is the branch that fits.

    HMI and touchscreens