When OPC tags count as PowerTags in WinCC flexible 2008

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Tags exposed by the WinCC flexible 2008 OPC server cost no PowerTags: the server publishes tags the project already has, whatever reads them. Only the client direction spends the license — every tag created in the HMI tag table on a SIMATIC NET OPC client connection is connected and non-internal, so it counts against the 128-PowerTag limit.

On this page
  1. The direction rule decides the count
  2. What counts as a PowerTag
  3. Serving tags through the OPC server
  4. Reading SIMATIC NET OPC as the client
  5. Checking the count before deployment
  6. Worked example: 96 connected PLC tags plus 40 OPC client tags against a 128-PowerTag license
  7. The decision for each direction
  8. Questions asked

Yes, the tags can go on OPC, and whether they cost PowerTags depends entirely on direction. Tags exposed by the WinCC flexible 2008 OPC server and read by any OPC client add no PowerTags: the server hands out references to tags the project already has, so nothing new is created. Tags you create in the HMI tag table on an OPC client connection are new connected tags, and each one counts against the runtime license. Below is the rule, the two configurations that follow from it, the project report that gives you the exact count, and a worked check against the runtime license behind this case.

The direction rule decides the count #

OPC sits on one of two sides. With the runtime as OPC server, WinCC flexible publishes the project's own HMI tags and clients elsewhere on the network read them. With the runtime as OPC client, the runtime reaches out through a client channel and consumes data from another OPC server. The license only sees tags created inside the project, so the direction, not the protocol, decides the cost.

Runtime role What you configure Effect on the PowerTag count
OPC server Activate OPC in the Runtime settings; the configured HMI tags are then visible on the server None: reads of existing HMI tags create no tags in the project
OPC client Create a connection to the OPC server, then create tags in the HMI tag table on that connection Every connected, non-internal tag counts as a PowerTag

The asymmetry is easy to trip over. A tag the runtime already holds can be published to the whole plant through the server at no license cost. Declaring the same value again on a client connection creates a second tag inside your own project, and that second tag is what the license counts.

What counts as a PowerTag #

A PowerTag is a tag created in the HMI tag table of the WinCC flexible project that is not internal, meaning a tag with a connection behind it. Internal tags carry screen-local values and scratch results; they have no connection, so they never enter the count. Everything connected does: PLC tags, tags on any other driver, and tags on an OPC client channel are all PowerTags.

The count belongs to the runtime. The engineering seat that builds and edits the project consumes no PowerTags; the runtime license on the target PC is sold by PowerTag count, and the license in the case this article answers allows 128.

Serving tags through the OPC server #

This is the direction the setup in question needs: WinCC flexible Runtime and the SIMATIC NET OPC server on one PC, with network clients reading the runtime's tags. It is a PC project, selected as PC > WinCC flexible Runtime under Project > New, and the runtime side of that project type is covered in Running a WinCC flexible 2008 Project in PC runtime.

Two things put the server to work. Activate OPC in the Runtime settings of the project: from that moment the configured HMI tags are visible on the runtime's OPC server for clients to browse and read. And hold the separate license for the OPC server function, because on WinCC flexible 2008 the server role is licensed in addition to the runtime license; match that license to the installed version before the machine goes into production.

The PowerTag ledger does not move in this direction. Publishing costs nothing because the server never creates a tag; it only exposes the ones the project already holds.

Reading SIMATIC NET OPC as the client #

The client direction is the one that spends the license. When the runtime must consume values that live behind another OPC server, such as a gateway, a legacy device or another machine's data, you create a connection to that OPC server in the project and then create every value you need in the HMI tag table on that connection. Each of those tags has a connection and is not internal, so each one is a PowerTag, exactly as if it sat on a PLC driver. The transport being OPC changes nothing about that.

So sort the values before you route them. A value the runtime already holds as an HMI tag goes out through the server, where it costs nothing. A value that only exists on the far side of the OPC server has to come in as a client tag, and each of those costs one PowerTag against the license.

Checking the count before deployment #

The project tells you its own number. Generate the project and read the used PowerTags from the generation report; that figure is the licensing check, so re-run it after every batch of added or deleted connected tags instead of estimating by hand. The exact license article numbers depend on version and delivery, so match them in the licensing documentation for the installed software rather than ordering from memory.

If the report lands above the license, the honest levers are the ones that work: delete connected tags that no screen or script references any more, or step the runtime license up to a higher PowerTag count, which is the tier structure described in Runtime tag license tiers for an HMI panel PC. Which numbers feed the license choice at all is laid out in Where tag count matters in a WinCC flexible license choice. An upgrade license also exists that moves a WinCC flexible 2008 runtime onto WinCC Runtime, and with 2008 this old the migration belongs in the same decision as the license; WinCC flexible 2008 lifecycle and the Runtime Advanced license maps what is still supported and what the Runtime Advanced license covers.

