Troubleshooting
What WinCC V11 needs to run a PC as an HMI
Short answer
WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.
On this page
Your V11 SP2 workstation will not run the PC as an HMI because only the engineering software is on it. STEP 7 V11 Professional and WinCC V11 Professional configure the project and download it to the KTP 600 Basic, but a PC becomes a runtime station only after WinCC Runtime Advanced or WinCC RT Professional is installed and licensed on it. No extra download is needed: both runtime products come on the same TIA Portal V11 SP2 delivery you already own. When the setup stops at Mandatory sepro not found: Sebu_winccv11, the fault is the machine, not a missing package: this Windows 7 Ultimate 64-bit image carries six classic SIMATIC releases the WinCC V11 compatibility list does not clear beside V11 SP2. Remove them or rebuild the image, install the runtime, and put a runtime license where the PC can find it.
Why the PC is not a runtime station yet #
Engineering and runtime are separate products that share one project file. TIA Portal V11 with STEP 7 V11 and WinCC V11 engineering builds the project, compiles it and downloads it to a panel. Running that project on the PC needs a runtime product installed on that PC:
- WinCC Runtime Advanced: the panel-class runtime. It reproduces panel operation on a single PC station and is the right product for a project built against a KTP 600 Basic.
- WinCC RT Professional: the SCADA-class runtime, for stations that archive at plant scale and serve other stations.
The machine needs three things, and this installation has only the engineering side: the runtime component selected and installed from the V11 delivery, a runtime license that Automation License Manager can find at every start, and a station in the project configured as a PC runtime station. The engineering license that activated STEP 7 covers none of that, which is why the runtime entry is missing or dead on the PC. The same separation trips up later versions, and the V13 case is described in why the WinCC V13 Professional runtime command stays disabled.
What each WinCC V11 edition installs #
| Package | Configures | PC runtime it delivers |
|---|---|---|
| WinCC V11 Basic | Basic Panels | none |
| WinCC V11 Comfort | all panel classes, mobile panels included | none |
| WinCC V11 Advanced | panels and PC runtime stations | WinCC Runtime Advanced |
| WinCC V11 Professional | panels, PC runtime stations and SCADA stations | WinCC Runtime Advanced and WinCC RT Professional |
You hold Professional, so both runtimes are on your media and the choice is only which one the station needs. A PC that replaces the KTP 600 Basic as the local operator station takes Runtime Advanced; a supervising station with plant-scale archiving and clients takes RT Professional. Note the trap: a WinCC Professional line in the installed-software list proves engineering, not runtime, which is exactly the question whether a WinCC Professional entry means SCADA runtime is installed answers for the later versions.
The sepro error and the compatibility list #
Mandatory sepro not found: Sebu_winccv11 is the V11 setup refusing to continue because a required V11 entry it checks for is missing from the machine's software state. The cause on this image is not a missing download; it is the stack the machine already carries.
The inventory from the fault lists six classic-generation packages beside the two TIA V11 packages, all on Windows 7 Ultimate 64-bit: WinCC V7.0 SP3, STEP 7 Professional V5.5 SP2, Soft Starter ES 2007 SP4, F-Config V55 SP9 U1, PC Access SP6 and STEP 7 MicroWIN V4.0 SP9. The classic and TIA generations share installer plumbing, and combinations beyond the documented ones leave the V11 setup facing a software state it cannot verify, so the check fails mid-install. This is the same failure family as why a STEP 7 V5.7 SP1 setup stops on Windows 10 Pro: software released against a documented platform list refuses to complete outside it.
The compatibility list published for SIMATIC WinCC V11 is the arbiter. Work through the machine item by item:
- Operating system edition and patch level, matched to your exact V11 service pack.
- Every SIMATIC package on the image, at its exact version, against the co-installable products the list allows.
- Service-pack order: V11 base first, then SP1, then SP2. The SP2 package upgrades existing V11 and V11 SP1 installations; it is not a product in its own right.
- License state: every container Automation License Manager can see, with the runtime license present.
A missing license entry is restored through Automation License Manager using your original license certificates or the vendor's support channel, never by copying authorization files between machines.
Recover the machine in this order #
- Open the compatibility list for WinCC V11 SP2 and mark every package on the image the list does not clear. On this machine that is the six classic releases; anything the list explicitly allows may stay.
- Uninstall the off-list packages with their own uninstallers, not just the entry in Programs and Features, and reboot between groups. Let each uninstaller report success before you start the next.
- If the image still fights you, rebuild it. A fresh Windows 7 Ultimate 64-bit installation with only TIA Portal V11 plus SP1 and SP2 applied in order validates faster than uninstall archaeology on a shared bench PC.
- Run the WinCC V11 SP2 setup from the original media and select the runtime the station needs: WinCC Runtime Advanced for the panel-class project, WinCC RT Professional for SCADA.
- Open Automation License Manager and put the matching runtime license on a container the PC reaches at every start. The move from a USB key onto the machine's own storage follows the steps in how a WinCC license transfers between a USB key and the hard disk.
- In the project, select the KTP station, use the Change device command to swap it for the PC runtime station and recompile. Start the runtime and confirm tag values track the PLC before the station faces the machine.
If the sepro check still fails on a clean, list-compliant machine, the remaining suspect is the license state: take the exact error text and your license certificates to the vendor's support channel.
Worked example: count the image, then decide #
Count the SIMATIC packages installed on this image: six classic-generation releases and two TIA V11 packages. Six plus two is eight installed packages, and six of the eight sit outside the TIA generation: 6 / 8 = 0.75, so 75 percent of the SIMATIC software on the machine belongs to a generation the V11 setup cannot verify against. The rule the compatibility list gives you is binary: a package it does not clear leaves the image before the runtime install. Six uninstall-and-reboot cycles on a shared image, each able to leave shared plumbing half-removed, versus one clean operating system build and one documented V11 install, take the rebuild. The deciding number is the count of off-list packages, and any value above zero points the same way.
Verify the runtime before it faces the machine #
- Compile the project for the PC runtime station without errors, then start the runtime from the entry the setup places in the Windows start menu.
- Confirm live tag values track the real PLC or PLCSIM, then power-cycle the PC once to prove the license is found again on a cold start. A runtime that dies after a restart almost always has its license on a USB key that is not plugged in.
- Walk every screen the operator uses after the device swap, because panel and PC runtime render some elements differently; alarms and recipes need the same pass.
- Then decide what the station physically is. If this PC now sits at the machine as the operator interface, an office tower and a consumer monitor are the parts that fail first, and that is the point where a move to industrial panel PCs puts the runtime on hardware built for the cabinet instead of the desk.
One safety note: the PC runtime is an operating interface, never a safety layer. The machine's emergency stop and interlocks stay wired outside it, and no stop or start function moves into HMI screens.
The decision for each case #
- The runtime entry is missing but no installer ever complained: nothing is broken. Install WinCC Runtime Advanced, or WinCC RT Professional for SCADA, from your V11 SP2 delivery and license it.
- The setup stops at
Mandatory sepro not found: Sebu_winccv11: the image is at fault. Clear the off-list packages or rebuild, reinstall V11 SP2, then add the runtime. - The station must archive at plant scale or serve clients: WinCC RT Professional, not Runtime Advanced.
- Clean machine, list-compliant image, license still not found: Automation License Manager with the original certificates, then the vendor's support channel.
Questions asked
Do I need a separate license to run the PC as an HMI with WinCC V11?
Yes. The engineering license that activates STEP 7 V11 and WinCC V11 covers configuration and download only. A PC station running panel-class projects needs a WinCC Runtime Advanced license, and SCADA functions need WinCC RT Professional licenses. Automation License Manager checks the license at every runtime start, so keep it on a container the PC can always reach: a USB key left in a drawer stops the runtime cold.
Does the KTP 600 Basic project run unchanged on WinCC Runtime Advanced?
Not unchanged. The station is configured as a Basic Panel, so you swap it for the PC runtime station with the Change device command and recompile before the runtime can open it. Tags, connections and the screen structure carry over, but the panel and the PC runtime render some elements differently, so walk every screen on the bench before the station goes on the machine.
What does the sepro text in the error mean?
Sepro is the V11 installer internal name for a required software entry it verifies before copying files. The message Mandatory sepro not found: Sebu_winccv11 means the WinCC V11 setup could not find the required V11 entry it needs before continuing. Treat it as an installation-state fault, not a missing download: it appears when the installed software does not match the compatibility list, and it clears on a compliant image.
Can engineering and runtime sit on the same PC?
Yes, on an image the compatibility list allows. TIA Portal V11 SP2 engineering and WinCC Runtime Advanced or RT Professional coexist on one supported Windows installation, and a bench often works that way. A machine-facing runtime station should run the operator application alone, though, so a setup wizard, an update or a developer test cannot blank the screen while the process runs.
Which Windows edition does TIA Portal V11 SP2 need?
Match the exact edition against the compatibility list published for that service pack; the machine in this fault ran Windows 7 Ultimate 64-bit. Each TIA Portal generation publishes its own supported list, and the current documentation names Windows 10 64-bit editions for recent releases, so never carry a list entry from one version level to the next.
When is WinCC RT Professional the right product instead of Runtime Advanced?
Runtime Advanced covers a single PC station running a panel-class project: screens, alarms, recipes and logging at panel scale. RT Professional adds SCADA behavior such as archiving at plant scale, server and client stations and larger configurations. If the PC only replaces the KTP 600 Basic as the local operator interface, Runtime Advanced is the product; choose RT Professional when the PC supervises several machines or serves other stations.