Worked example: 96 connected PLC tags plus 40 OPC client tags against a 128-PowerTag license #

This is an example project sized to the setup above, not a measurement from a real machine.

Inputs:

  • Runtime license limited to 128 PowerTags, as in the setup this article answers.
  • 96 tags in the HMI tag table on the PLC connection: example input.
  • 40 tags in the HMI tag table on the OPC client connection: example input.
  • 22 internal tags for screen-local values: example input.

Rule in words: a PowerTag is any HMI tag table entry that is not internal, so the licensed figure is the sum of connected tags across all connections; internal tags and OPC reads of server-exposed tags add nothing.

Arithmetic: 96 connected PLC tags + 40 connected OPC client tags = 136 PowerTags, and the 22 internal tags stay out of the sum. 136 - 128 = 8, so the project stands 8 PowerTags above the cap.

Decision: the license is short by 8 PowerTags, so delete at least 8 connected tags (OPC client tags and PLC tags weigh the same here) or hold a runtime license with a higher PowerTag count before generating for deployment. Turn the same 40 values into server reads instead and the sum is 96 + 0 = 96 PowerTags, which the license covers with 32 to spare; the extra item to hold in that direction is the OPC server license, not a larger runtime license.

The decision for each direction #

Two cases, two decisions. If other systems should read the runtime's tags, serve them: activate OPC in the Runtime settings, hold the separate OPC server license, and leave the PowerTag count alone, because it does not move when clients read. If the runtime should consume tags that live behind a SIMATIC NET OPC server, treat them like PLC tags: every connected tag created in the HMI tag table on the client channel is a PowerTag against the runtime license, and the generation report is the number to trust. Size the license to the real count, because the fix for standing above the cap is a higher tier or fewer connected tags, never a sidestep of the license check.

Questions asked

Does it matter how many OPC clients connect to the runtime's OPC server?

No. The number of clients is invisible to the PowerTag ledger: the server publishes tags that already exist in the project, so a read from one client or from thirty at once creates no tag and moves no count. The count only grows when a connected tag is added to the HMI tag table in the project itself.

Does the engineering license used to build the project cover the runtime PowerTags?

No. WinCC flexible Advanced is the engineering license: it opens and edits the project but does not license Runtime. Runtime needs its own license, sized in PowerTags, and the OPC server function is licensed separately on top of that. Check all three when a machine changes hands.

What does a PC runtime show when the license tier does not cover the project?

The licensing documentation for WinCC describes the missing-license indicator on PC-based runtime as a message window that reappears about every 10 minutes while the runtime runs. A project with more connected tags than the license covers trips that indicator, so read the PowerTags figure from the generation report before deploying rather than discovering it on the machine.

If WinCC flexible Runtime and the SIMATIC NET OPC server run on the same PC, do client-channel tags still count?

Yes. Running both on one machine changes nothing about the rule: a tag created in the HMI tag table on the OPC client connection is connected and non-internal, so it is a PowerTag even though the data never leaves the PC. Only the server direction is free of extra PowerTags.

Keep reading

  • Explainer

    Reading raw PLC tags as diagnostics in WinCC over OPC

    No. An OPC server does not limit WinCC to slave diagnostics: WinCC reads every item the server publishes, process tags included. A raw tag is only an undecoded value — match its type to the server item, decode packed words at the tag level, and drive configured alarms and displays instead of C scripts in each graphic object.

    HMI and touchscreens

  • How-to

    How to Simulate a PLC Behind WinCC Flexible 2008 SP3

    WinCC Flexible 2008 SP3 simulation runs your screens on the engineering PC and executes no PLC program, so give every animated object a real data source: STEP 7 with PLCSIM for an S7-300 test, PC Access or KepServerEx OPC for an S7-200, or a PC Adapter USB cable to the physical controller. Then wire M0.0 in parallel with I0.0, M0.1 in series as the stop, and animate the motor symbol on Q0.0, not on the command bit.

    HMI and touchscreens

  • How-to

    How to Exchange Recipe Data Records Between an HMI and a PLC

    Bind every recipe element to an external tag whose data type and byte offset match the PLC data block, then move whole records with the system functions set data record to PLC and get data record from PLC. The records live in the panel's storage and the PLC holds only the current working values. Set tag synchronization so values move only on an explicit transfer, and prove the exchange with five checks ending in a delete test.

    HMI and touchscreens

What counts against the TP1200 Comfort PowerTag 2048 limit